{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1155-6AA01-7BN0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1155-6AA01-7BN0","canonicalUrl":"https://aoctrl.com/siemens/6AG1155-6AA01-7BN0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1155-6AA01-7BN0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC ET 200AL interface module IM 155-6 PN BA, 6AG1155-6AA01-7BN0, PROFINET IRT, 2 RJ45 ports, bus adapter, 24 V DC, 1.9 W.","salesMarkdown":"## PROFINET interface for ET 200AL – IRT and integrated switch The 6AG1155-6AA01-7BN0: Network loading class 2 and prioritised startup are on board; media redundancy (MRP) is supported for ring topologies. The interface handles I&M data 0–3, SNMP, LLDP, and shared device operation, giving a controls integrator full diagnostic reach without extra gateways. ## I²t and inrush – supply coordination point The module draws a typical 1.9 W at 24 V DC, but the inrush current hits a peak of 3.7 A and carries an I²t of 0.09 A²·s. That energy number matters when sizing the upstream 24 V supply – a small power supply with foldback current limiting can trip on that inrush if the I²t exceeds the supply's dynamic response. For a cabinet with multiple IM 155s, sum the I²t and verify the supply's inrush headroom; the 3.7 A peak lasts only milliseconds but a weakly buffered supply may drop out.","metaTitle":"Siemens 6AG1155-6AA01-7BN0 IM 155-6 PN BA, PROFINET IRT","metaDescription":"Siemens 6AG1155-6AA01-7BN0 interface module for ET 200AL, PROFINET IRT with 250 µs send cycles, 2-port switch, current production. I²t 0.09 A²·s.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"I2t":"0.09 A²·s","IRT":"Yes; with send cycles of between 250 µs and 4 ms in increments of 125 µs","MRP":"Yes","LLDP":"Yes","MRPD":"No","SNMP":"Yes","Depth":"74 mm","Width":"50 mm","title":"6AG1155-6AA01-7BN0","Alarms":"Yes","Height":"117 mm","TCP/IP":"Yes","10 Mbps":"Yes; for Ethernet services","RUN LED":"Yes; green LED","100 Mbps":"Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)","I&M data":"Yes; I&M0 to I&M3","ERROR LED":"Yes; red LED","MAINT LED":"Yes; Yellow LED","PROFIenergy":"Yes","Via Dataset":"Yes","description":"SIPLUS ET 200SP IM155-6PN ST BA based on 6ES7155-6AA01-0BN0 with conformal coating, -40…+70 °C, bundle PROFINET IM, 1 slot for BusAdapter, max. 32 I/O modules and 16 ET 200AL modules, single hot swap, bundle consists of: interface module (6AG1155-6AU01-7BN0), server module (6AG1193-6PA00-7AA0), BusAdapter BA 2xRJ45 (6AG1193-6AR00-7AA0)","Autocrossing":"Yes","Shared device":"Yes","Security level":"According to Security Level 1 Test Cases V1.1.1","via BU/BA Send":"Yes; + 16 ET 200AL modules","Autonegotiation":"Yes","Number of ports":"2","Weight, approx.":"190 g; IM 155-6 PN BA with 2x RJ45 ports and server module","lifecycle_stage":"current","Isochronous mode":"No","Media redundancy":"Yes; PROFINET MRP","Power loss, typ.":"1.9 W","RJ 45 (Ethernet)":"Yes; Pre-assembled BusAdapter BA 2x RJ45","Rated value (DC)":"24 V","Status indicator":"Yes","Integrated Switch":"Yes","PROFINET IO Device":"Yes","Prioritized startup":"Yes","Diagnostics function":"Yes","Inrush current, max.":"3.7 A","BusAdapter (PROFINET)":"Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FC","Network loading class":"2","Open IE communication":"Yes","Modules per rack, max.":"32; + 16 ET 200AL modules","Transmission procedure":"PROFINET with 100 Mbit/s full duplex (100BASE-TX)","Short-circuit protection":"Yes","Current consumption, max.":"550 mA","Between Different Circuits":"Safety extra low voltage SELV","Reverse polarity protection":"Yes","Vertical Installation, Max.":"50 °C; = Tmax","Vertical Installation, Min.":"-40 °C; = Tmin","Connection display LINK TX/RX":"Yes; 2x green link LEDs on BusAdapter","Horizontal Installation, Max.":"70 °C; = Tmax","Horizontal Installation, Min.":"-40 °C; = Tmin (incl. condensation/frost)","Number of PROFINET interfaces":"1; 2 ports (switch)","Address space per module, max.":"256 byte; per input / output","Address space per station, max.":"512 byte; Dependent on configuration","PROFINET system redundancy (S2)":"No","Current consumption (rated value)":"450 mA","Infeed power to the backplane bus":"4.5 W","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","Between Backplane Bus And Electronics":"No","Between Supply And All Other Circuits":"No","Number of submodules per station, max.":"256","between PROFINET and all other circuits":"Yes; 1 500 V AC","Mains/voltage failure stored energy time":"10 ms","Monitoring of the supply voltage (PWR-LED)":"Yes; green PWR LED","Installation altitude above sea level, max.":"5 000 m","Protection against fouling acc. to EN 60664-3":"Yes; Type 1 protection","Module swapping during operation (hot swapping)":"Yes; Single hot swapping","Number of IO Controllers with shared device, max.":"2","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","STEP 7 TIA Portal configurable/integrated from version":"see entry ID: 109746275","Resistant to commercially available coolants and lubricants":"Yes; Incl. diesel and oil droplets in the air","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$488.95","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a8a36b8f10a30a3bcb80310048e52ad2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1093409&mlfb=6AG1155-6AA01-7BN0"},"ai":{"faq":[{"question":"What PROFINET real-time level does this module support?","answer":"It supports PROFINET IRT (Isochronous Real-Time) with send cycles from 250 µs to 4 ms in 125 µs increments, suitable for synchronous motion applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1155-6AA01-7BN0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1155-6AA01-7BN0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}