{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1210-1PE26-2UL0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1210-1PE26-2UL0","canonicalUrl":"https://aoctrl.com/siemens/6AG1210-1PE26-2UL0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1210-1PE26-2UL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120, 6AG1210-1PE26-2UL0, FSD 30 kW, 90 A output, 41.6 kVA apparent power, IE2, IP20.","salesMarkdown":"## Drive selection memo – 6AG1210-1PE26-2UL0 FSD 30 kW variant outputs 90 A continuous, 41.6 kVA apparent power, IE2 class, efficiency 0.98, power loss 0.765 kW. Braking includes DC braking and integrated brake chopper. ## Integration checklist — field service angle Mount the drive with clearance for top and bottom air intake/exhaust; internal air cooling relies on unobstructed vertical flow. Condensation is not permissible (rated for non-condensing environments), so avoid mounting in unheated enclosures without climate control. Pulse frequency is 4 kHz — derate output current if you raise it. Parameter locking and overload protection are built in; stall protection and blocked-rotor protection are present. Ground-fault, short-circuit, undervoltage, and overvoltage protection are all integrated.","metaTitle":"Siemens 6AG1210-1PE26-2UL0 SINAMICS G120, FSD 30 kW, 90 A","metaDescription":"Siemens SINAMICS G120 drive, 6AG1210-1PE26-2UL0. 30 kW FSD, 90 A output, 41.6 kVA. IE2, IP20. Sourced to order against RFQ. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Max.":"50 °C; = Tmax","Min.":"-20 °C; = Tmin","Depth":"237 mm","Width":"200 mm","title":"6AG1210-1PE26-2UL0","Height":"472 mm","Present":"No","Efficiency":"0.98","description":"SIPLUS G120 PM240-2 IP20-FSD-U-400V 30 kW based on 6SL3210-1PE26-0UL0 with conformal coating, -20…+50 °C, unfiltered with integrated braking chopper 380-480 V 3 AC +10/-20% 47-63 Hz power high overload: 22 kW at 200% 3 s,150% 57 s,100% 240 s power low overload: 30 kW at 150% 3 s,110% 57 s,100% 240 s 472x 200x 237 (HxWxD), FSF design, degree of protection IP20 without CU and operating unit released as of CU FW version V4.7 HF8","Brake design":"DC braking, compound braking, resistance braking with integrated brake chopper (for size FSGX optional)","Storage, max.":"55 °C","Storage, min.":"-25 °C","Cooling method":"Internal air cooling","Operation, max.":"98 %","Product version":"FSD 30 kW","Pulse frequency":"4 kHz","lifecycle_stage":"current","Cooling air flow":"0.055 m³/s","Power loss, max.":"0.765 kW","Stall protection":"Yes","Parameter locking":"Yes","With blocked rotor":"Yes","Degree of pollution":"2 according to EN 61800-5-1","IE class of the CDM":"IE2","Overload protection":"Yes","Storage, max. [°F]":"131 °F; Class 1K3 acc. to EN 60721-3-1","Storage, min. [°F]":"-13 °F","Output current, max.":"90 A","Transportation, max.":"70 °C","Transportation, min.":"-40 °C","Apparent Power Output":"41.6 kVA","Transport, max. [°F]":"158 °F; Class 2K3 according to EN 60721-3-2","Transport, min. [°F]":"-40 °F","Type of input voltage":"AC","Overvoltage protection":"Yes","Design of the converter":"FSD","Ground-fault protection":"Yes","IP degree of protection":"IP20","Undervoltage protection":"Yes","Condensation permissible":"No","Short-circuit protection":"Yes","Weight (without packaging)":"17 kg","Shock load during operation":"(15x g)/11 ms","Temperature monitor for motor":"Yes","Input current with low overload":"57 A","Output current without overload":"60 A","Input current with high overload":"47 A","Output current with low overload":"60 A","Sound pressure level (1 m), max.":"71.6 dB","Output current with high overload":"45 A","Temperature monitor for converter":"Yes","Power loss of the CDM in standby mode":"27 W","Cable length for motor, shielded, max.":"200 m","Emitted Active Power With Low Overload":"30 kW","Cable length for braking resistor, max.":"10 m","Emitted Active Power With High Overload":"22 kW","Design of electrical connection of motor":"Screw terminals","Standard for EMC according to EN 61800-3":"the EMC product standard EN 61800-3 does not apply directly to a frequency inverter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the inverter","Active Power Output With Low Overload [Hp]":"40 hp","Touch protection according to EN 61800-5-1":"Assuming use as prescribed","Active Power Output With High Overload [Hp]":"30 hp","Type of duty cycle duration with low overload":"1.1x rated output current (i.e. 110 % overload) for 57 s with a cycle time of 300 s; 1.5x rated output current (i.e. 150 % overload) for 3 s with a cycle time of 300 s","Type of duty cycle duration with high overload":"1.5x output current rating (i.e. 150 % overload) for 57 s with a cycle time of 300 s; 2x output current rating (i.e. 200 % overload) for 3 s with a cycle time of 300 s","Output voltage in relation to input voltage, max.":"95 %","Output voltage in relation to input voltage, min.":"0 %","Power loss of the CDM at the operating point (0/25)":"279 W","Power loss of the CDM at the operating point (0/50)":"357 W","Type of electrical connection for mains supply line":"Screw terminals","Design of electrical connection for the PE conductor":"Screw terminals","Power loss of the CDM at the operating point (0/100)":"603 W","Power loss of the CDM at the operating point (50/25)":"295 W","Power loss of the CDM at the operating point (50/50)":"395 W","Power loss of the CDM at the operating point (90/50)":"445 W","Connectable conductor cross-section for AWG cables, max.":"6","Connectable conductor cross-section for AWG cables, min.":"14","Connectable Cable Cross-Section For Mains Supply Line, Max.":"35 mm²","Connectable Cable Cross-Section For Mains Supply Line, Min.":"10 mm²","Connectable Cable Cross-Section For Motor Supply Line, Max.":"35 mm²","Connectable Cable Cross-Section For Motor Supply Line, Min.":"10 mm²","Installation altitude above sea level without derating, max.":"1 000 m","Relative power loss of the CDM at the operating point (0/25)":"0.67 %","Relative power loss of the CDM at the operating point (0/50)":"0.86 %","Relative power loss of the CDM at the operating point (0/100)":"1.45 %","Relative power loss of the CDM at the operating point (50/25)":"0.71 %","Relative power loss of the CDM at the operating point (50/50)":"0.95 %","Relative power loss of the CDM at the operating point (90/50)":"1.07 %","Type of electrical connection for supply cable to braking resistor":"Screw terminals","Connectable cable cross-section for supply cable to braking resistor, max.":"16 mm²","Connectable cable cross-section for supply cable to braking resistor, min.":"2.5 mm²","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)","Short-time withstand current (SCCR) of the entire control cabinet in accordance with UL 508A":"65 kA","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/122ac295d479e4a3e3dc3fe94638a391.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1092023&mlfb=6AG1210-1PE26-2UL0"},"ai":{"faq":[{"question":"What are the ambient operating temperature limits?","answer":"The operating temperature range is -20 °C minimum to 50 °C maximum. Storage range is -25 °C to 55 °C; transport range is -40 °C to 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1210-1PE26-2UL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1210-1PE26-2UL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}