{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1210-1PE32-2AL0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1210-1PE32-2AL0","canonicalUrl":"https://aoctrl.com/siemens/6AG1210-1PE32-2AL0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1210-1PE32-2AL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120X drive, FSF 132 kW frame, 410 A output current, 173.21 kVA apparent power, IP20.","salesMarkdown":"## What this drive delivers on a mill floor The Siemens 6AG1210-1PE32-2AL0 is an FSF 132 kW drive, rated for 410 A output current and 173.21 kVA apparent power. It operates at ambient temperatures from -20°C to 50°C, but condensation is not permissible. ## Key ratings for mill duty Output current max 410 A at 173.21 kVA for the 132 kW frame. Efficiency 0.98, so the internal air cooling (0.153 m³/s airflow) handles the 2.841 kW max power loss without excessive heat recirculation. Pulse frequency factory set at 2 kHz; enough for standard induction motors, not the higher carrier needed for high-speed spindles. Brake design includes DC braking, compound braking, and resistance braking with an integrated brake chopper (optional on size FSGX). That chopper lets the drive hold strip tension during rapid deceleration — no external braking resistor needed for most mill applications. Lifecycle status is current — this is not an NRND or phase-out line. Sourced to order via RFQ; no last-time-buy pressure.","metaTitle":"6AG1210-1PE32-2AL0 SINAMICS G120X, FSF 132 kW, 410 A","metaDescription":"Current-production Siemens SINAMICS G120X drive, FSF 132 kW, 410 A, 173.21 kVA. IP20, 50°C ambient, 0.98 efficiency. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Max.":"50 °C; = Tmax","Min.":"-20 °C; = Tmin","Depth":"357 mm","Width":"305 mm","title":"6AG1210-1PE32-2AL0","Height":"708 mm","Present":"Yes","Efficiency":"0.98","description":"SIPLUS G120 PM240-2 IP20-FSF-A-400V 132 kW based on 6SL3210-1PE32-5AL0 with conformal coating, -20…+50 °C, with integrated class A filter with integrated braking chopper 380-480 V 3 AC +10/-20% 47-63 Hz power high overload: 110 kW at 200% 3 s,150% 57 s,100% 240 s power rating low overload: 132 kW at 150% 3 s,110% 57 s,100% 240 s 708x 305x 357 (HxWxD), FSF design, degree of protection IP20 without CU and operating unit released as of CU FW version V4.7 HF8","Brake design":"DC braking, compound braking, resistance braking with integrated brake chopper (for size FSGX optional)","Storage, max.":"55 °C","Storage, min.":"-25 °C","Cooling method":"Internal air cooling","Operation, max.":"98 %","Product version":"FSF 132 kW","Pulse frequency":"2 kHz","lifecycle_stage":"current","Cooling air flow":"0.153 m³/s","Power loss, max.":"2.841 kW","Stall protection":"Yes","Parameter locking":"Yes","With blocked rotor":"Yes","Degree of pollution":"2 according to EN 61800-5-1","IE class of the CDM":"IE2","Overload protection":"Yes","Storage, max. [°F]":"131 °F; Class 1K3 acc. to EN 60721-3-1","Storage, min. [°F]":"-13 °F","Output current, max.":"410 A","Transportation, max.":"70 °C","Transportation, min.":"-40 °C","Apparent Power Output":"173.21 kVA","Design of line filter":"Class A","Transport, max. [°F]":"158 °F; Class 2K3 according to EN 60721-3-2","Transport, min. [°F]":"-40 °F","Type of input voltage":"AC","Overvoltage protection":"Yes","Design of the converter":"FSF","Ground-fault protection":"Yes","IP degree of protection":"IP20","Undervoltage protection":"Yes","Condensation permissible":"No","Short-circuit protection":"Yes","Weight (without packaging)":"65 kg","Shock load during operation":"(15x g)/11 ms","Temperature monitor for motor":"Yes","Input current with low overload":"242 A","Output current without overload":"250 A","Input current with high overload":"218 A","Output current with low overload":"250 A","Sound pressure level (1 m), max.":"67.7 dB","Output current with high overload":"205 A","Temperature monitor for converter":"Yes","Power loss of the CDM in standby mode":"48.1 W","Cable length for motor, shielded, max.":"300 m","Emitted Active Power With Low Overload":"132 kW","Cable length for braking resistor, max.":"10 m","Emitted Active Power With High Overload":"110 kW","Design of electrical connection of motor":"M10 screw stud","Standard for EMC according to EN 61800-3":"the EMC product standard EN 61800-3 does not apply directly to a frequency inverter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the inverter","Active Power Output With Low Overload [Hp]":"200 hp","Touch protection according to EN 61800-5-1":"Assuming use as prescribed","Active Power Output With High Overload [Hp]":"150 hp","Type of duty cycle duration with low overload":"1.1x rated output current (i.e. 110 % overload) for 57 s with a cycle time of 300 s; 1.5x rated output current (i.e. 150 % overload) for 3 s with a cycle time of 300 s","Type of duty cycle duration with high overload":"1.5x output current rating (i.e. 150 % overload) for 57 s with a cycle time of 300 s; 2x output current rating (i.e. 200 % overload) for 3 s with a cycle time of 300 s","Output voltage in relation to input voltage, max.":"95 %","Output voltage in relation to input voltage, min.":"0 %","Power loss of the CDM at the operating point (0/25)":"747.2 W","Power loss of the CDM at the operating point (0/50)":"1 055.2 W","Type of electrical connection for mains supply line":"M10 screw stud","Design of electrical connection for the PE conductor":"M10 screw stud","Power loss of the CDM at the operating point (0/100)":"2 011.1 W","Power loss of the CDM at the operating point (50/25)":"811.1 W","Power loss of the CDM at the operating point (50/50)":"1 205.5 W","Power loss of the CDM at the operating point (90/50)":"1 430.3 W","Connectable conductor cross-section for AWG cables, min.":"4","Connectable Cable Cross-Section For Mains Supply Line, Max.":"120 mm²","Connectable Cable Cross-Section For Mains Supply Line, Min.":"35 mm²","Connectable Cable Cross-Section For Motor Supply Line, Max.":"120 mm²","Connectable Cable Cross-Section For Motor Supply Line, Min.":"35 mm²","Installation altitude above sea level without derating, max.":"1 000 m","Relative power loss of the CDM at the operating point (0/25)":"0.43 %","Relative power loss of the CDM at the operating point (0/50)":"0.61 %","Relative power loss of the CDM at the operating point (0/100)":"1.16 %","Relative power loss of the CDM at the operating point (50/25)":"0.47 %","Relative power loss of the CDM at the operating point (50/50)":"0.7 %","Relative power loss of the CDM at the operating point (90/50)":"0.83 %","Type of electrical connection for supply cable to braking resistor":"Screw terminals","Connectable cable cross-section for supply cable to braking resistor, max.":"70 mm²","Connectable cable cross-section for supply cable to braking resistor, min.":"25 mm²","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)","Short-time withstand current (SCCR) of the entire control cabinet in accordance with UL 508A":"65 kA","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/122ac295d479e4a3e3dc3fe94638a391.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1092028&mlfb=6AG1210-1PE32-2AL0"},"ai":{"faq":[{"question":"What is the maximum ambient operating temperature?","answer":"50°C."},{"question":"What is the minimum ambient operating temperature?","answer":"-20°C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1210-1PE32-2AL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1210-1PE32-2AL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}