{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1211-1HD30-2XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1211-1HD30-2XB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1211-1HD30-2XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1211-1HD30-2XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS S7-1200 CPU 1211C, 6AG1211-1HD30-2XB0, FBD/LAD, 24 V DC, PROFINET, -40 to 70 °C.","salesMarkdown":"The 6AG1211-1HD30-2XB0 is a SIPLUS variant of the S7-1200 CPU 1211C, built for extended temperature and harsh environments. It supports both FBD and LAD programming, runs on 24 V DC (permissible range 20.4–28.8 V), and communicates via PROFINET (TCP/IP, autocrossing). No local expansion modules—this is a compact fixed-I/O CPU. Dimensions 90 x 100 x 75 mm; mounts on standard DIN rail. ## SIPLUS vs Standard 6ES7211-1HE31-0XB0 The sibling 6ES7211-1HE31-0XB0 is the standard S7-1200 CPU 1211C. The SIPLUS version extends the ambient range to -40 to 70 °C with conformal coating and wider component tolerance. Mechanical footprint and communication interface are identical—swap a standard unit for this one in a panel without rewiring. The SIPLUS has the same 1 MB load memory, 240 h backup, and no local expansion. If your job lives in a nacelle, cold store, or desert cabinet, this is the one to specify.","metaTitle":"Siemens 6AG1211-1HD30-2XB0 SIPLUS S7-1200 CPU, -40 to 70°C","metaDescription":"SIPLUS S7-1200 CPU 1211C, FBD/LAD, 24 V DC, PROFINET, rated -40 to 70 °C. Sourced to order. Ask about fit vs standard 6ES7211-1HE31-0XB0.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"FBD":"Yes","LAD":"Yes","24 V":"Permissible range: 20.4V to 28.8V","Max.":"70 °C","Min.":"-40 °C","Depth":"75 mm","Width":"90 mm","cULus":"Yes","title":"6AG1211-1HD30-2XB0","Height":"100 mm","Inputs":"1 024 byte","MODBUS":"No","TCP/IP":"Yes","24 V DC":"Yes","Forcing":"Yes","Outputs":"1 024 byte","Overall":"15; dynamically","Physics":"Ethernet","Present":"Yes; Entire project maintenance-free in the integral EEPROM","Voltage":"Yes","Isolated":"Yes","PROFIBUS":"No","As Server":"Yes","Supported":"Yes","Variables":"Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters","0 to +10 V":"Yes","Adjustable":"Yes","Expandable":"No","Integrated":"1 Mbyte; Load memory expandable using SIEMENS Memory Card","Backup time":"240 h; Typical","UL approval":"Yes","description":"***Spare part*** SIPLUS S7-1200 CPU 1211C DC/DC/relay -25...+70 °C with conformal coating based on 6ES7211-1HD30-0XB0. compact CPU, DC/DC/RY, onboard I/O: 6 DI 24 V DC 4 DO relay 0.5A 2 AI 0-10 V DC Power supply: AC 20.4-28.8V DC Program/data memory 25 KB","AS-Interface":"No","Autocrossing":"Yes","For Uprating":"No","Number, max.":"4 kbyte; Size of bit memory address area","2-Wire Sensor":"Yes","For Signal \"0\"":"5 V DC at 1 mA","For Signal \"1\"":"15 V DC at 2.5 mA","Interface type":"PROFINET","PID controller":"Yes","Shielded, Max.":"100 m; shielded, twisted pair","Autonegotiation":"Yes","Parameterizable":"Single phase : 3 @ 100 kHz, differential: 3 @ 80 kHz","Weight, approx.":"380 g","Without Battery":"Yes","lifecycle_stage":"current","\"0\" To \"1\", Max.":"10 ms; max.","\"1\" To \"0\", Max.":"10 ms; max.","Power loss, typ.":"8 W","Rated value (DC)":"24 V","Unshielded, Max.":"150 m","Fall height, max.":"0.3 m; five times, in product package","Source/sink input":"Yes","Inputs, adjustable":"1 kbyte","Number of counters":"3","On Lamp Load, Max.":"30 W with DC, 200 W with AC","At \"0\" To \"1\", Max.":"12.8 ms","At \"0\" To \"1\", Min.":"0.2 ms","Outputs, adjustable":"1 kbyte","Programming package":"STEP 7 Basic V10.5","Between The Channels":"No","For Signal \"1\", Typ.":"1 mA","ISO-on-TCP (RFC1006)":"Yes","Inrush current, max.":"12 A; at 28.8 V DC","Frequency measurement":"Yes","User-defined websites":"Yes","Controlled Positioning":"Yes","Number of alarm inputs":"4","PROFINET IO Controller":"Yes","Deviation per day, max.":"±60 s/month at 25 °C","IP degree of protection":"IP20","Number of analog inputs":"2; > +60 °C Number of simultaneously controllable inputs and outputs max. 50%","Number of relay outputs":"4","Status/control variable":"Yes","For Bit Operations, Typ.":"0.1 µs; / Operation","Number of analog outputs":"0","Number of blocks (total)":"DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used","Number of digital inputs":"6; Integrated; > +60 °C Number of simultaneously controllable inputs and outputs max. 50 %","Short-circuit protection":"No; to be provided externally","For Word Operations, Typ.":"12 µs; / Operation","Number of digital outputs":"4; Relay; > +60 °C Number of simultaneously controllable inputs and outputs max. 50%","With Resistive Load, Max.":"2 A","Between Different Circuits":"500 V DC between 24 V DC and 5 V DC","Hardware clock (real-time)":"Yes","Vertical Installation, Max.":"45 °C; = Tmax","Vertical Installation, Min.":"-25 °C; = Tmin","Input resistance (0 to 10 V)":"≥100k ohms","Conversion time (per channel)":"625 µs","Horizontal Installation, Max.":"70 °C; = Tmax; > +60 °C Number of simultaneously controllable inputs and outputs max. 50 %; no signal board can be used","Horizontal Installation, Min.":"-25 °C; = Tmin","Test voltage at air discharge":"8 kV","For voltage/current measurement":"2","Number of operating cycles, max.":"mechanically 10 million, at rated load voltage 100 000","for backplane bus (5 V DC), max.":"750 mA; Max. 5 V DC for SM and CM","Counting frequency (counter) max.":"100 kHz","Current consumption (rated value)":"300 mA; Typical","Integration time, parameterizable":"Yes","Supports protocol for PROFINET IO":"No","Test voltage at contact discharge":"6 kV","Between The Channels, In Groups Of":"1","Number of modules per system, max.":"3 communication modules, no signal board can be used","tested according to IEC 60068-2-27":"Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms","For Floating Point Arithmetic, Typ.":"18 µs; / Operation","Plug-in (SIMATIC Memory Card), max.":"24 Mbyte; with SIEMENS Memory Card","Potential separation digital inputs":"No; 500V AC for 1 minute","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","Potential separation digital outputs":"Relays","Automatic Detection Of Transmission Rate":"Yes","Limit class A, for use in industrial areas":"Yes; Group 1","Limit class B, for use in residential areas":"Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011","Operation, tested according to IEC 60068-2-6":"Yes","Of The Pulse Outputs, With Resistive Load, Max.":"1 Hz","Of Which Inputs Usable For Technological Functions":"3; HSC (High Speed Counting)","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Resolution with overrange (bit including sign), max.":"10 bit","Retentive data area (incl. timers, counters, flags), max.":"2 048 byte"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/122ac295d479e4a3e3dc3fe94638a391.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=334888&mlfb=6AG1211-1HD30-2XB0"},"ai":{"faq":[{"question":"What is the temperature range of 6AG1211-1HD30-2XB0?","answer":"Rated for -40 °C to 70 °C, making it suitable for extreme environments like wind turbine nacelles or refrigerated areas."},{"question":"Does the SIPLUS CPU support FBD and LAD programming?","answer":"Yes, both FBD and LAD are supported, consistent with the standard S7-1200 family."},{"question":"Can this CPU be expanded with local signal modules?","answer":"No. The CPU 1211C is a compact, non-expandable unit with fixed I/O capacity. For expansion, step to a 1212C or higher."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1211-1HD30-2XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1211-1HD30-2XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}