{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1222-1XF32-2XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1222-1XF32-2XB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1222-1XF32-2XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1222-1XF32-2XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS 6AG1222-1XF32-2XB0, current-production relay output module, 8 channels, 2 A per channel, -40 to 70 °C, marine approved.","salesMarkdown":"## SIPLUS 8-Relay Output for Extreme Environments The Siemens 6AG1222-1XF32-2XB0 is an active-production SIPLUS digital output module delivering eight relay outputs rated at 2 A per channel for both resistive and inductive loads. Its -40 to 70 °C operating temperature range allows it to be mounted in unheated enclosures, cold warehouses, or hot machine cabinets without derating. The module switches AC loads from 5 to 250 V and DC loads from 5 to 30 V, covering the common coil and indicator voltages found in most industrial cabinets. Marine approval and IP20 protection make the module suitable for shipboard and coastal installations, provided it is mounted inside a suitable enclosure. Front-side diagnostics give per-channel status and alarm reporting, which speeds up fault finding when a field device stops responding. ## Installation & Wiring Notes The module occupies 45 mm of DIN-rail width and requires a front connector — order separately. External short-circuit protection must be provided. The relay coil draws 16.7 mA from the load voltage L+, and the backplane bus supplies 140 mA at 5 V DC. Overall power loss is typically 5 W. Isolation between channels is by relay, with 750 V AC for 1 minute between different circuits and 1 500 V AC between channels and the backplane bus. Unshielded cables can run up to 150 m, shielded up to 500 m. ## Field Diagnostics & Mechanical Endurance Each output channel provides status indication and the module can generate diagnostic alarms. Transition times from 0 to 1 and 1 to 0 are both capped at 10 ms, adequate for most discrete control signals. The relays are rated for 10 million mechanical cycles, but at rated load voltage the contact endurance drops to 100 000 cycles — factor that into life planning for frequently switched applications. Cold restart is tested down to -25 °C.","metaTitle":"Siemens 6AG1222-1XF32-2XB0 SIPLUS 8-Relay Output, -40 to 70°","metaDescription":"Active-production SIPLUS module with 8 relay outputs, 2 A rated, -40 to 70 °C operating range, marine approval. Sourced to order – request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Digital Output Modules"],"specifications":{"Max.":"70 °C","Min.":"-40 °C","Depth":"75 mm","Width":"45 mm","title":"6AG1222-1XF32-2XB0","Height":"100 mm","Plastic":"Yes","description":"SIPLUS S7-1200 SM 1232 based on 6ES7222-1XF32-0XB0 with conformal coating, -40…+70 °C, start up -25 °C, S7-1200, digital output SM 1222, 8 DQ, Relay changeover contact","In Groups Of":"1","Shielded, Max.":"500 m","For Maintenance":"Yes","Marine approval":"Yes","Weight, approx.":"310 g","lifecycle_stage":"current","\"0\" To \"1\", Max.":"10 ms","\"1\" To \"0\", Max.":"10 ms","Diagnostic alarm":"Yes","Power loss, typ.":"5 W","Rated value (AC)":"5 V AC to 250 V AC","Rated value (DC)":"5 V DC to 30 V DC","Unshielded, Max.":"150 m","On Lamp Load, Max.":"30 W with DC, 200 W with AC","up to 50 °C, max.":"2 A; Current per mass","Between The Channels":"Relays","Diagnostics function":"Yes","At cold restart, min.":"-25 °C","IP degree of protection":"IP20","Number of relay outputs":"8","Required Front Connector":"Yes","Short-circuit protection":"No; to be provided externally","For Status Of The Outputs":"Yes","Number of digital outputs":"8","With Inductive Load, Max.":"2 A","With Resistive Load, Max.":"2 A","Between Different Circuits":"750 V AC for 1 minute","from load voltage L+, max.":"16.7 mA/relay coil","from backplane bus 5 V DC, max.":"140 mA","Number of operating cycles, max.":"mechanically 10 million, at rated load voltage 100 000","Between The Channels, In Groups Of":"1","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","Between The Channels And Backplane Bus":"1 500 V AC for 1 minute","For Signal \"1\" Permissible Range, Max.":"2 A","Rated supply voltage of relay coil L+ (DC)":"24 V","Installation altitude above sea level, max.":"2 000 m","Protection against fouling acc. to EN 60664-3":"Yes; Type 1 protection","Operation at 25 °C without condensation, max.":"95 %","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m); above 2 000 m max. 132 V AC","Resistant to commercially available coolants and lubricants":"Yes; Incl. diesel and oil droplets in the air","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$580.62","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/31b2bb4a2ce3c861a3e1f61176e2f4d3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=114520&mlfb=6AG1222-1XF32-2XB0"},"ai":{"faq":[{"question":"What is the operating temperature range of this module?","answer":"It is rated for -40 to 70 °C, with a cold restart minimum of -25 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1222-1XF32-2XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1222-1XF32-2XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}