{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1223-1PL30-2XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1223-1PL30-2XB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1223-1PL30-2XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1223-1PL30-2XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 6AG1223-1PL30-2XB0 digital I/O module, 16 inputs (DC) and 16 relay outputs, rated -40 to 70 °C, cULus/CE/FM.","salesMarkdown":"The Siemens 6AG1223-1PL30-2XB0 is a 16-channel digital input / 16-channel relay output module from the SIPLUS extended-temperature range, rated for -40 to 70 °C ambient—critical for panels in cold storage, northern installations, or outdoor cabinets without climate control. Digital inputs accept 5 V DC at 1 mA for signal 0 and 15 V DC at 2.5 mA (typical 4 mA) for signal 1; switching time is 10 ms max in either direction. Relay outputs handle AC loads up to 250 V AC, 5 to 250 V AC, and lamp loads up to 30 W DC or 200 W AC. cULus, CE, and FM approvals are listed; diagnostic alarms and diagnostics function are built in. Front connector required—order separately. ## Signal integrity and wiring notes Shielded cable runs up to 500 m; unshielded drops to 150 m. If you're running inputs past a VFD panel, go shielded—it's noise till proven otherwise. No internal short-circuit protection is provided. Each output group needs an external fuse or breaker. Budget for that in the BOM. Relay outputs are not isolated per channel; groups of 4 share a common. Watch the grouping when laying out inductive loads—suppress coils externally if you want the relays to last. Power loss is 10 W typical. Ensure the backplane power budget accounts for that, especially in densely loaded racks.","metaTitle":"Siemens 6AG1223-1PL30-2XB0 Digital I/O Module, -40 to 70°C","metaDescription":"Active production. 16 digital inputs (5/15V DC), 16 relay outputs (5-250V AC). cULus, CE, FM. Shielded cable up to 500 m. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLC I/O & Expansion Modules"],"specifications":{"Max.":"70 °C","Min.":"-40 °C","Depth":"75 mm","Width":"70 mm","cULus":"Yes","Alarms":"Yes","Height":"100 mm","CE mark":"Yes","Plastic":"Yes","FM approval":"Yes","In Groups Of":"4","For Signal \"0\"":"5 V DC at 1 mA","For Signal \"1\"":"15 V DC at 2.5 mA","Shielded, Max.":"500 m","For Maintenance":"Yes","Parameterizable":"Yes","Weight, approx.":"350 g","lifecycle_stage":"current","\"0\" To \"1\", Max.":"10 ms","\"1\" To \"0\", Max.":"10 ms","Diagnostic alarm":"Yes","Power loss, typ.":"10 W","Rated value (AC)":"5 V AC to 250 V AC","Rated value (DC)":"5 to 30 V AC","Unshielded, Max.":"150 m","Fall height, max.":"0.3 m; five times, in product package","On Lamp Load, Max.":"30 W with DC, 200 W with AC","up to 40 °C, max.":"16","up to 50 °C, max.":"8 A; Current per mass","Between The Channels":"Relays","Diagnostics function":"Yes","For Signal \"1\", Min.":"2.5 mA","For Signal \"1\", Typ.":"4 mA","Type of input voltage":"DC","IP degree of protection":"IP20","Number of relay outputs":"16","For Status Of The Inputs":"Yes","Number of digital inputs":"16","Required Front Connector":"Yes","Short-circuit protection":"No; to be provided externally","For Status Of The Outputs":"Yes","Number of digital outputs":"16","With Inductive Load, Max.":"2 A","With Resistive Load, Max.":"2 A","Between Different Circuits":"750 V AC for 1 minute","For Signal \"1\" Rated Value":"2 A","from backplane bus 5 V DC, max.":"180 mA","Number of operating cycles, max.":"mechanically 10 million, at rated load voltage 100 000","Between The Channels, In Groups Of":"4","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","Between The Channels And Backplane Bus":"1 500 V AC for 1 minute","For Signal \"1\" Permissible Range, Max.":"2 A","from load voltage L+ (without load), max.":"4 mA/input 11 mA/relay","Rated supply voltage of relay coil L+ (DC)":"24 V","Product Function / Supply Voltage For Transmitters":"Yes","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","For Signal \"0\", Max. (Permissible Quiescent Current)":"1 mA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=421111&mlfb=6AG1223-1PL30-2XB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6AG1223-1PL30-2XB0/alternatives.json"},"ai":{"faq":[{"question":"What are the temperature ratings?","answer":"Rated for -40 °C to 70 °C ambient operating temperature."},{"question":"Does the module include short-circuit protection?","answer":"No. Short-circuit protection must be provided externally on each output circuit."},{"question":"What approvals does it carry?","answer":"cULus, CE, and FM approval."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1223-1PL30-2XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1223-1PL30-2XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}