{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1226-6BA32-5XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1226-6BA32-5XB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1226-6BA32-5XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1226-6BA32-5XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS S7-1200 SM 1226 F-DI 16x24 V DC fail-safe digital input module, 16 channels (1oo1) or 8 (1oo2), PROFIsafe, conformal-coated, -40…+70 °C, 70 mm width.","salesMarkdown":"## What this module is The Siemens 6AG1226-6BA32-5XB0 is the SIPLUS variant of the SIMATIC S7-1200 SM 1226 F-DI 16×24 V DC fail-safe digital input module, built on the 6ES7226-6BA32-0XB0 with conformal coating added for corrosive and condensing atmospheres. It drops onto the S7-1200 backplane beside the F-CPU as a PROFIsafe slave and contributes 16 fail-safe inputs that the safety program reads as either 16 single-channel (1oo1) signals or 8 dual-channel (1oo2) pairs — each pair of inputs a.x and b.x is independently assignable. ## Signal levels and input filter Signal \"0\" is recognised from -30 V DC to +5 V DC, signal \"1\" from 15 V DC to 30 V DC, with a typical 5 mA input current at the \"1\" level and a maximum quiescent current of 0.5 mA still tolerated as \"0\" — a comfortable margin against sensor leakage on long home runs. The input filter is parameterisable in five steps: 0.8 / 1.6 / 3.2 / 6.4 / 12.8 ms, so the integrator trades noise immunity against response time per channel. Cable-length guidance is conditional on the filter step and the 0.8 ms input-delay setting: shielded cable up to 200 m is supported at 0.8 ms to 12.6 ms input filter, and the same 200 m ceiling applies unshielded at 0.8 ms to 12.6 s — with the explicit caveat that an input delay of 0.8 ms forces shielded cable on the digital inputs and the sensor supply. ## Channel-count derating vs temperature All 16 inputs are usable up to 40 °C, after which Siemens specifies 16 inputs at 45 °C vertical mounting and 16 inputs at 55 °C horizontal mounting — so channel count does not drop with temperature on this variant, but orientation does become the governing detail once the cabinet runs warm. The operating envelope is -40 °C to 70 °C with a permissible change rate of 5 °C to 55 °C at 3 °C per minute, and installation altitude is limited to 2 000 m above sea level. ## Power and bus draw The module draws 155 mA from the backplane 5 V DC (SM bus) and takes its load-side supply from L+ at 24 V DC nominal, with a permissible range of 20.4 V to 28.8 V DC and a quiescent draw of 130 mA from L+ before sensor current is added. Sensor load scales linearly with usage: each input that is actually wired adds 6 mA to the L+ budget, plus whatever Vs1 / Vs2 current is drawn downstream — plan the stack headroom accordingly. Power dissipation is typically 7 W, which matters for cabinet thermal sizing on a fully loaded F-CPU + F-DI stack. ## Harsh-environment posture (the SIPLUS reason) Mechanical footprint is 70 mm wide × 100 mm tall × 75 mm deep, which fixes its slot allocation on the S7-1200 DIN rail and its thermal footprint inside the enclosure. Lifecycle status is current, so the 6AG1226-6BA32-5XB0 fits new-build safety I/O budgets rather than a phase-out buy.","metaTitle":"Siemens 6AG1226-6BA32-5XB0 SM 1226 F-DI 16x24VDC, -40…70 °C","metaDescription":"Siemens 6AG1226-6BA32-5XB0 SIPLUS S7-1200 SM 1226 F-DI 16x24 V DC fail-safe digital input, 16 channels, PL e / SIL 3, conformal coated, -40…70 °C. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"75 mm","Width":"70 mm","Height":"100 mm","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"3 °C","Permissible Temperature Change":"5 °C to 55 °C, 3 °C / minute"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$295.91 – $769.74","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e6bd79869fb28658b5fb38bdc5f0dac0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=599398&mlfb=6AG1226-6BA32-5XB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6AG1226-6BA32-5XB0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1226-6BA32-5XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1226-6BA32-5XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}