{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1322-5FF00-4AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1322-5FF00-4AB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1322-5FF00-4AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1322-5FF00-4AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens S7-1500 digital output module, 8 DO, 2 A, 24 V DC, -40 to 70 °C, 40 mm, diagnostic alarms.","salesMarkdown":"Siemens 6AG1322-5FF00-4AB0 digital output module, 8 channels, 2 A per channel with zero-crossing switching at 60 V. Diagnostic alarms; operating range -40 to 70 °C; 40 mm wide; requires 40-pin front connector. ## Derating and protection Resistive load switching is rated at 10 Hz, inductive at 0.5 Hz. Short-circuit protection is external — spec calls for a 3.15 A quick-blow fuse per channel group. Power dissipation is 8.6 W typical; keep adjacent modules spaced per manual thermal recommendations to stay at the rated 4 A through 60 °C. ## Certifications UL recognized under File E239877, CE, EAC, RCM, and KC approvals are listed on the module. Documentation for RoHS/REACH is available from Siemens upon request. The module carries a CE mark, meeting EU directives for industrial automation.","metaTitle":"Siemens 6AG1322-5FF00-4AB0 8DO 2A -40 to 70°C","metaDescription":"Active production Siemens S7-1500 digital output module 6AG1322-5FF00-4AB0: 8 channels, 2 A per output, 24 V DC, -40 to 70 °C, diagnostic alarms, UL File E239877. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Digital Output Modules"],"specifications":{"Max.":"70 °C","Min.":"-40 °C","Depth":"120 mm","Width":"40 mm","title":"6AG1322-5FF00-4AB0","Height":"125 mm","CE mark":"Yes","EN 50155":"No","KC approval":"Yes","UL approval":"Yes; File E239877","description":"SIPLUS S7-300 SM 322 8DQ based on 6ES7322-5FF00-0AB0 with conformal coating, 0…+60 °C, digital output isolated, 8 DQ, 120/230 V AC, 2 A, with single rooting/channel and selectable failure mode, 1x 40-pole","For Uprating":"No","Shielded, Max.":"1 000 m","Weight, approx.":"275 g","lifecycle_stage":"current","Diagnostic alarm":"Yes; Parameterizable","Power loss, typ.":"8.6 W","Rated value (AC)":"230 V; 120/230 V AC","Unshielded, Max.":"600 m","On Lamp Load, Max.":"1 Hz","up to 40 °C, max.":"4 A","up to 60 °C, max.":"4 A","Between The Channels":"Yes","Diagnostics function":"Yes; Parameterizable","For Signal \"1\", Min.":"L1 (-8.5 V)","Group error SF (red)":"Yes","Zero-crossing switch":"Yes; 60 V","EAC (formerly Gost-R)":"Yes","Isolation tested with":"1 500 V AC","RCM (formerly C-TICK)":"Yes","Required Front Connector":"40-pin","Short-circuit protection":"Yes; to be provided externally; fuse 3.15 A / 250 V, quick response","Number of digital outputs":"8","With Inductive Load, Max.":"0.5 Hz","With Resistive Load, Max.":"10 Hz","For Signal \"1\" Rated Value":"2 A","Controlling a digital input":"Yes","For Redundant Control Of A Load":"Yes","from backplane bus 5 V DC, max.":"100 mA","Between The Channels, In Groups Of":"1","For Signal \"1\" Minimum Load Current":"10 mA","permissible range, lower limit (AC)":"79 V","permissible range, upper limit (AC)":"264 V","For Signal \"0\" Residual Current, Max.":"2 mA","Between The Channels And Backplane Bus":"Yes; Optocoupler","Status indicator digital output (green)":"Yes","from load voltage L1 (without load), max.":"2 mA","Installation altitude above sea level, max.":"5 000 m","For Signal \"1\" Permissible Surge Current, Max.":"20 A; with 2 half waves","Size of motor starters according to NEMA, max.":"Size 5 according to NEMA","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","for signal \"1\" permissible range for 0 to 40 °C, max.":"2 A","for signal \"1\" permissible range for 0 to 40 °C, min.":"10 mA","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$468.63","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e2eecf099e03cc66d7c0f4ca3a633740.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=334645&mlfb=6AG1322-5FF00-4AB0"},"ai":{"faq":[{"question":"What type of short-circuit protection does the module require?","answer":"Short-circuit protection must be provided externally. The spec recommends a 3.15 A / 250 V quick-response fuse per channel group."},{"question":"Does 6AG1322-5FF00-4AB0 include diagnostics?","answer":"Yes, it has parameterizable diagnostic alarms and a group error SF (red) LED per channel."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1322-5FF00-4AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1322-5FF00-4AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}