{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1322-8BH10-7AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1322-8BH10-7AB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1322-8BH10-7AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1322-8BH10-7AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS S7-1500 digital output module, 16 channels, 24 V DC, 0.5 A per channel, -25 to 70 °C, diagnostics, wire-break and short-circuit protection.","salesMarkdown":"## Comparison with standard variant The 6AG1322-8BH10-7AB0: The standard 6ES7522-1BH01-0AB0 shares the same 16 DO footprint and basic diagnostics but is rated for the standard 0–60 °C range and lacks the UL/ATEX/FM markings at 60 °C. For panels requiring 70 °C ambient or hazardous location certification, this SIPLUS variant is the approved alternate. Electrical characteristics otherwise match; no rewiring needed when swapping within a panel that already uses the standard module but requires ambient-temperature headroom. ## Integration and physical mounting Mounts on the S7-1500 DIN rail, 40 mm wide, requires a 40-pin front connector (not included). Diagnostic data is readable via the backplane; wire-break and short-circuit alarms are group and per-channel respectively. Response time 3 ms per transition. Derating applies above 60 °C: at 70 °C per-channel current drops to 0.5 A. Between-channel isolation is not provided — common load groups must be managed at the wiring level.","metaTitle":"Siemens 6AG1322-8BH10-7AB0 SIPLUS DO Module, 16ch, 70°C","metaDescription":"Active production SIPLUS digital output module for S7-1500. 16 outputs, 24V DC, 0.5A, 70°C. Diagnostics, wire-break, short-circuit protection. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Digital Output Modules"],"specifications":{"Max.":"70 °C; = Tmax; @ 60°C for UL/ATEX/FM use","Min.":"-25 °C; = Tmin","Depth":"120 mm","Width":"40 mm","title":"6AG1322-8BH10-7AB0","Alarms":"Yes","Height":"125 mm","CE mark":"Yes","Wire-break":"Yes","Lower Limit":"48 Ω","Upper Limit":"4 kΩ","description":"SIPLUS S7-300 SM 322 16DA 24 V DC based on 6ES7322-8BH10-0AB0 with conformal coating, -25…+70 °C, digital output SM 322, 16 DQ; 24 V DC/0.5 A, diagnostics-capable, wire break detection with 0 and 1 signal, 1x 40-pole, connection IM 153-X HF required","For Uprating":"No","Short-circuit":"Yes","Shielded, Max.":"1 000 m","Weight, approx.":"350 g","lifecycle_stage":"current","\"0\" To \"1\", Max.":"3 ms","\"1\" To \"0\", Max.":"3 ms","Diagnostic alarm":"Yes","Power loss, typ.":"5.7 W","Rated value (DC)":"24 V","Unshielded, Max.":"600 m","On Lamp Load, Max.":"10 Hz","up to 40 °C, max.":"2 A","up to 60 °C, max.":"2 A","up to 70 °C, max.":"0.5 A","Between The Channels":"No","Diagnostics function":"Yes","For Signal \"1\", Min.":"L+ (-0.7 V)","Group error SF (red)":"Yes","Missing Load Voltage":"Yes","Isolation tested with":"500 V DC","Required Front Connector":"1x 40-pin","Response threshold, typ.":"1.4 A; per channel","Short-circuit protection":"Yes","Number of digital outputs":"16","With Resistive Load, Max.":"100 Hz","For Signal \"1\" Rated Value":"0.5 A","Rated load voltage PWR (green)":"No","Channel fault indicator F (red)":"Yes","Diagnostic information readable":"Yes","For Redundant Control Of A Load":"Yes","from backplane bus 5 V DC, max.":"80 mA","Between The Channels, In Groups Of":"4","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","For Signal \"0\" Residual Current, Max.":"0.7 mA","Between The Channels And Backplane Bus":"Yes","For Signal \"1\" Permissible Range, Max.":"0.6 A","For Signal \"1\" Permissible Range, Min.":"5 mA","Status indicator digital output (green)":"Yes","from load voltage L+ (without load), max.":"88 mA","Installation altitude above sea level, max.":"5 000 m","Limitation of inductive shutdown voltage to":"L+ (-68 V)","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Between The Channels And The Power Supply Of The Electronics":"No","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3a9f67a6f80433ed4a696d92b83469bf.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=367039&mlfb=6AG1322-8BH10-7AB0"},"ai":{"faq":[{"question":"What is the maximum ambient operating temperature?","answer":"Rated up to 70 °C, with UL/ATEX/FM compliance at 60 °C. Derate the 0.5 A per-channel current at 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1322-8BH10-7AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1322-8BH10-7AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}