{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1332-8TF01-4AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1332-8TF01-4AB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1332-8TF01-4AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1332-8TF01-4AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens S7-1200 SM 1232 analog output module, 8 current outputs, 0–20 mA / 4–20 mA, diagnostics, UL/CE/FM, 24 V DC.","salesMarkdown":"The 6AG1332-8TF01-4AB0: The maximum load resistance with current outputs is 750 Ω. This dictates the total loop resistance — including actuator impedance and wiring — that the output can drive while staying within its compliance voltage. For inductive loads such as solenoid valves or relay coils the module handles up to 10 mH; above that, external suppression is required. Isolation is tested at 500 V DC between channels and backplane bus, and between channels and load voltage L+. Reverse-polarity protection on the load supply and full diagnostic readback via the backplane bus are standard, so loop validation during commissioning is straightforward. Maximum unshielded cable length is not given, but the shielded cable length is rated at 800 m. For installations exceeding that or running in high-EMI environments, a remote I/O drop may be preferable.","metaTitle":"Siemens 6AG1332-8TF01-4AB0 S7-1200 Analog Output, 8 AO, Curr","metaDescription":"Siemens 6AG1332-8TF01-4AB0 S7-1200 SM 1232 analog output module with 8 current outputs, 0–20 mA / 4–20 mA, diagnostics, UL/CE/FM approval, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Analog Output Modules"],"specifications":{"Max.":"60 °C; = Tmax","Min.":"0 °C; = Tmin","Depth":"117 mm","Width":"40 mm","Height":"125 mm","CE mark":"Yes","EN 50155":"No","0 to 20 mA":"Yes","EN 50121-4":"No","FM approval":"Yes","KC approval":"Yes","UL approval":"Yes; File E239877","4 mA to 20 mA":"Yes","Shielded, Max.":"800 m","Weight, approx.":"220 g","lifecycle_stage":"current","-20 mA to +20 mA":"No","Diagnostic alarm":"Yes","Power loss, typ.":"6 W","Rated value (DC)":"24 V","For Inductive Load":"0.5 ms","For Resistive Load":"0.1 ms","Between The Channels":"No","Diagnostics function":"Yes","Group error SF (red)":"Yes","EAC (formerly Gost-R)":"Yes","Isolation tested with":"500 V DC","RCM (formerly C-TICK)":"Yes","Number of analog outputs":"8","Required Front Connector":"20-pin","With Current Outputs, Max.":"750 Ω","Reverse polarity protection":"Yes","Diagnostic information readable":"Yes","from backplane bus 5 V DC, max.":"110 mA","Current output, no-load voltage, max.":"24 V","Between The Channels And Backplane Bus":"Yes","Between the channels and load voltage L+":"Yes","Current, relative to output range, (+/-)":"0.1 %","from load voltage L+ (without load), max.":"350 mA","With Current Outputs, Inductive Load, Max.":"10 mH","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Resolution with overrange (bit including sign), max.":"16 bit","Between The Channels And The Power Supply Of The Electronics":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=51944&mlfb=6AG1332-8TF01-4AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6AG1332-8TF01-4AB0/alternatives.json"},"ai":{"faq":[{"question":"What are the key approvals on this module?","answer":"It holds UL (File E239877), CE, FM, KC, EAC, and RCM approvals, covering North America, Europe, Korea, Eurasia, and Australia."},{"question":"What is the maximum load the current outputs can drive?","answer":"With current outputs, the maximum load resistance is 750 Ω per channel. For inductive loads, the maximum inductance is 10 mH."},{"question":"Does the module provide diagnostics?","answer":"Yes. Diagnostic alarms are available per channel, and a red group error SF indicator lights on fault. Diagnostic information is readable via the backplane bus."},{"question":"What is the maximum shielded cable length for the analog outputs?","answer":"Shielded cable length is rated up to 800 m for analog current outputs."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1332-8TF01-4AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1332-8TF01-4AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}