{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1516-3FN02-2AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1516-3FN02-2AB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1516-3FN02-2AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1516-3FN02-2AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS S7-1500 CPU 1516-3 PN/DP, 6AG1516-3FN02-2AB0, extended temperature range -40 to 70 °C, MRP Automanager, PROFIsafe, 32 kbyte process image.","salesMarkdown":"## What this CPU is The 6AG1516-3FN02-2AB0: It supports MRP (Media Redundancy Protocol) as Automanager, Manager, or Client per IEC 62439-2 Ed 2.0, handling up to 50 devices in the ring. MRPD is also available, though it requires IRT frames — note that the CPU itself does not support IRT natively, so MRPD is only functional when a separate IRT-capable device is on the line. Programming languages include LAD, FBD, and SCL, with failsafe logic blocks integrated into both LAD and FBD editors. PROFIsafe is built in, so safety-oriented process data can be mapped without a separate safety module. Process image size is 32 kbyte for both inputs and outputs — comfortable for a medium-sized line but not a large distributed system. If your application exceeds that, you will need to offload to distributed I/O via PROFINET or PROFIBUS. The I²t rating is 0.02 A²·s. DCP (Discovery and Configuration Protocol) is supported, so the CPU can be detected and assigned an IP address via the Siemens tool chain without a separate memory card or DIP switches. MODBUS TCP is also available for integration with third-party HMIs or SCADAs. Up to 8 communication modules (CMs/CPs) can be inserted for additional PROFIBUS, PROFINET, or Ethernet interfaces. That leaves room for expansion beyond the onboard PROFIBUS and PROFINET ports. ## Comparing to the -01 revision (6AG1516-3FN01-2AB0) Supports MRP Automanager per IEC 62439-2 Edition 2.0 for up to 50 devices. IRT not supported; dimensions 70 x 147 x 129 mm.","metaTitle":"6AG1516-3FN02-2AB0 SIPLUS S7-1500 CPU, -40..70°C, MRP","metaDescription":"Siemens SIPLUS CPU 1516-3 PN/DP with extended temperature range -40 to 70 °C. Supports MRP Manager, PROFIsafe, FBD/LAD with failsafe. DCP, MODBUS TCP. Quote to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"129 mm","Width":"70 mm","Height":"147 mm","Backup Time":"6 wk; At 40 °C ambient temperature, typically","Product Type":"Hardware clock","Product Status":"Active","Screen Diagonal":"6.1 cm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2ed26864a4538689e263fb80d426fcbf.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1437351&mlfb=6AG1516-3FN02-2AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6AG1516-3FN02-2AB0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1516-3FN02-2AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1516-3FN02-2AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}