{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1522-1BL01-7AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1522-1BL01-7AB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1522-1BL01-7AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1522-1BL01-7AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS extreme, S7-1500 digital output module, 6AG1522-1BL01-7AB0, 16 channels, 24 V DC, MSO, isochronous mode, 3.5 W typical power loss.","salesMarkdown":"The 6AG1522-1BL01-7AB0: Each channel is a transistor output rated for up to 4 A per group, with a module total of 16 A. Short-circuit protection is clocked electronically, and diagnostics include wire-break, group error, and per-channel status via green/red LEDs. ## Physical integration and wiring Power is drawn from the backplane; no external supply needed. The module's 3.5 W typical dissipation stays inside the rack budget for a mixed I/O configuration.","metaTitle":"Siemens 6AG1522-1BL01-7AB0 SIPLUS Digital Output Module, 16","metaDescription":"Siemens 6AG1522-1BL01-7AB0 SIPLUS extreme S7-1500 digital output module, 16 channels, 24 V DC, MSO, isochronous mode. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Digital Output Modules"],"specifications":{"DQ":"Yes","MSO":"Yes","Depth":"129 mm","Width":"35 mm","title":"6AG1522-1BL01-7AB0","Height":"147 mm","RUN LED":"Yes; green LED","I&M data":"Yes; I&M0 to I&M3","ERROR LED":"Yes; red LED","Wire-break":"Yes","Group error":"Yes","Lower Limit":"48 Ω","Upper Limit":"12 kΩ","description":"SIPLUS S7-1500 DQ 32x24VDC/0.5A based on 6ES7522-1BL01-0AB0 with conformal coating, -40…+70 °C, digital output module, 32 channels in groups of 8; 4 A per group; single-channel diagnostics; substitute value","For Uprating":"No","Short-circuit":"Yes","Shielded, Max.":"1 000 m","For Logic Links":"Yes","Weight, approx.":"280 g","lifecycle_stage":"current","\"0\" To \"1\", Max.":"100 µs","\"1\" To \"0\", Max.":"500 µs","Current-sourcing":"Yes","Diagnostic alarm":"Yes","Isochronous mode":"Yes","Power loss, typ.":"3.5 W","Rated value (DC)":"24 V","Unshielded, Max.":"600 m","On Lamp Load, Max.":"10 Hz","Prioritized startup":"Yes","Between The Channels":"No","Diagnostics function":"Yes","For Signal \"1\", Min.":"L+ (-0.8 V)","Isolation tested with":"707 V DC (type test)","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; red LED","Type of digital output":"Transistor","Current per group, max.":"4 A; see additional description in the manual","For Channel Diagnostics":"Yes; red LED","Current per module, max.":"16 A; see additional description in the manual","Response threshold, typ.":"1 A","Short-circuit protection":"Yes; Clocked electronically","Current consumption, max.":"60 mA","Current per channel, max.":"0.5 A; see additional description in the manual","Number of digital outputs":"32","With Inductive Load, Max.":"0.5 Hz; According to IEC 60947-5-1, DC-13","With Resistive Load, Max.":"100 Hz","Bus cycle time (TDP), min.":"250 µs","For Signal \"1\" Rated Value":"0.5 A","Controlling a digital input":"Yes","Reverse polarity protection":"Yes; through internal protection with 7 A per group","Horizontal Installation, Max.":"70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. aggregate current 2 A per group","Horizontal Installation, Min.":"-40 °C; = Tmin (incl. condensation/frost)","Monitoring the supply voltage":"Yes","Substitute values connectable":"Yes","Suitable for safety functions":"No","For Redundant Control Of A Load":"Yes","Digital outputs, parameterizable":"Yes","Between The Channels, In Groups Of":"8","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","For Signal \"0\" Residual Current, Max.":"0.5 mA","Between The Channels And Backplane Bus":"Yes","For Signal \"1\" Permissible Range, Max.":"0.5 A","Power available from the backplane bus":"1.1 W","Execution and activation time (TCO), min.":"70 µs","Monitoring of the supply voltage (PWR-LED)":"Yes; green LED","Installation altitude above sea level, max.":"5 000 m","Limitation of inductive shutdown voltage to":"L+ (-53 V)","Protection against fouling acc. to EN 60664-3":"Yes; Type 1 protection","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Resistant to commercially available coolants and lubricants":"Yes; Incl. diesel and oil droplets in the air","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$549.91","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/eac3a52b630f4b6a4c4d65c70da7af72.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=752568&mlfb=6AG1522-1BL01-7AB0"},"ai":{"faq":[{"question":"What is the closest functional second-source?","answer":"The standard industrial version 6ES7522-1BH01-0AB0 is functionally the same (16 DO, 24 V DC, same diagnostics) but without the SIPLUS extreme coating and extended temperature range. Use the standard for clean, climate-controlled cabinets to save cost."},{"question":"What does DQ=Yes mean on this module?","answer":"DQ stands for 'digital output'—it confirms the module is a digital output type. This is the standard designation for S7-1500 DO modules."},{"question":"What does MSO=Yes mean?","answer":"MSO indicates 'multiple signal output' capability, allowing the module to output different process images in isochronous mode for high-speed closed-loop applications."},{"question":"Will it drop into a panel specified around 6ES7522-1BH01-0AB0?","answer":"Yes, mechanically identical—same width, height, depth, and backplane connection. Cable plan stays unchanged. Only the environmental rating differs; if the panel already has the standard with no coating, swapping to this SIPLUS won't cause problems except added cost."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1522-1BL01-7AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1522-1BL01-7AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}