{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1543-1MX00-7XE0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1543-1MX00-7XE0","canonicalUrl":"https://aoctrl.com/siemens/6AG1543-1MX00-7XE0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1543-1MX00-7XE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS S7-1500 CP 1543-1 communication processor, double-wide, DNP3 and IEC 60870-5, 20.4-28.8 V DC.","salesMarkdown":"## Where this thing goes The 6AG1543-1MX00-7XE0: Fits into an S7-1500 rack, occupying two slot widths. The 2-pole pluggable terminal block supplies DC power locally if the backplane bus cannot carry it. It's rated for storage from -40 to +70 °C, so it'll survive a cold plant idle weekend or a hot truck ride. Operating temperature isn't listed in the short specs, but the SIPLUS badge usually means it's a step tougher than the standard CP.","metaTitle":"Siemens 6AG1543-1MX00-7XE0 CP 1543-1, DNP3, IEC 60870-5","metaDescription":"Active. SIPLUS S7-1500 communication processor with DNP3 and IEC 60870-5 for substation links. 20.4–28.8 V DC, double-wide. Requires TIA Portal V14 SP1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLC Communication Modules"],"specifications":{"PC":"No","BGP":"No","DCP":"Yes","NTP":"Yes","PPP":"No","DNP3":"Yes","LLDP":"Yes","Note":"Number of TIM per S7-1500: 1","VRRP":"No","Depth":"129 mm","RIPv2":"No","Width":"70 mm","title":"6AG1543-1MX00-7XE0","Height":"147 mm","OSPFv2":"No","RIP v1":"No","Maximum":"132; only via LAN","SNMP v1":"Yes","SNMP v3":"Yes","Required":"STEP 7 Professional V14 SP1 (TIA Portal) or higher","Modbus RTU":"No","Substation":"Yes","IEC 60870-5":"Yes","description":"SIPLUS TIM 1531 IRC based on 6GK7543-1MX00-0XE0 with conformal coating, -40…+70 °C, communications module for SIMATIC S7-1500, S7-400, S7-300 with SINAUT ST7 with three RJ45 interfaces for communication via IP-based networks (WAN / LAN) and an RS-232/RS-485 interface for Communications via classic wide area networks","NTP (secure)":"Yes","Node Station":"Yes","PPoE via DSL":"No","DynDNS client":"No","Module Format":"Compact module S7-1500 double-wide","VRRP for IPv6":"No","At Interface 3":"10 ... 100 Mbit/s","During Storage":"-40 ... +70 °C","I&M3 - comment":"Yes","RIPnG for IPv6":"No","Supply Voltage":"20.4 ... 28.8 V","OSPFv3 for IPv6":"No","from GPS-signal":"No","from NTP-server":"Yes","lifecycle_stage":"current","During Transport":"-40 ... +70 °C","For Memory Cards":"1","For Power Supply":"2-pole plugable terminal block","static IP routing":"Yes","Of The Memory Card":"SD 1.0, SD 1.1, SDHC, Siemens SMC","TIM control center":"Yes","dynamic IP routing":"No","From Control Center":"Yes","PG/OP communication":"Yes","SINAUT ST1 protocol":"No","SINAUT ST7 protocol":"Yes","according to RS 232":"300 ... 115200 bit/s","protection class IP":"IP20","At The 1st Interface":"10 ... 1000 Mbit/s","At The 2nd Interface":"10 ... 100 Mbit/s","Remote Configuration":"Yes","S7-300 rail mounting":"No","Security Information":"Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action(e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. For more information about industrial security, visit http://www.siemens.com/industrialsecurity. To stay informed about product updates as they occur, sign up for a product-specific newsletter. For more information, visit http://support.automation.siemens.com. (V3.4)","Pass On Position Data":"No","S7-1500 rail mounting":"Yes","Remote Firmware Update":"Yes","for Ethernet / maximum":"4","static IP routing IPv6":"Yes","dynamic IP routing IPv6":"No","for SINAUT ST7 protocol":"4","I&M2 - installation date":"Yes","In Update Mode / Typical":"3.9 W","Service / Routing / Note":"IP routing up to 1 Mbps","As Email Client / Maximum":"1","Control Center Connection":"Systems with ST7, DNP3 and IEC 60870-5-101/104 protocol","is supported / MSC protocol":"Yes","position detection with GPS":"No","From Mobile Network Provider":"No","with OP connections / maximum":"4","with PG connections / maximum":"4","product function / MIB support":"Yes","35 mm top hat DIN rail mounting":"No","In Communication Mode / Typical":"3.9 W","SINAUT ST7 via S7 communication":"Yes","with RS 232 interface / maximum":"4","with RS 485 interface / maximum":"30 m","of Industrial Ethernet interface":"RJ45 port","with PG/OP connections / maximum":"4","By Means Of A Permanent Connection":"Systems with ST7, DNP3 and IEC 60870-5-101/104 protocol","I&M0 - device-specific information":"Yes","product function / SICLOCK support":"No","as MSC client / with VPN connection":"1","as MSC server / with VPN connection":"127","conformity according to EN 60721-3-3":"Yes; Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation.","conformity according to EN 60721-3-6":"Yes; Class 6S3 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation.","of SIMATIC communication / as server":"Yes","program download with SIMATIC STEP 7":"Yes","as server / by means of HTTP / maximum":"2","Type Of Voltage / Of The Supply Voltage":"DC","as server / by means of HTTPS / maximum":"2; 2 per Ethernet interface","Product Function / Web-Based Diagnostics":"Yes","Number Of Data Points Per Station / Maximum":"3000","For Vertical Installation / During Operation":"-40 ... +50 °C","Product Component / Hardware Real Time Clock":"No","storage location / of TIM configuration data":"Flash or SD card of the TIM 1531 IRC","MSC client via GPRS modem with MSC capability":"Yes","Product Extension / Optional / Backup Battery":"No","At Interface 1 / For External Data Transmission":"9 pin Sub-D-connector, RS232 switchable to RS485","Product Feature / Buffered Message Frame Memory":"Yes","Product Function / Pass On Time Synchronization":"Yes","Storage Capacity / Of The Memory Card / Maximum":"32 Gibyte","supply voltage / external / at DC / rated value":"20.4 ... 28.8 V","with Virtual Private Network MSC / is supported":"TCP/IP","with dial-up network / with SINAUT ST7 protocol":"spontaneous","For Horizontally Arranged Busbars / During Operation":"-40 ... +70 °C","I&M1 - higher level designation/location designation":"Yes","for external data transmission / according to RS 232":"1","number of interfaces / according to Industrial Ethernet":"3","Product Function / Data Buffering If Connection Is Aborted":"Yes; 100000 data telegrams (ST7) or 250000 events (IEC 60870-5 / DNP3)","Product Feature / Hardware Real Time Clock W. Battery Backup":"No","diagnostics function / online diagnostics with SIMATIC STEP 7":"Yes","Chemical Resistance / To Commercially Available Cooling Lubricants":"Yes; incl. airborne diesel and oil droplets","Ambient Condition / Relating To Ambient Temperature - Air Pressure - Installation Altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$3,460.75","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/126b2a7ce775a5aba9d0fafaa6bbfdf4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1268872&mlfb=6AG1543-1MX00-7XE0"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1543-1MX00-7XE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1543-1MX00-7XE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}