{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ED1052-2HB00-0BA8","brand":"Siemens","brandSlug":"siemens","productSlug":"6ED1052-2HB00-0BA8","canonicalUrl":"https://aoctrl.com/siemens/6ED1052-2HB00-0BA8","factsUrl":"https://aoctrl.com/api/mcp/products/6ED1052-2HB00-0BA8","rawCanonicalId":null},"summary":{"shortDescription":"Siemens LOGO! 24RCEO logic module, 6ED1052-2HB00-0BA8, 24V DC/24V AC supply, 8 digital inputs, 4 relay outputs (10A resistive/3A inductive), without display, 400-block memory, Ethernet, web server, data logging, 55°C max.","salesMarkdown":"## What you're getting This is a current-production LOGO! 24RCEO logic module – part number 6ED1052-2HB00-0BA8 – built for 24V DC or 24V AC supply. It gives you 8 digital inputs and 4 relay outputs rated 10A resistive, 3A inductive. No display, so you program it via LOGO! Soft Comfort V8 or higher. Ethernet onboard for web server and data logging, and a 480-hour power reserve keeps your program alive when the mains drops. Temperature range is 0°C to 55°C standard; if you're running the FS04 firmware version, the low end stretches to -20°C. That 55°C ceiling means it'll sit inside a hot panel without cooking. Out here in the grease, I've buried plenty of logic modules that couldn't take the heat – this one keeps ticking. Approvals include UL, CSA, FM, Marine, CE, and VDE/IEC compliance, with Limit class B for residential area use. ## Panel fitting and wiring Snap it onto 35 mm DIN rail – four spacing units, 71.5 mm wide, 90 mm tall, 58 mm deep. No short-circuit protection built in; you'll need external fusing per the wiring diagram. Relay outputs are rated 10 A resistive, 3 A inductive – that inductive number matters if you're switching contactors or solenoids. Inputs are 24V DC/AC, 47–63 Hz. Power reserve of 480 hours ties into the internal capacitor – no battery to swap. Handy if you lose line power over a long weekend. The Ethernet port gives you a web server for remote monitoring and data logging. Programming goes through LOGO! Soft Comfort V8 or higher; older projects need conversion. We source it to order against your RFQ. Provide quantity and target delivery, and we'll quote firm pricing. Standard lead times apply through Siemens channels.","metaTitle":"Siemens 6ED1052-2HB00-0BA8 LOGO! 24RCEO, 55°C","metaDescription":"Active Siemens LOGO! 24RCEO logic module. 24V DC/24V AC, 8DI/4DO relay, 10A resistive, 3A inductive. UL/CSA/FM/Marine. DIN rail 4SU. Sourced to order – submit RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Max.":"55 °C","Min.":"0 °C; LOGO! 8 FS04 and higher: -20 °C","Depth":"58 mm","Width":"71.5 mm","Height":"90 mm","Number":"190","24 V AC":"Yes","24 V DC":"Yes","CE mark":"Yes","Mounting":"on 35 mm DIN rail, 4 spacing units wide","FM approval":"Yes","UL approval":"Yes","CSA approval":"Yes","Power reserve":"480 h","Marine approval":"Yes","lifecycle_stage":"current","according to VDE 0631":"Yes","Number of digital inputs":"8","Short-circuit protection":"No; external fusing necessary","Number of digital outputs":"4; Relays","With Inductive Load, Max.":"3 A","With Resistive Load, Max.":"10 A","Permissible Range, Lower Limit":"47 Hz","Permissible Range, Upper Limit":"63 Hz","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","developed in accordance with IEC 61131":"Yes","Limit class B, for use in residential areas":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a73ac12e4471645b99f8c88c58a26207.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=327462&mlfb=6ED1052-2HB00-0BA8","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ED1052-2HB00-0BA8/alternatives.json"},"ai":{"faq":[{"question":"What is the maximum operating temperature?","answer":"Maximum operating temperature is 55 °C. The minimum is 0 °C, or -20 °C for LOGO! 8 FS04 and higher firmware versions."},{"question":"Will 6ED1052-2HB00-0BA8 drop into a panel specified for 6ED1052-1MD00-0BA6 without rewiring?","answer":"No – the supply voltage differs (24V vs 12V). The footprint is nearly identical (71.5 mm vs 72 mm, both 4 spacing units), so mechanical fit is fine, but you must rewire the power input and check programming cable compatibility."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ED1052-2HB00-0BA8","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ED1052-2HB00-0BA8 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}