{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6EP1323-2BA00","brand":"Siemens","brandSlug":"siemens","productSlug":"6EP1323-2BA00","canonicalUrl":"https://aoctrl.com/siemens/6EP1323-2BA00","factsUrl":"https://aoctrl.com/api/mcp/products/6EP1323-2BA00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SITOP PSU8200, 6EP1323-2BA00, 24 VDC / 14 A, 85-264 VAC input, DIN rail mount, IP20.","salesMarkdown":"## Power supply for control cabinets — 24 VDC, 14 A, wide-range input The Siemens 6EP1323-2BA00 is a SITOP PSU8200 power supply delivering 24 VDC at 14 A from a single-phase AC input covering 85-132 V or 170-264 V (auto-ranging), 47-63 Hz. It's built for 24 V control loops in industrial panels — PLCs, I/O racks, contactor coils, and instrumentation. Rated output holds at 14 A up to +50 °C ambient; above that, derate 3.5% per Kelvin up to +70 °C. For a 60 °C cabinet, expect about 12.2 A continuous — plan the load margin accordingly. The unit snaps onto standard DIN rail EN 60715 35×7.5/15. Keep 50 mm free above and below for convection airflow — that's the clearance that avoids thermal throttling. cULus-Listed to UL 508 and CSA C22.2 No. 107.1 (file E197259), plus cCSAus to UL/CSA 60950-1 for ITE. CE and EAC marked. That covers North American and European panel builds — no extra NRTL paperwork needed for a UL 508A panel. DNV GL marine type approval is on file, so it's accepted for shipboard electrical rooms and offshore packages without a separate certification run. Safety extra-low output voltage (SELV) per EN 60950-1 and EN 50178 — the 24 VDC rail is touch-safe for dry locations. ## Sourcing and lifecycle — active, quoted to order MTBF at 40 °C is 1,614,510 hours — roughly 184 years continuous. That's calculated per Siemens reliability data; real-world field life depends on thermal cycling and load profile, but it's a solid number for a 24 V supply in a controlled environment. Recommended upstream protection: a 10 A characteristic C miniature circuit breaker in the feeder.","metaTitle":"Siemens 6EP1323-2BA00 SITOP PSU8200, 14 A, 24 VDC","metaDescription":"Siemens 6EP1323-2BA00 SITOP PSU8200 power supply, 24 VDC / 14 A, 85-264 VAC input, UL/CSA listed, DIN rail mount. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["DIN Rail Power Supplies"],"specifications":{"Top":"50 mm","ATEX":"No","Left":"0 mm","IECEx":"No","Right":"0 mm","title":"6EP1323-2BA00","Bottom":"50 mm","DNV GL":"Yes","1 at AC":"85 ... 132 V","2 at AC":"170 ... 264 V","Maximum":"3.5 mA","Typical":"0.8 mA","At Input":"L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded","At Output":"+, -: 2 screw terminals each for 0.5 ... 2.5 mm²","CE marking":"Yes","NEC Class 2":"No","Rated Range":"0 ... 14 A; +50 ... +70 °C: Derating 3.5%/K","Rated Value":"14 A","UL approval":"Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)","description":"SITOP PSU100S 12 V/14 A stabilized power supply input: 120/230 V AC output: 12 V DC/14 A *Ex approval no longer available*","CSA approval":"Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)","EAC approval":"Yes","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","In The Feeder":"Recommended miniature circuit breaker: from 10 A characteristic C","Initial Value":"Automatic range selection","During Storage":"-40 ... +85 °C","Line Frequency":"47 ... 63 Hz","MTBF at 40 °C":"1 614 510 h","FM registration":"No","lifecycle_stage":"current","During Operation":"-25 ... +70 °C; with natural convection","During Transport":"-40 ... +85 °C","Fastening Method":"Snaps onto DIN rail EN 60715 35x7.5/15","Other Information":"Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)","ULhazloc approval":"No","Galvanic Isolation":"Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178","1 at AC rated value":"120 V","2 at AC rated value":"230 V","protection class IP":"IP20","Fuse Protection Type":"T 6.3 A/250 V (not accessible)","Bridging Of Equipment":"Yes","Efficiency In Percent":"87 %","For Signaling Contact":"2 screw terminals for 0.5 ... 2.5 mm²","Shipbuilding Approval":"DNV GL","Depth Of The Enclosure":"120 mm","For Auxiliary Contacts":"Alarm signals: 2 screw terminals for 0.5 ... 2.5 mm²","Response Delay Maximum":"0.3 s","Width Of The Enclosure":"70 mm","Height Of The Enclosure":"125 mm","Voltage Curve At Output":"Controlled, isolated DC voltage","For Emitted Interference":"EN 55022 Class B","Nippon Kaiji Kyokai (NK)":"No","Type Of Signal At Output":"Relay contact (NO contact, rating 60 V DC/ 0.3 A) for 12 V OK","Adjustable Output Voltage":"11.5 ... 15.5 V","For Interference Immunity":"EN 61000-6-2","Load Step 10 To 90% Typical":"1 ms","Load Step 90 To 10% Typical":"1 ms","cCSAus, Class 1, Division 2":"No","at rated input voltage 120 V":"3.24 A","at rated input voltage 230 V":"1.41 A","Supplied Active Power Typical":"168 W","Type Of Electrical Connection":"screw-type terminals","at output 1 at DC rated value":"12 V","For Mains Harmonics Limitation":"EN 61000-3-2","Type Of Output Voltage Setting":"via potentiometer","Overvoltage Overload Capability":"2.3 × Vin rated, 1.3 ms","Design Of Input Wide Range Input":"No","Type Of The Power Supply Network":"1-phase AC","output voltage at DC rated value":"12 V","At Short-Circuit During Operation":"800 ms","Lloyds Register of Shipping (LRS)":"No","Response Value Current Limitation":"14 ... 16.4 A","Design Of Short-Circuit Protection":"Constant current characteristic","On Slow Fluctuation Of Ohm Loading":"1 %","Operating Resource Protection Class":"Class I","Design Of The Overvoltage Protection":"< 20 V","Display Version For Normal Operation":"Green LED for 12 V OK","On Slow Fluctuation Of Input Voltage":"0.1 %","On Short-Circuiting During The Start-Up":"800 ms","At Short-Circuit During Operation Typical":"40 A","French marine classification society (BV)":"No","Relative Overall Tolerance Of The Voltage":"3 %","Operating Condition Of The Mains Buffering":"at Vin = 93/187 V","Product Function Output Voltage Adjustable":"Yes","Property Of The Output Short-Circuit Proof":"Yes","Galvanic Isolation Between Input And Output":"Yes","American Bureau of Shipping Europe Ltd. (ABS)":"No","environmental category according to IEC 60721":"Climate class 3K3, 5 … 95% no condensation","On Short-Circuiting During The Start-Up Typical":"40 A","Behavior Of The Output Voltage When Switching On":"Overshoot of Vout < 3 %","Overcurrent Overload Capability In Normal Operation":"overload capability 150 % Iout rated up to 5 s/min","current limitation of inrush current at 25 °C maximum":"60 A","Product Feature Of The Enclosure Housing Can Be Lined Up":"Yes","At Rated Output Voltage For Rated Value Of The Output Current Typical":"24 W","Number Of Parallel-Switched Equipment Resources For Increasing The Power":"2","Buffering Time For Rated Value Of The Output Current In The Event Of Power Failure Minimum":"20 ms"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$249.22","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/afae4e48c53f83b18d6f13a3844691b1.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=185828&mlfb=6EP1323-2BA00"},"ai":{"faq":[{"question":"What compliance documentation does the 6EP1323-2BA00 carry?","answer":"cULus-Listed (UL 508, CSA C22.2 No. 107.1), cCSAus (UL/CSA 60950-1), CE, EAC, and DNV GL marine type approval. SELV output per EN 60950-1 and EN 50178."},{"question":"What clearance is needed above and below the unit?","answer":"50 mm free space above and below for natural convection cooling. The unit is rated for -25 to +70 °C operation with that clearance."},{"question":"Does the 6EP1323-2BA00 have ATEX or IECEx certification?","answer":"No. ATEX and IECEx are not listed; the unit is intended for general-purpose and marine (DNV GL) environments, not hazardous locations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6EP1323-2BA00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6EP1323-2BA00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}