{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6EP1332-5BA10","brand":"Siemens","brandSlug":"siemens","productSlug":"6EP1332-5BA10","canonicalUrl":"https://aoctrl.com/siemens/6EP1332-5BA10","factsUrl":"https://aoctrl.com/api/mcp/products/6EP1332-5BA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SITOP PSU100M power supply, 6EP1332-5BA10, 4 A rated output, 110-300 VDC input, IP20, snaps onto DIN rail EN 60715.","salesMarkdown":"## Power Supply for DC-Bus Applications The 4 A rating holds up to +55 °C ambient; above that, derate 3% per K, reaching 2.2 A at +70 °C — so if your enclosure runs hot, size for the derated figure, not the headline 4 A. ## Clearance and Mounting Requires 50 mm clearance above and below the unit for natural convection cooling — no forced air needed, but don't box it in. Left and right clearance is 0 mm, so units can be ganged side-by-side without spacing. IP20 rated, so it's for clean, dry enclosures only; not for washdown or outdoor locations. ## Input and Protection AC input range 100-230 V, 47-63 Hz; DC input range 85-264 V (110-300 V rated). Internal fuse protection; the feeder should use a 16 A characteristic B or 10 A characteristic C MCB. Maximum I²t is 3 A²·s. MTBF at 40 °C is 2,726,727 hours.","metaTitle":"Siemens 6EP1332-5BA10 Power Supply, 4 A, 110-300 VDC Input","metaDescription":"Siemens 6EP1332-5BA10 power supply, 4 A rated output, 110-300 VDC input, UL/CSA listed, DIN rail mount. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["DIN Rail Power Supplies"],"specifications":{"Top":"50 mm","ATEX":"No","Left":"0 mm","IECEx":"No","Right":"0 mm","at DC":"110 ... 300 V","title":"6EP1332-5BA10","Bottom":"50 mm","DNV GL":"Yes","Maximum":"3.5 mA","Typical":"0.4 mA","At Input":"L, N, PE: Removable screw terminal, each for 1 x 0.5 ... 2.5 mm²","At Output":"+: 1 screw terminal for 0.5 ... 2.5 mm²; -: 2 screw terminals for 0.5 ... 2.5 mm²","CE marking":"Yes","NEC Class 2":"No","Rated Range":"0 ... 4 A; +55 ... +70 °C: Derating 3%/K; at +70 °C Iout rated 2.2 A","Rated Value":"4 A","UL approval":"Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)","description":"SITOP PSU100C 24 V/4 A stabilized power supply input: 120-230 V AC (110-300 V DC) output: 24 V DC/4 A *Ex approval no longer available*","CSA approval":"Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)","EAC approval":"Yes","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","In The Feeder":"Recommended miniature circuit breaker: from 16 A characteristic B or from 10 A characteristic C","Initial Value":"85 V","During Storage":"-40 ... +85 °C","Line Frequency":"47 ... 63 Hz","MTBF at 40 °C":"2 726 727 h","FM registration":"No","lifecycle_stage":"current","During Operation":"-20 ... +70 °C; with natural convection","During Transport":"-40 ... +85 °C","Fastening Method":"Snaps onto DIN rail EN 60715 35x7.5/15","Full-Scale Value":"264 V","I2t value maximum":"3 A²·s","Other Information":"Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)","ULhazloc approval":"No","Galvanic Isolation":"Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178","Maximum Rated Value":"230 V","Minimum Rated Value":"100 V","protection class IP":"IP20","Fuse Protection Type":"internal","Bridging Of Equipment":"Yes; Start-up with single nominal load only","Efficiency In Percent":"88 %","Shipbuilding Approval":"ABS, DNV GL","Depth Of The Enclosure":"100 mm","Electrical Accessories":"Removable spring-type terminal 6EP1971-5BA00","Response Delay Maximum":"1.5 s","Width Of The Enclosure":"52.5 mm","Height Of The Enclosure":"80 mm","Voltage Curve At Output":"Controlled, isolated DC voltage","For Emitted Interference":"EN 55022 Class B","Nippon Kaiji Kyokai (NK)":"No","Adjustable Output Voltage":"22.2 ... 26.4 V","For Interference Immunity":"EN 61000-6-2","Load Step 10 To 90% Typical":"4 ms","Load Step 90 To 10% Typical":"4 ms","cCSAus, Class 1, Division 2":"No","at rated input voltage 100 V":"2.25 A","at rated input voltage 230 V":"1.15 A","Supplied Active Power Typical":"96 W","Type Of Electrical Connection":"screw-type terminals","at output 1 at DC rated value":"24 V","For Mains Harmonics Limitation":"EN 61000-3-2","Type Of Output Voltage Setting":"via potentiometer","Overvoltage Overload Capability":"2.3 × Vin rated, 1.3 ms","Design Of Input Wide Range Input":"Yes","During NO-Load Operation Maximum":"0.75 W","Type Of The Power Supply Network":"1-phase AC or DC","output voltage at DC rated value":"24 V","Lloyds Register of Shipping (LRS)":"No","Design Of Short-Circuit Protection":"Electronic shutdown, automatic restart","On Slow Fluctuation Of Ohm Loading":"0.2 %","Operating Resource Protection Class":"Class I","Design Of The Overvoltage Protection":"Yes, according to EN 60950-1","Display Version For Normal Operation":"Green LED for output voltage OK","On Slow Fluctuation Of Input Voltage":"0.1 %","French marine classification society (BV)":"No","Relative Overall Tolerance Of The Voltage":"3 %","Operating Condition Of The Mains Buffering":"at Vin = 230 V","Product Function Output Voltage Adjustable":"Yes","Property Of The Output Short-Circuit Proof":"Yes","Galvanic Isolation Between Input And Output":"Yes","American Bureau of Shipping Europe Ltd. (ABS)":"Yes","environmental category according to IEC 60721":"Climate class 3K3, 5 … 95% no condensation","Behavior Of The Output Voltage When Switching On":"Overshoot of Vout approx. 1 %","current limitation of inrush current at 25 °C maximum":"34 A","Product Feature Of The Enclosure Housing Can Be Lined Up":"Yes","At Rated Output Voltage For Rated Value Of The Output Current Typical":"13 W","Number Of Parallel-Switched Equipment Resources For Increasing The Power":"2","Buffering Time For Rated Value Of The Output Current In The Event Of Power Failure Minimum":"20 ms","Relative Control Precision Of The Output Voltage With Rapid Fluctuation Of The Input Voltage By +/- 15% Typical":"0.1 %"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$76.20 – $168.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e9d7f5cd548653e4b5dd8bad8b62945f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=170856&mlfb=6EP1332-5BA10"},"ai":{"faq":[{"question":"What approvals does 6EP1332-5BA10 carry?","answer":"CE, UL (cULus-Listed to UL 508 and CSA C22.2 No. 107.1), CSA (cCSAus to CSA C22.2 No. 60950-1 and UL 60950-1), EAC, and DNV GL marine. Not ATEX, IECEx, or NEC Class 2."},{"question":"Where can I buy 6EP1332-5BA10?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"What is the top clearance required for 6EP1332-5BA10?","answer":"50 mm above and below for natural convection cooling; 0 mm left and right allows side-by-side ganging."},{"question":"Does 6EP1332-5BA10 have ATEX certification?","answer":"No, ATEX and IECEx are not listed for this unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6EP1332-5BA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6EP1332-5BA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}