{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6EP1336-3BA10","brand":"Siemens","brandSlug":"siemens","productSlug":"6EP1336-3BA10","canonicalUrl":"https://aoctrl.com/siemens/6EP1336-3BA10","factsUrl":"https://aoctrl.com/api/mcp/products/6EP1336-3BA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SITOP PSU100M, 6EP1336-3BA10, 20 A rated, 120-230 V AC/DC input, DIN rail mount, IP20.","salesMarkdown":"The Siemens 6EP1336-3BA10 is a SITOP power supply delivering a rated 20 A at 24 V DC from a 120-230 V AC or 88-350 V DC input. The 20 A rated current is the continuous output at 25 °C; above 60 °C derate 3% per Kelvin up to 70 °C. That matters for a panel running warm near other heat sources — plan your thermal budget around the derating curve, not the headline number. Input accepts 120-230 V AC (45-65 Hz) or 88-350 V DC. Below 100 V AC or DC the unit needs additional temperature derating down to 50 °C. If your site has a weak or fluctuating line, factor that in. The recommended feeder breaker is a 10 A characteristic C for single-phase, or a 2-pole breaker for two-phase. The 6EP1336-3BA10 carries CE, cULus (UL 508, CSA C22.2 No. 107.1), cCSAus (UL/CSA 60950-1), EAC, and DNV GL marine approvals. It is not ATEX or IECEx rated — keep it out of hazardous areas.","metaTitle":"Siemens 6EP1336-3BA10 Power Supply, 20 A, 120-230 V AC/DC","metaDescription":"Siemens 6EP1336-3BA10 power supply, 20 A rated, 120-230 V AC/DC input, UL 508 listed, DIN rail mount, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["DIN Rail Power Supplies"],"specifications":{"Top":"50 mm","ATEX":"No","Left":"0 mm","IECEx":"No","Right":"0 mm","at DC":"88 ... 350 V","title":"6EP1336-3BA10","Bottom":"50 mm","DNV GL":"Yes","Maximum":"3.5 mA","Typical":"1 mA","At Input":"L, N, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded","At Output":"+, -: 2 screw terminals each for 0.2 ... 4 mm²","CE marking":"Yes","NEC Class 2":"No","Rated Range":"0 ... 20 A; +60 ... +70 °C: Derating 3%/K","Rated Value":"20 A","UL approval":"Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)","description":"SITOP PSU8200 20 A stabilized power supply input: 120-230 V AC 110-220 V DC output: 24 V DC/20 A *Ex approval no longer available*","CSA approval":"Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)","EAC approval":"Yes","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","In The Feeder":"Recommended miniature circuit breaker at 1-phase operation: 10 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2711-1HD10 (UL 489) at 120 V or 3RV2711-1ED10 (UL 489) at 230 V","Initial Value":"85 V; Derating of temperature necessary down to 50 °C at Vin < 100 V AC or DC","During Storage":"-40 ... +85 °C","Line Frequency":"45 ... 65 Hz","MTBF at 40 °C":"667 048 h","FM registration":"No","lifecycle_stage":"current","During Operation":"-25 ... +70 °C; With natural convection; startup tested starting from -40 °C nominal voltage","During Transport":"-40 ... +85 °C","Fastening Method":"Snaps onto DIN rail EN 60715 35x7.5/15","Full-Scale Value":"275 V","I2t value maximum":"5 A²·s","Other Information":"Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)","ULhazloc approval":"No","Galvanic Isolation":"Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178","Maximum Rated Value":"230 V","Minimum Rated Value":"120 V","protection class IP":"IP20","Fuse Protection Type":"Yes","Bridging Of Equipment":"Yes; switchable characteristic","Efficiency In Percent":"93 %","Shipbuilding Approval":"ABS, DNV GL","Depth Of The Enclosure":"125 mm","Electrical Accessories":"Buffer module","For Auxiliary Contacts":"13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²","Mechanical Accessories":"Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20","Response Delay Maximum":"1.5 s","Width Of The Enclosure":"90 mm","Height Of The Enclosure":"125 mm","Voltage Curve At Output":"Controlled, isolated DC voltage","For Emitted Interference":"EN 55022 Class B","Nippon Kaiji Kyokai (NK)":"No","Type Of Signal At Output":"Relay contact (NO contact, rating 60 V DC/ 0.3 A) for \"24 V OK\"","Adjustable Output Voltage":"24 ... 28.8 V","For Interference Immunity":"EN 61000-6-2","cCSAus, Class 1, Division 2":"No","Load Step 100 To 50% Typical":"1 ms","Load Step 50 To 100% Typical":"1 ms","at rated input voltage 120 V":"4.6 A","at rated input voltage 230 V":"2.5 A","Supplied Active Power Typical":"480 W","Type Of Electrical Connection":"screw-type terminals","at output 1 at DC rated value":"24 V","For Mains Harmonics Limitation":"EN 61000-3-2","Type Of Output Voltage Setting":"via potentiometer","Design Of Input Wide Range Input":"Yes","Type Of The Power Supply Network":"1-phase and 2-phase AC or DC","output voltage at DC rated value":"24 V","At Short-Circuit During Operation":"25 ms","Lloyds Register of Shipping (LRS)":"No","Design Of Short-Circuit Protection":"Alternatively, constant current characteristic approx. 23 A or latching shutdown","On Slow Fluctuation Of Ohm Loading":"0.3 %","Operating Resource Protection Class":"Class I","Design Of The Overvoltage Protection":"< 33 V","Display Version For Normal Operation":"Green LED for 24 V OK","On Slow Fluctuation Of Input Voltage":"0.1 %","At Short-Circuit During Operation Typical":"60 A","French marine classification society (BV)":"No","Relative Overall Tolerance Of The Voltage":"3 %","Operating Condition Of The Mains Buffering":"at Vin = 230 V","Product Function Output Voltage Adjustable":"Yes","Property Of The Output Short-Circuit Proof":"Yes","Galvanic Isolation Between Input And Output":"Yes","American Bureau of Shipping Europe Ltd. (ABS)":"Yes","environmental category according to IEC 60721":"Climate class 3K3, 5 … 95% no condensation","Display Version For Overload And Short Circuit":"LED yellow for \"overload\", LED red for \"latching shutdown\"","On Short-Circuiting During The Start-Up Typical":"30 A","Behavior Of The Output Voltage When Switching On":"No overshoot of Vout (soft start)","Overcurrent Overload Capability In Normal Operation":"overload capability 150 % Iout rated up to 5 s/min","current limitation of inrush current at 25 °C maximum":"20 A","Product Feature Of The Enclosure Housing Can Be Lined Up":"Yes","At Rated Output Voltage For Rated Value Of The Output Current Typical":"42 W","Number Of Parallel-Switched Equipment Resources For Increasing The Power":"2","Buffering Time For Rated Value Of The Output Current In The Event Of Power Failure Minimum":"20 ms","Relative Control Precision Of The Output Voltage With Rapid Fluctuation Of The Input Voltage By +/- 15% Typical":"0.5 %"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$207.80 – $406.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e9d7f5cd548653e4b5dd8bad8b62945f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=385111&mlfb=6EP1336-3BA10"},"ai":{"faq":[{"question":"What approvals does 6EP1336-3BA10 carry?","answer":"CE, cULus (UL 508, CSA C22.2 No. 107.1), cCSAus (UL/CSA 60950-1), EAC, and DNV GL marine. No ATEX or IECEx."},{"question":"What is the recommended input protection?","answer":"For single-phase: a 10 A characteristic C miniature circuit breaker. For two-phase: a 2-pole breaker or Siemens 3RV2 series (3RV2711-1HD10 at 120 V, 3RV2711-1ED10 at 230 V)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6EP1336-3BA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6EP1336-3BA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}