{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6EP3436-8SB00-2AY0","brand":"Siemens","brandSlug":"siemens","productSlug":"6EP3436-8SB00-2AY0","canonicalUrl":"https://aoctrl.com/siemens/6EP3436-8SB00-2AY0","factsUrl":"https://aoctrl.com/api/mcp/products/6EP3436-8SB00-2AY0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SITOP PSU, 6EP3436-8SB00-2AY0, DIN rail power supply, 20 A output, 400–500 V AC input, PROFINET, galvanic isolation.","salesMarkdown":"## DIN Rail Power Supply – 20 A, SITOP Line The 6EP3436-8SB00-2AY0: Snaps onto standard EN 60715 35×15 mm DIN rail with zero side clearance, 50 mm top and bottom for ventilation. Output rated 20 A with natural convection up to 60 °C ambient; above 50 °C derate 2.5%/K unless the CNX8600 expansion module is used (no derating with that module up to 240 W total load). Galvanic isolation to SELV per EN 60950-1 and EN 50178. Requires a 3-pole miniature circuit breaker 6–16 A characteristic C (or Siemens 3RV2011-1DA10, 3 A setting) in the feeder. Input plug-in terminal accepts 0.2–4 mm² single-wire or fine-stranded; output uses two screw connectors 0.2–4 mm². ## Mounting & Derating DIN rail clearance: 50 mm top, 50 mm bottom, zero on sides. Operating ambient -25 to +60 °C with natural convection; storage/transport -40 to +85 °C. Input voltage range 400–500 V AC (320–360 V and 530–575 V with derating), 47–63 Hz. Line frequency 50/60 Hz rated. PROFINET protocol onboard for integration into automation networks. Output specifications at rated input voltage and +25 °C unless otherwise noted. For loads above 50 °C ambient, apply derating curve or use expansion module CNX8600 to maintain full 20 A output. Keep inductive loads' free-wheel diode polarity correct to avoid damage to the output stage.","metaTitle":"Siemens 6EP3436-8SB00-2AY0, 20A DIN Rail PSU, PROFINET","metaDescription":"Siemens 6EP3436-8SB00-2AY0 is a current-production DIN-rail power supply, 20 A output, 400–500 V AC input. Approvals include UL, CSA, EAC, DNV GL, CE. Galvanic isolation to SELV. S","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["DIN Rail Power Supplies"],"specifications":{"Top":"50 mm","ATEX":"No","Left":"0 mm","IECEx":"No","Right":"0 mm","title":"6EP3436-8SB00-2AY0","Bottom":"50 mm","C-Tick":"No","DNV GL":"Yes","Maximum":"3.5 mA","At Input":"L1, L2, L3, PE: Plug-in terminal with 1 screwed connection each for 0.2 ... 4 mm² single-wire / fine stranded","At Output":"Output: plug-in terminals with 2 screw connectors for 0.2 ... 4 mm²; 0 V: screw terminal with 3 screw connectors for 0.2 ... 4 mm²","CE marking":"Yes","Per Output":"20 A","NEC Class 2":"No","Rated Range":"0 ... 20 A; +50 ... +60 °C: Derating 2.5%/K; no derating in connection with expansion module CNX8600 and total load of the outputs at the basic device max. 240 W","Rated Value":"20 A","UL approval":"Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)","description":"SITOP PSU8600 3AC 20 A PN stabilized power supply input: 400-500 V 3 AC output: 24 V DC/20 A with PN/IE connection web server integrated OPC UA server integrated *Ex approval no longer available*","CSA approval":"Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)","EAC approval":"Yes","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","In The Feeder":"Required: 3-pole connected miniature circuit breaker 6 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)","Initial Value":"320 V; Derating 320 … 360 and 530 … 575 V","During Storage":"-40 ... +85 °C","Line Frequency":"47 ... 63 Hz","MTBF at 40 °C":"298 979 h","FM registration":"No","lifecycle_stage":"current","During Operation":"-25 ... +60 °C; with natural convection","During Transport":"-40 ... +85 °C","Fastening Method":"Snaps onto DIN rail EN 60715 35x15","Full-Scale Value":"575 V","I2t value maximum":"1.2 A²·s","Number Of Outputs":"1","Other Information":"Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)","PROFINET protocol":"Yes","ULhazloc approval":"No","Galvanic Isolation":"Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178","Maximum Rated Value":"500 V","Minimum Rated Value":"400 V","protection class IP":"IP20","Bridging Of Equipment":"Yes; suitable output characteristics via DIP switch can be selected","Efficiency In Percent":"93 %","For Signaling Contact":"11, 12, 14 (alarm signal): Plug-in terminal (together with Reset) with 1 screwed connection each for 0.2 ... 1.5 mm²","Of The Excess Current":"Ia >1.0…<1.5 x Ia threshold permissible for 5 s; Ia limit (= 1.5 x Ia threshold) permissible for 200 ms","Remote Reset Function":"Non-electrically isolated 24 V input (signal level \"high\" at > 15 V)","Shipbuilding Approval":"ABS, DNV GL","Depth Of The Enclosure":"150 mm","Electrical Accessories":"Expansion modules CNX8600, buffer modules BUF8600, module UPS8600","For Auxiliary Contacts":"RST (Reset): Plug-in terminal (together with alarm signal) with 1 screwed connection for 0.2 ... 1.5 mm²","Mechanical Accessories":"Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20","Response Delay Maximum":"1 s","Width Of The Enclosure":"80 mm","At Output 1 Rated Value":"20 A","Design Of The Interface":"Ethernet/PROFINET","Height Of The Enclosure":"125 mm","Voltage Curve At Output":"Controlled, isolated DC voltage","For Emitted Interference":"EN 55022 Class B","Nippon Kaiji Kyokai (NK)":"No","Type Of Signal At Output":"Relay contact (changeover contact, contact current capacity DC 60 V/0.3 A) for \"Operating state OK\"","Adjustable Output Voltage":"4 ... 28 V","For Interference Immunity":"EN 61000-6-2","Of The Current Limitation":"Ia limit (= 1.5 x Ia threshold) permissible for 5 s, afterwards Ia threshold continuous","Type Of Outputs Connection":"Simultaneous connecting-in of all outputs after device booting or delay time of 25 ms, 100 ms or \"load-optimized\" for sequential cutting-in of the outputs via DIP switches can be set (only with expansion module CNX8600)","Removable Terminal At Input":"Yes","cCSAus, Class 1, Division 2":"No","Removable Terminal At Output":"Yes","at rated input voltage 400 V":"1.4 A","at rated input voltage 500 V":"1.1 A","protocol is supported OPC UA":"Yes","Supplied Active Power Typical":"480 W","Type Of Electrical Connection":"Plug-in terminals with screwed connection","at output 1 at DC rated value":"24 V","For Mains Harmonics Limitation":"EN 61000-3-2","Type Of Output Voltage Setting":"via potentiometer or IE/PN interface; Derating > 24 V: 4%/V; max. 480 W overall system","Type Of Response Value Setting":"via potentiometer or IE/PN interface","Design Of Input Wide Range Input":"Yes","During NO-Load Operation Maximum":"12 W","Type Of The Power Supply Network":"3-phase AC","output voltage at DC rated value":"24 V","At Short-Circuit During Operation":"25 ms","Lloyds Register of Shipping (LRS)":"No","Design Of Short-Circuit Protection":"Electronic overload shutdown; optional constant-current operation can be selected via DIP switch","On Slow Fluctuation Of Ohm Loading":"0.1 %","Operating Resource Protection Class":"Class I","Design Of The Overvoltage Protection":"max. 35 V (max. 500 ms)","Display Version For Normal Operation":"3-color LED for operating state device; LED for operating mode manual/remote; 4 LEDs for communication PROFINET; 3-color LED for operating state output","On Slow Fluctuation Of Input Voltage":"0.2 %","At Short-Circuit During Operation Typical":"60 A; only in operation without CNX8600 extension module","Design Of The Interface For Communication":"PROFINET/Ethernet: two RJ45 sockets (2-port switch)","French marine classification society (BV)":"No","Relative Overall Tolerance Of The Voltage":"3 %","Operating Condition Of The Mains Buffering":"at Vin = 400 V; prioritized supply of the output in case of power failure selectable via DIP switch (only in conjunction with CNX8600 expansion module)","Product Function Output Voltage Adjustable":"Yes","Property Of The Output Short-Circuit Proof":"Yes","Suitability For Interaction Modular System":"Yes","Galvanic Isolation Between Input And Output":"Yes","American Bureau of Shipping Europe Ltd. (ABS)":"Yes","environmental category according to IEC 60721":"Climate class 3K3, 5 … 95% no condensation","Design Of The Reset Device/Resetting Mechanism":"via sensor or IE/PN interface","Display Version For Overload And Short Circuit":"3-color LED for operating state device; 3-color LED for operating state output","Behavior Of The Output Voltage When Switching On":"No overshoot of Vout (soft start)","Overcurrent Overload Capability In Normal Operation":"Total system overloadable 150% Ia rated to 5 s/min","current limitation of inrush current at 25 °C maximum":"14 A","Product Feature Of The Enclosure Housing Can Be Lined Up":"Yes","At Rated Output Voltage For Rated Value Of The Output Current Typical":"34 W","Number Of Parallel-Switched Equipment Resources For Increasing The Power":"2","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2 ... 20 A","Buffering Time For Rated Value Of The Output Current In The Event Of Power Failure Minimum":"15 ms","Relative Control Precision Of The Output Voltage With Rapid Fluctuation Of The Input Voltage By +/- 15% Typical":"0.1 %"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$358.14 – $563.13","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bf383fc437904e693ba1786c54ba30b1.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=630257&mlfb=6EP3436-8SB00-2AY0"},"ai":{"faq":[{"question":"What approvals does this power supply carry?","answer":"CE, cULus (UL 508, CSA C22.2 No. 107.1), cCSAus (UL 60950-1, CSA C22.2 No. 60950-1), EAC, and DNV GL (marine). No ATEX, IECEx, FM, or UL hazloc rating."},{"question":"What is the output current and derating requirement?","answer":"Rated output current is 20 A. Above 50 °C ambient, derate 2.5%/K unless using the CNX8600 expansion module, which allows no derating up to 240 W total load."},{"question":"What upstream protection is required?","answer":"A 3-pole miniature circuit breaker 6–16 A characteristic C, or a Siemens 3RV2011-1DA10 (set to 3 A) or 3RV2711-1DD10 (UL 489)."},{"question":"What are the DIN rail clearance requirements?","answer":"50 mm clearance above and below, zero on the sides. The unit snaps onto a 35×15 mm rail per EN 60715."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6EP3436-8SB00-2AY0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6EP3436-8SB00-2AY0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}