{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6EP7133-6AB00-0BN0","brand":"Siemens","brandSlug":"siemens","productSlug":"6EP7133-6AB00-0BN0","canonicalUrl":"https://aoctrl.com/siemens/6EP7133-6AB00-0BN0","factsUrl":"https://aoctrl.com/api/mcp/products/6EP7133-6AB00-0BN0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SITOP PSU8200, 6EP7133-6AB00-0BN0, 6 A power supply, 85-132 V / 170-264 V AC input, 50 mm width, ATEX II 3G.","salesMarkdown":"The Siemens 6EP7133-6AB00-0BN0 is a SITOP PSU8200 power supply rated for 6 A output, with a continuous 5 A up to +60 °C and derating above that. It accepts dual AC input ranges — 85…132 V or 170…264 V — and automatically selects the range. Output is safety extra-low voltage (SELV) per EN 60950-1 and EN 50178, so it can supply control circuits without additional isolation. The 50 mm height and 0 mm left/right clearance requirements mean it packs tightly into a crowded cabinet — no side breathing gaps needed. ## Certifications and approvals This unit carries ATEX II 3G Ex ec nC IIC T3 Gc and IECEx Ex ec nC IIC T3 Gc, making it suitable for Zone 2 gas environments. UL and CSA listings cover UL 61010-2-201, CSA C22.2 No. 142, plus ITE safety standards (UL 60950-1, CSA C22.2 No. 60950-1). CE, UKCA, EAC, and C-Tick marks are also present. Marine approval from DNV GL is on file. Output side has two PushIn terminals per polarity (+ and -) for the same wire range. The recommended upstream protective device is a B/C 6 A or 3 A miniature circuit breaker. Operating temperature range is -30…+70 °C with natural convection; storage and transport range is -40…+85 °C. The MTBF at 40 °C is 1 598 441 hours. I²t value is 3.15 A²·s, useful for fuse coordination.","metaTitle":"Siemens 6EP7133-6AB00-0BN0 SITOP PSU8200, 6 A, 50 mm","metaDescription":"Siemens 6EP7133-6AB00-0BN0 SITOP PSU8200 power supply, 6 A rated, 5 A at 60°C, ATEX II 3G, cULus listed. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["DIN Rail Power Supplies"],"specifications":{"Top":"50 mm","ATEX":"Yes; ATEX (EX) II 3G Ex ec nC IIC T3 Gc","Left":"0 mm","IECEx":"Yes; IECEx Ex ec nC IIC T3 Gc","Right":"0 mm","title":"6EP7133-6AB00-0BN0","Bottom":"50 mm","C-Tick":"Yes","DNV GL":"Yes","1 at AC":"85 ... 132 V","2 at AC":"170 ... 264 V","Maximum":"3.5 mA","Typical":"1 mA","At Input":"L, N, PE: 1 PushIn terminal each for 0.2 ... 2.5 mm² single-core/finely stranded","At Output":"+, -: 2 PushIn terminals each for 0.2 ... 2.5 mm²","CE marking":"Yes","NEC Class 2":"No","Rated Range":"0 ... 6 A; 5 A up to +60°C; +60 ... +70 °C: Derating 3%/K","Rated Value":"5 A","UL approval":"Yes; cULus-Listed (UL61010-2-201, CSA C22.2 No.142); cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)","description":"SIMATIC ET 200SP PS 24V/5A Stabilized power supply Input: 120/230 V AC Output: 24 V DC/5 A","CSA approval":"Yes; cULus-Listed (UL61010-2-201, CSA C22.2 No.142), cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)","EAC approval":"Yes","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","In The Feeder":"recommended LS switch: B/C 6 A/3 A","Initial Value":"Automatic range selection","During Storage":"-40 ... +85 °C","Line Frequency":"47 ... 63 Hz","MTBF at 40 °C":"1 598 441 h","lifecycle_stage":"current","During Operation":"-30 ... +70 °C; with natural convection","During Transport":"-40 ... +85 °C","Fastening Method":"Snaps onto DIN rail EN 60715 35x7.5/15","relating to ATEX":"IECEx Ex ec nC IIC T3 Gc; ATEX (EX) II 3G Ex ec nC IIC T3 Gc","I2t value maximum":"3.15 A²·s","Other Information":"Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)","ULhazloc approval":"No","Galvanic Isolation":"Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178","1 at AC rated value":"120 V","2 at AC rated value":"230 V","protection class IP":"IP20","Fuse Protection Type":"T 3,15 A/250 V (not accessible)","Bridging Of Equipment":"Yes","Efficiency In Percent":"88 %","For Signaling Contact":"2 push-in terminals for 0.2 ... 2.5 mm²","Shipbuilding Approval":"BV, DNV GL","Depth Of The Enclosure":"74 mm","Electrical Accessories":"redundancy module, buffer module, selectivity module, DC UPS","For Auxiliary Contacts":"Signaling contact: 2 push-in terminals for 0.2 ... 2.5 mm²","Response Delay Maximum":"0.3 s","Width Of The Enclosure":"160 mm","Height Of The Enclosure":"117 mm","Voltage Curve At Output":"Controlled, isolated DC voltage","For Emitted Interference":"EN 61000-6-3 Class B","Nippon Kaiji Kyokai (NK)":"No","Type Of Signal At Output":"Relay contact (NO contact, rating 60 V DC/ 0.3 A) for \"24 V OK\"","Adjustable Output Voltage":"22.8 ... 28 V","For Interference Immunity":"EN 61000-6-2","Load Step 10 To 90% Typical":"1 ms","Load Step 90 To 10% Typical":"1 ms","Removable Terminal At Input":"Yes","cCSAus, Class 1, Division 2":"No","Removable Terminal At Output":"Yes","at rated input voltage 120 V":"2.16 A","at rated input voltage 230 V":"1.22 A","Supplied Active Power Typical":"120 W","Type Of Electrical Connection":"Push-in terminals","at output 1 at DC rated value":"24 V","For Mains Harmonics Limitation":"EN 61000-3-2","Type Of Output Voltage Setting":"via potentiometer","Overvoltage Overload Capability":"2.3 × Vin rated, 1.3 ms","Design Of Input Wide Range Input":"No","During NO-Load Operation Maximum":"2.7 W","Type Of The Power Supply Network":"1-phase AC","output voltage at DC rated value":"24 V","At Short-Circuit During Operation":"800 ms","Lloyds Register of Shipping (LRS)":"No","Response Value Current Limitation":"7 ... 7.5 A","Design Of Short-Circuit Protection":"Constant current characteristic","On Slow Fluctuation Of Ohm Loading":"1 %","Operating Resource Protection Class":"Class I","Design Of The Overvoltage Protection":"protection against overvoltage in case of internal fault Vout < 31.8 V","Display Version For Normal Operation":"Green LED for 24 V OK","On Slow Fluctuation Of Input Voltage":"0.1 %","On Short-Circuiting During The Start-Up":"800 ms","At Short-Circuit During Operation Typical":"15 A","French marine classification society (BV)":"Yes","Relative Overall Tolerance Of The Voltage":"3 %","Operating Condition Of The Mains Buffering":"at Vin = 93/187 V","Product Function Output Voltage Adjustable":"Yes","Property Of The Output Short-Circuit Proof":"Yes","Galvanic Isolation Between Input And Output":"Yes","American Bureau of Shipping Europe Ltd. (ABS)":"No","environmental category according to IEC 60721":"Climate class 3K3, 5 … 95% no condensation","On Short-Circuiting During The Start-Up Typical":"15 A","Behavior Of The Output Voltage When Switching On":"Overshoot of Vout < 3 %","Overcurrent Overload Capability In Normal Operation":"overload capability 150 % Iout rated up to 5 s/min","current limitation of inrush current at 25 °C maximum":"45 A","Product Feature Of The Enclosure Housing Can Be Lined Up":"Yes","At Rated Output Voltage For Rated Value Of The Output Current Typical":"17 W","Number Of Parallel-Switched Equipment Resources For Increasing The Power":"2","Buffering Time For Rated Value Of The Output Current In The Event Of Power Failure Minimum":"20 ms","Relative Control Precision Of The Output Voltage With Rapid Fluctuation Of The Input Voltage By +/- 15% Typical":"0.3 %"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$323.65","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ef152b67b37d6b1f8ec067df68149de3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1110011&mlfb=6EP7133-6AB00-0BN0"},"ai":{"faq":[{"question":"What approvals does this power supply carry?","answer":"It holds ATEX II 3G, IECEx, cULus (UL 61010-2-201, CSA C22.2 No. 142), cCSAus (UL 60950-1, CSA C22.2 No. 60950-1), CE, UKCA, EAC, C-Tick, and DNV GL marine approval."},{"question":"What is the output current rating and derating?","answer":"Rated output is 6 A. At +60 °C the continuous rating is 5 A; above +60 °C up to +70 °C, derate by 3% per Kelvin."},{"question":"What input voltage ranges does it accept?","answer":"Two ranges: 85…132 V AC and 170…264 V AC, with automatic selection. Line frequency is 47…63 Hz."},{"question":"Will 6EP7133-6AB00-0BN0 drop into a panel specified for 6EP1336-3BA00?","answer":"Both are 50 mm wide DIN-rail power supplies from the SITOP family, but the 6EP1336-3BA00 is a higher-current unit (10 A). The 6EP7133-6AB00-0BN0 has a lower output rating and different input terminal layout — verify load current and wiring before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6EP7133-6AB00-0BN0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6EP7133-6AB00-0BN0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}