{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7132-0BH01-0XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7132-0BH01-0XB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7132-0BH01-0XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7132-0BH01-0XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC DP, digital output module, 16 outputs, 24 V DC, 2 A, PROFIBUS DP, 6ES7132-0BH01-0XB0.","salesMarkdown":"## 16 outputs at 2 A — the per-channel budget that decides the load The 6ES7132-0BH01-0XB0 is a Siemens SIMATIC DP digital output module with 16 channels, each rated 24 V DC. The per-channel current ceiling is 2 A, but the module's total output is split as 2x 2 A and 6x 0.5 A — meaning only two channels can carry the full 2 A simultaneously; the remaining six are limited to 0.5 A each. That asymmetry matters when you're mapping solenoid banks or contactor coils across the card. ## PROFIBUS DP at 12 Mbit/s — the bus that sets the scan cycle The module communicates over PROFIBUS DP at up to 12 Mbit/s, which is the standard fieldbus for this generation of SIMATIC DP slaves. The backplane is isolated between the electronics and the PROFIBUS DP interface, so a bus fault on the network side won't drag down the module's logic supply. ## I2t of 0.05 A²·s — the inrush that blows fuses if ignored The listed I2t of 0.05 A²·s with starting current inrush is the energy the output stage can handle during capacitive or lamp loads. If your load draws a cold-filament inrush above this threshold, the electronic short-circuit protection (present on every channel) will trip and latch off. For incandescent indicators or capacitive-coupled valves, size the load so the inrush energy stays under 0.05 A²·s.","metaTitle":"Siemens 6ES7132-0BH01-0XB0 Digital Output Module, 16 DO","metaDescription":"Siemens 6ES7132-0BH01-0XB0 digital output module, 16 outputs, 24 V DC, 2 A per channel, PROFIBUS DP. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Digital Output Modules"],"specifications":{"I2t":"0.05 A²·s; with starting current inrush","Depth":"60 mm; EB and TB","Width":"160 mm; EB and TB","title":"6ES7132-0BH01-0XB0","Height":"130 mm; EB and TB","RUN LED":"Yes","description":"*** SPARE PART*** SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 16DO 24V DC, (12X0.5A; 4X2A), DEGR. OF PROTECT. IP20,STANDARD","Operation, max.":"95 %; RH class 2 in accordance with IEC 1131-2","Operation, min.":"15 %","SYNC capability":"Yes","Weight, approx.":"600 g; EB and TB","lifecycle_stage":"current","Power loss, max.":"5 W","Rated value (DC)":"24 V","Unshielded, Max.":"100 m","Bus fault BF (red)":"Yes","On Lamp Load, Max.":"8 Hz","up to 60 °C, max.":"4 A","For Signal \"0\", Max.":"2 V; idling","For Signal \"1\", Min.":"UE -3 V","Usable terminal block":"TB1/DC, TB1-4/DC, TB3/DC, TB3-4/DC","Transmission rate, max.":"12 Mbit/s","Short-circuit protection":"Yes; Electronic","Current consumption, typ.":"80 mA; from L3+; logic","Number of digital outputs":"16","With Inductive Load, Max.":"0.5 Hz","With Resistive Load, Max.":"100 Hz","Controlling a digital input":"Yes","Horizontal Installation, Max.":"60 °C; 40°C for other mountings","Horizontal Installation, Min.":"0 °C","Permissible Range, Lower Limit":"795 hPa","Permissible Range, Upper Limit":"1 080 hPa","Between The Channels, In Groups Of":"8","Bus protocol/transmission protocol":"PROFIBUS DP","tested according to IEC 60068-2-27":"Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms","permissible range, lower limit (DC)":"18.5 V","permissible range, upper limit (DC)":"30.2 V","Potential separation digital outputs":"No","For Signal \"0\" Residual Current, Max.":"1 mA","For Signal \"1\" Permissible Range, Max.":"2 A; 2x 2 A and 6x 0.5 A","Status indicator digital output (green)":"Yes","between electronic block and PROFIBUS DP":"Yes","Limitation of inductive shutdown voltage to":"typ. (L1+, L2+) -55 V","Operation, tested according to IEC 60068-2-6":"Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)","Design of electrical connection for the inputs and outputs":"Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$217.17","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5444c2a6d45e12e1a825e1259ff12c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=385229&mlfb=6ES7132-0BH01-0XB0"},"ai":{"faq":[{"question":"What is the I2t rating of 6ES7132-0BH01-0XB0?","answer":"The I2t is 0.05 A²·s with starting current inrush — this is the energy limit the output stage can handle before the electronic short-circuit protection trips."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7132-0BH01-0XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7132-0BH01-0XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}