{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7132-0GF00-0XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7132-0GF00-0XB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7132-0GF00-0XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7132-0GF00-0XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC DP electronic module, 8 relay outputs, 24-60 VDC, for ET 200B, 160 mm width, IP20, PROFIBUS DP.","salesMarkdown":"## What the I2t rating means for your fuse selection The 6ES7132-0GF00-0XB0 carries an I2t rating of 0.05 A²·s, measured with starting current inrush. That figure is what you hand to the panel builder for sizing the branch-circuit fuse or breaker protecting this module — it tells you the energy the output circuit can withstand before the semiconductor junction lets go. A fuse with a lower I2t let-through than the module's rating will clear before the module fails. This is a spare-part designation for the SIMATIC DP electronic module used in the ET 200B distributed I/O system. It provides 8 relay outputs rated for 24 V DC to 60 V DC, with resistive load capacity of 2 A at 24 V DC, 1.5 A at 48 V DC, and 1 A at 60 V DC. ## PROFIBUS DP integration and physical fit The module communicates over PROFIBUS DP at up to 12 Mbit/s, with a bus fault LED (red) and a RUN LED for status at a glance. It supports SYNC capability for coordinated output updates across multiple stations on the bus. ## Output ratings and channel isolation Each of the 8 relay outputs is individually isolated — there is no grouping of channels. The module provides potential separation between the electronic block and the PROFIBUS DP bus, and between the digital outputs themselves. This matters when you are driving loads on different voltage potentials from the same module. Maximum inductive load switching is 0.5 A at 30 V DC. The module does not include short-circuit protection on the outputs, so each output circuit needs its own overcurrent protection device sized per the I2t rating. ## Environmental limits and operating conditions Rated for horizontal installation from 0 °C to 60 °C (derated to 40 °C for other mounting orientations). Humidity tolerance spans 15 % to 95 % RH, Class 2 per IEC 1131-2. The module is tested to IEC 60068-2-27 for shock (15 g, 11 ms half-sine) and IEC 60068-2-6 for vibration (10-150 Hz, 1 g constant acceleration). Typical power loss is 2 W. Current consumption from the L3+ logic supply is 130 mA. The permissible DC supply range is 18.5 V to 30.2 V.","metaTitle":"Siemens 6ES7132-0GF00-0XB0 Digital Output Module","metaDescription":"Siemens 6ES7132-0GF00-0XB0 SIMATIC DP electronic module for ET 200B. 8 relay outputs, 24-60 VDC, PROFIBUS DP. I2t 0.05 A²·s. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Digital Output Modules"],"specifications":{"I2t":"0.05 A²·s; with starting current inrush","Depth":"60 mm; EB and TB","Width":"160 mm; EB and TB","Height":"130 mm; EB and TB","RUN LED":"Yes","Operation, max.":"95 %; RH class 2 in accordance with IEC 1131-2","Operation, min.":"15 %","SYNC capability":"Yes","Weight, approx.":"650 g; EB and TB","lifecycle_stage":"current","Power loss, typ.":"2 W","Rated value (DC)":"24 V; 24 V DC to 60 V DC","Unshielded, Max.":"100 m","Bus fault BF (red)":"Yes","Usable terminal block":"TB1/DC, TB1-4/DC, TB3/DC, TB3-4/DC","Transmission rate, max.":"12 Mbit/s","Short-circuit protection":"No","Current consumption, typ.":"130 mA; from L3+; logic","Number of digital outputs":"8; Relays","With Inductive Load, Max.":"0.5 A; at 30 V DC","With Resistive Load, Max.":"2 A; at 24 V DC; max. 1.5 A at 48 V DC; max. 1 A at 60 V DC","Controlling a digital input":"Yes","Horizontal Installation, Max.":"60 °C; 40°C for other mountings","Horizontal Installation, Min.":"0 °C","Permissible Range, Lower Limit":"795 hPa","Permissible Range, Upper Limit":"1 080 hPa","Thermal continuous current, max.":"5 A","Between The Channels, In Groups Of":"1","Bus protocol/transmission protocol":"PROFIBUS DP","tested according to IEC 60068-2-27":"Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms","permissible range, lower limit (DC)":"18.5 V","permissible range, upper limit (DC)":"30.2 V","Potential separation digital outputs":"Yes","Status indicator digital output (green)":"Yes","between electronic block and PROFIBUS DP":"Yes","Operation, tested according to IEC 60068-2-6":"Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)","Design of electrical connection for the inputs and outputs":"Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5444c2a6d45e12e1a825e1259ff12c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=92902&mlfb=6ES7132-0GF00-0XB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7132-0GF00-0XB0/alternatives.json"},"ai":{"faq":[{"question":"Does the 6ES7132-0GF00-0XB0 work with ET 200B?","answer":"Yes. The module is specifically designated as a spare part for the SIMATIC DP ET 200B distributed I/O system, with a 160 mm width matching the ET 200B enclosure format."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7132-0GF00-0XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7132-0GF00-0XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}