{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7132-1JH00-0XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7132-1JH00-0XB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7132-1JH00-0XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7132-1JH00-0XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC DP, ET 200S electronic module, 16 DO relay outputs, 24 V DC/120 V AC, PROFIBUS DP, diagnostics, current production.","salesMarkdown":"## What's in the box — 16 relay outputs on PROFIBUS The 6ES7132-1JH00-0XB0: Diagnostics are built in — the module flags bus faults via a red BF LED and reports channel-level faults. The SYNC capability means it can be used for time-critical output updates across the network. ## Derating that matters — current vs. temperature Output current per channel is 1 A up to 40 °C, but drops to 1 000 mA at 60 °C in horizontal mounting. If you're stacking modules in a warm cabinet, budget that derating into your load calculations. The module measures 191 mm wide, 85.5 mm deep, 61 mm tall — not tiny, so check your DIN rail real estate. The usable terminal block is a TB 16L AC, and the module plugs into the ET 200S rail. Max transmit rate of 6 Mbit/s means it fits fast segments, but keep unshielded cable runs under 600 m and shielded under 1 000 m.","metaTitle":"Siemens 6ES7132-1JH00-0XB0 SIMATIC DP 16DO Relay, PROFIBUS","metaDescription":"Siemens SIMATIC DP ET 200S electronic module, 16 relay outputs, 24 V DC/120 V AC, PROFIBUS DP, diagnostics, still in active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Digital Output Modules"],"specifications":{"Depth":"85.5 mm","Width":"191 mm","title":"6ES7132-1JH00-0XB0","Alarms":"No","Height":"61 mm","description":"*** SPARE PART*** SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, 16 RELAY OUTPUT, 120V AC CAN BE PLUGGED INTO TB16L AC","For Uprating":"No","Shielded, Max.":"1 000 m","Operation, max.":"95 %; RH class 2 in accordance with IEC 1131-2","Operation, min.":"5 %","SYNC capability":"Yes","Weight, approx.":"302 g","lifecycle_stage":"current","\"0\" To \"1\", Max.":"10 ms","\"1\" To \"0\", Max.":"10 ms","Power loss, typ.":"25.6 W","Rated value (AC)":"120 V","Rated value (DC)":"24 V","Unshielded, Max.":"600 m","Bus fault BF (red)":"Yes","On Lamp Load, Max.":"1 Hz","up to 40 °C, max.":"1 A","up to 60 °C, max.":"1 000 mA","Between The Channels":"Yes","Diagnostics function":"Yes","For Signal \"1\", Min.":"Ua - 1 V","Isolation tested with":"1 500 V AC","Usable terminal block":"TB 16L AC","IP degree of protection":"IP20","Transmission rate, max.":"6 Mbit/s; 9,6 / 19,2 / 93,75 / 187,5 / 500 kbit/s; 1,5 / 3 / 6 Mbit/s","Number of digital outputs":"16; Relays","With Inductive Load, Max.":"0.5 Hz","With Resistive Load, Max.":"10 Hz","Controlling a digital input":"Yes","from supply voltage L1, max.":"220 mA","Horizontal Installation, Max.":"60 °C; 40°C for other mountings","Horizontal Installation, Min.":"0 °C","Permissible Range, Lower Limit":"795 hPa","Permissible Range, Upper Limit":"1 080 hPa","For Redundant Control Of A Load":"Yes","Bus protocol/transmission protocol":"PROFIBUS DP","tested according to IEC 60068-2-27":"Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms","between the channels and PROFIBUS DP":"Yes","For Signal \"0\" Residual Current, Max.":"0 mA","For Signal \"1\" Permissible Range, Max.":"2 A","For Signal \"1\" Permissible Range, Min.":"10 mA","Status indicator digital output (green)":"Yes","Mains/voltage failure stored energy time":"20 ms","Monitoring 24 V voltage supply ON (green)":"Yes","Operation, tested according to IEC 60068-2-6":"Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)","Size of motor starters according to NEMA, max.":"Size 5 to NEMA (up to 40 °C); size 4 to NEMA (up to 60 °C)","Direct data exchange (slave-to-slave communication)":"Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC)","between PROFIBUS DP and all other circuit components":"Yes","Design of electrical connection for the inputs and outputs":"Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,207.17","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5444c2a6d45e12e1a825e1259ff12c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=63688&mlfb=6ES7132-1JH00-0XB0"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7132-1JH00-0XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7132-1JH00-0XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}