{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7132-4HB01-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7132-4HB01-0AB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7132-4HB01-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7132-4HB01-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC DP, 5 electronic modules for ET 200S, 2 DO relay 24 V DC-230 V AC/5 A, 15 mm width, Substitute value output with LED SF (group fault) 5 units per packing unit.","salesMarkdown":"## Integrator note The 6ES7132-4HB01-0AB0: Outputs are relay type, isolating between channels and between channels and backplane bus. Short-circuit protection is not built in; external fusing must be provided per channel or per module depending on load. On CPU/master STOP, the module can substitute a value or keep the last value. Substitute values are connectable as 0 or 1. Diagnostics function is not available, so channel monitoring relies on the green status LED. Slides into an ET 200S terminal module; 15 mm width matches a single slot. Reverse polarity protection is present on the supply. Inductive load switching is limited to 0.5 Hz; resistive load or lamp load to 2 Hz. Minimum load current for reliable contact wetting is 8 mA. Status indicator per channel shows signal state via green LED. No short-circuit protection onboard; coordinate external fusing per the load type.","metaTitle":"Siemens 6ES7132-4HB01-0AB0 SIMATIC DP 2 DO Relay 5A","metaDescription":"Current-production Siemens 6ES7132-4HB01-0AB0 ET 200S module, 2 relay outputs rated 5A, 24V DC, 15mm width. Sourced to order – confirm fit for your BOM. RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Digital Output Modules"],"specifications":{"Depth":"52 mm","Width":"15 mm","title":"6ES7132-4HB01-0AB0","Height":"81 mm","description":"SIMATIC DP, 5 electronic modules for ET 200S, 2 DO relay 24 V DC-230 V AC/5 A, 15 mm width, Substitute value output with LED SF (group fault) 5 units per packing unit","With Packing":"2 bit","Shielded, Max.":"1 000 m","Weight, approx.":"50 g","lifecycle_stage":"current","Power loss, typ.":"0.6 W","Rated value (DC)":"24 V; From power module","Unshielded, Max.":"600 m","On Lamp Load, Max.":"2 Hz","Between The Channels":"Yes","Diagnostics function":"No","Type of digital output":"Relays","Short-circuit protection":"No","Number of digital outputs":"2","With Inductive Load, Max.":"0.5 Hz","With Resistive Load, Max.":"2 Hz","For Signal \"1\" Rated Value":"5 A","Controlling a digital input":"Yes","Response to CPU/master STOP":"Substitute a value/keep last value","Reverse polarity protection":"Yes","Substitute values connectable":"Yes; 0/1","Address space per module, max.":"1 byte","Thermal continuous current, max.":"5 A","from backplane bus 3.3 V DC, max.":"10 mA","For Signal \"1\" Minimum Load Current":"8 mA","Between The Channels And Backplane Bus":"Yes","Status indicator digital output (green)":"Yes","Between the channels and load voltage L+":"Yes","from load voltage L+ (without load), max.":"30 mA","Limitation of inductive shutdown voltage to":"No","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$44.44","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5444c2a6d45e12e1a825e1259ff12c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=273288&mlfb=6ES7132-4HB01-0AB0"},"ai":{"faq":[{"question":"What are the width and depth of this module?","answer":"Width is 15 mm, depth is 52 mm."},{"question":"Does this module include diagnostics?","answer":"No, it does not have a diagnostics function."},{"question":"Can this module switch inductive loads?","answer":"Yes, but at a maximum switching frequency of 0.5 Hz."},{"question":"Is the 6AG1123-2DB03-2AX0 a functional substitute?","answer":"No, that is an HMI panel with a completely different form factor and function. It is not an ET 200S digital output module."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7132-4HB01-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7132-4HB01-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}