{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7132-6BF01-2BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7132-6BF01-2BA0","canonicalUrl":"https://aoctrl.com/siemens/6ES7132-6BF01-2BA0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7132-6BF01-2BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200SP digital output module, 6ES7132-6BF01-2BA0, DQ type, 4 A at 24 VDC, 15 mm wide, with wire-break and short-circuit diagnostics.","salesMarkdown":"## What this DQ module does in an ET 200SP rack The 6ES7132-6BF01-2BA0 is a digital output module for the Siemens ET 200SP distributed I/O system. It provides four channels of 24 VDC sourcing outputs (DQ type), each rated up to 4 A continuous at 50 °C and the same at 60 °C — no derating between those temperatures, which is unusual for a 15 mm-wide module. The output switches from 0 to 1 in 50 µs at rated load, and from 1 to 0 in 100 µs — fast enough for most valve banks and contactor coils, but not for PWM or isochronous motion axes (MSO and PWM are both listed as No). ## Base unit and wiring constraints This module snaps onto a BU type A0 base unit — that's the standard 15 mm-wide carrier for ET 200SP. The base unit provides the backplane bus connection and the field wiring terminals. For 2-wire and 3-wire sensors, the A0 base unit handles the connections directly; for 4-wire devices you need an additional potential distributor module. ## Diagnostics that save a service call Module-wise wire-break detection is built in — it flags an open load on any channel. The diagnostic threshold range is 48 Ω to 12 kΩ, which covers most solenoid and relay coil circuits. Short-circuit to M and short-circuit to L+ are also detected module-wise, and a group error signal is generated. Diagnostic alarms are supported, and I&M data (I&M0 through I&M3) is available for asset tracking in TIA Portal. Firmware version is V0.0, and no firmware update is possible — the module ships with the factory version. ## Cable length and load limits Unshielded cable runs up to 600 m are allowed; shielded runs up to 1 000 m. The maximum lamp load switching frequency is 10 Hz — fine for indicator lamps, not for strobes or fast pulsing loads. Typical power loss is 1 W. The minimum signal-1 voltage is L+ minus 0.8 V, so at 24 V supply the output holds above 23.2 V at rated current — enough margin for most 24 VDC loads.","metaTitle":"Siemens 6ES7132-6BF01-2BA0 Digital Output Module, 4 A, DQ","metaDescription":"Siemens 6ES7132-6BF01-2BA0 ET 200SP digital output module, 4 A at 24 VDC, DQ type, with wire-break and short-circuit diagnostics.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Digital Output Modules"],"specifications":{"DQ":"Yes","MSO":"No","PWM":"No","Depth":"58 mm","Width":"15 mm","Height":"73 mm","I&M data":"Yes; I&M0 to I&M3","Wire-break":"Yes; Module-wise","Group error":"Yes","Lower Limit":"48 Ω","Upper Limit":"12 kΩ","For Uprating":"No","Oversampling":"No","Shielded, Max.":"1 000 m","Weight, approx.":"30 g","lifecycle_stage":"current","\"0\" To \"1\", Max.":"50 µs; at rated load","\"1\" To \"0\", Max.":"100 µs; at rated load","Current-sourcing":"Yes","Diagnostic alarm":"Yes","Firmware version":"V0.0","Isochronous mode":"No","Power loss, typ.":"1 W","Rated value (DC)":"24 V","Unshielded, Max.":"600 m","usable BaseUnits":"BU type A0","1-Wire Connection":"BU type A0","2-Wire Connection":"BU type A0","3-Wire Connection":"BU type A0 with AUX terminals or potential distributor module","4-Wire Connection":"BU type A0 + Potential distributor module","Automatic encoding":"Yes","FW update possible":"No","On Lamp Load, Max.":"10 Hz","Short-circuit to M":"Yes; Module-wise","up to 50 °C, max.":"4 A","up to 60 °C, max.":"4 A","Short-circuit to L+":"Yes; Module-wise","Between The Channels":"No","Diagnostics function":"Yes","For Signal \"1\", Min.":"L+ (-0.8 V)","HW functional status":"From FS02","Isolation tested with":"707 V DC (type test)","SIL acc. to IEC 61508":"SIL 2","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red DIAG LED","Type of digital output":"Source output (PNP, current-sourcing)","For Channel Diagnostics":"No","Current per module, max.":"4 A","Response threshold, typ.":"1 A","Short-circuit protection":"Yes","Current consumption, max.":"35 mA; without load","Current per channel, max.":"0.5 A","Mechanical coding element":"Yes","Number of digital outputs":"8","With Inductive Load, Max.":"2 Hz","With Resistive Load, Max.":"100 Hz","For Signal \"1\" Rated Value":"0.5 A","Controlling a digital input":"Yes","Reverse polarity protection":"Yes","Vertical Installation, Max.":"50 °C","Vertical Installation, Min.":"-30 °C; < 0 °C as of FS02","Horizontal Installation, Max.":"60 °C","Horizontal Installation, Min.":"-30 °C; < 0 °C as of FS02","Monitoring the supply voltage":"Yes","Substitute values connectable":"Yes","Suitable for safety functions":"No","Address space per module, max.":"1 byte; + 1 byte for QI information","DQ with energy-saving function":"No","For Redundant Control Of A Load":"Yes","Digital outputs, parameterizable":"Yes","Type of mechanical coding element":"Type A","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","For Signal \"0\" Residual Current, Max.":"0.1 mA","Between The Channels And Backplane Bus":"Yes","For Signal \"1\" Permissible Range, Max.":"0.5 A","PROFIBUS from GSD version/GSD revision":"One GSD file each, Revision 3 and 5 and higher","PROFINET from GSD version/GSD revision":"GSDML V2.3","Monitoring of the supply voltage (PWR-LED)":"Yes; green PWR LED","PCS 7 configurable/integrated from version":"V8.1 SP1","Performance level according to ISO 13849-1":"PL d","Installation altitude above sea level, max.":"5 000 m; Restrictions for installation altitudes > 2 000 m, see manual","Limitation of inductive shutdown voltage to":"Typ. L+ (-50 V)","STEP 7 configurable/integrated from version":"V5.5 SP3 or higher","STEP 7 TIA Portal configurable/integrated from version":"V14","Suitable for safety-related tripping of standard modules":"Yes; see FAQ Entry ID: 39198632","Color code for module-specific color identification plate":"CC02","Between The Channels And The Power Supply Of The Electronics":"No"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$49.53 – $147.42","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/250cde3702b3bddfe2b30e1873f99264.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1075397&mlfb=6ES7132-6BF01-2BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7132-6BF01-2BA0/alternatives.json"},"ai":{"faq":[{"question":"What is the output type of Siemens 6ES7132-6BF01-2BA0?","answer":"It is a DQ (digital output) module — 24 VDC sourcing outputs, 4 channels, rated 4 A per channel. It does not support MSO or PWM output types."},{"question":"Is 6ES7132-6BF01-2BA0 compatible with ET 200SP base unit type A0?","answer":"Yes, it uses BU type A0 base units exclusively. For 2-wire and 3-wire connections the A0 base unit is sufficient; for 4-wire connections you need an additional potential distributor module."},{"question":"What diagnostics are available on 6ES7132-6BF01-2BA0?","answer":"Module-wise wire-break detection (48 Ω to 12 kΩ threshold), short-circuit to M, short-circuit to L+, diagnostic alarms, and group error indication. I&M data I&M0 through I&M3 is supported."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7132-6BF01-2BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7132-6BF01-2BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}