{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7133-0BN11-0XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7133-0BN11-0XB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7133-0BN11-0XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7133-0BN11-0XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200S digital I/O module, 6ES7133-0BN11-0XB0, 24 inputs/8 outputs, 24V DC, 2A output current, 12 Mbit/s PROFIBUS.","salesMarkdown":"The Siemens 6ES7133-0BN11-0XB0 is a current-production ET 200S digital input/output module with 24 inputs and 8 outputs, all at 24 V DC. It handles up to 2 A per output at 60 °C ambient, with an electronic short-circuit protection that limits let-through energy to 0.05 A²·s (I²t) — a number you'll want for sizing the DC supply and the wire protection on the 8 output channels. ## Outputs and protection Each of the 8 digital outputs switches 2 A resistive load at 100 Hz max, or 0.5 Hz with inductive loads. The 2 A is derated from the module's max power loss of 5.5 W; if the panel pushes 60 °C or you install the module vertically, the horizontal rating drops to 40 °C. The I²t of 0.05 A²·s with starting current inrush tells you the thermal stress during a short — fuse the output group accordingly. The red BF (bus fault) LED and green RUN LED are on the front. Input response from '0' to '1' is 20 µs; '1' to '0' is 0.5 ms — fast enough for counters but not for high-speed pulse trains. If you need synchronous gating, wire the SYNC input on the terminal block.","metaTitle":"Siemens 6ES7133-0BN11-0XB0 ET 200S 24DI/8DO, 2A","metaDescription":"Active ET 200S module with 24 digital inputs and 8 digital outputs, 2A per output at 60°C, 12 Mbit/s PROFIBUS. Spec into BOM.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Digital Output Modules"],"specifications":{"I2t":"0.05 A²·s; with starting current inrush","Depth":"60 mm; EB and TB","Width":"235 mm; EB and TB","title":"6ES7133-0BN11-0XB0","Height":"130 mm; EB and TB","RUN LED":"Yes","description":"*** SPARE PART*** SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 24DI 24V DC, 8DO 24V DC, 0.5A, 0.2MS INPUT DELAY, STANDARD","2-Wire Sensor":"Yes","For Signal \"0\"":"-30 to +5 V","For Signal \"1\"":"13 to 30V","Operation, max.":"95 %; RH class 2 in accordance with IEC 1131-2","Operation, min.":"15 %","SYNC capability":"Yes","Weight, approx.":"800 g; EB and TB","lifecycle_stage":"current","\"0\" To \"1\", Max.":"20 µs","\"1\" To \"0\", Max.":"0.5 ms","Power loss, max.":"5.5 W","Rated value (DC)":"24 V","Unshielded, Max.":"100 m","FREEZE capability":"Yes","Bus fault BF (red)":"Yes","On Lamp Load, Max.":"8 Hz","up to 60 °C, max.":"2 A","At \"0\" To \"1\", Max.":"0.2 ms","For Signal \"0\", Max.":"2 V; idling","For Signal \"1\", Min.":"UE -3 V","For Signal \"1\", Typ.":"4 mA","Usable terminal block":"TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC","Transmission rate, max.":"12 Mbit/s","Number of digital inputs":"24","Short-circuit protection":"Yes; Electronic","Current consumption, max.":"1 000 mA; from L5+; sensor","Current consumption, typ.":"85 mA; From L5+; logic","Number of digital outputs":"8","With Inductive Load, Max.":"0.5 Hz","With Resistive Load, Max.":"100 Hz","Controlling a digital input":"Yes","Horizontal Installation, Max.":"60 °C; 40°C for other mountings","Horizontal Installation, Min.":"0 °C","Permissible Range, Lower Limit":"795 hPa","Permissible Range, Upper Limit":"1 080 hPa","Between The Channels, In Groups Of":"8","Bus protocol/transmission protocol":"PROFIBUS DP","tested according to IEC 60068-2-27":"Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms","Potential separation digital inputs":"No","permissible range, lower limit (DC)":"18.5 V","permissible range, upper limit (DC)":"30.2 V","Potential separation digital outputs":"Yes","For Signal \"0\" Residual Current, Max.":"1 mA","For Signal \"1\" Permissible Range, Max.":"0.5 A; in one group","Status indicator digital input (green)":"Yes","Status indicator digital output (green)":"Yes","between electronic block and PROFIBUS DP":"Yes","Limitation of inductive shutdown voltage to":"typically (L1+) -55 V","Operation, tested according to IEC 60068-2-6":"Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)","Permissible Quiescent Current (2-Wire Sensor), Max.":"1.5 mA","Design of electrical connection for the inputs and outputs":"Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$857.94","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5444c2a6d45e12e1a825e1259ff12c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=217274&mlfb=6ES7133-0BN11-0XB0"},"ai":{"faq":[{"question":"What is the depth of the 6ES7133-0BN11-0XB0?","answer":"60 mm for both EB and TB versions. It fits standard ET 200S backplanes and enclosures."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7133-0BN11-0XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7133-0BN11-0XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}