{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7134-4JB01-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7134-4JB01-0AB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7134-4JB01-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7134-4JB01-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200S 2AI TC/Voltage analog input module, 15 mm width, 0.6 W, type B/E/J/K/L/N/R/S/T, 52 mm depth, current lifecycle.","salesMarkdown":"## Part identity & placement Siemens 6ES7134-4JB01-0AB0 is a 2-channel analog input module for the ET 200S family. It supports thermocouple types B, E, J, K, L, N, R, S, and T. Runs on 24 V DC from the power module, draws 0.6 W typical. Integration time is parameterizable at 16,7 or 20 ms, and digital filtering can be set in four stages (none, low, medium, high) to knock down line noise. The 1 MΩ input resistance (Type B) means negligible loading on thermocouple signals. Wire-break diagnostics work on thermocouples only — if you tie it to a voltage source, wire-break detection won't trip, so don't rely on it for RTD or mV-only loops. Shielded cable max length is 50 m; longer runs invite noise into the integrating ADC. The module isolates inputs to 500 V DC tested, which covers the ground-loop gap typical in multi-drop field wiring. Group diagnostics and overflow/underflow flags are individually enable/disable. The group error SF LED (red) on the front stays lit for any enabled fault, so you can wire it to the CPU's digital input for a single alarm point. Between-the-channels isolation is absent — keep the common-mode voltage within the module's range on each channel pair. ## Lifecycle & sourcing posture If you're filling a BOM line, quote this exact 6ES7134-4JB01-0AB0 against your order. No known direct replacement needed; it's the variant that covers the broadest TC list for a 2-channel ET 200S slice. Sourcing is straightforward — standard lead times apply, and we can quote to your schedule.","metaTitle":"Siemens 6ES7134-4JB01-0AB0 Analog Input Module, 2AI TC/Volta","metaDescription":"Siemens ET 200S 2-channel analog input module. Supports thermocouple types K,J,E,N,R,S,B,T,L. 15mm width, 0.6W. Still in current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Analog Input Modules"],"specifications":{"Depth":"52 mm","Width":"15 mm","Height":"81 mm","Remark":"4 byte","Type B":"Yes","Type E":"Yes","Type J":"Yes","Type K":"Yes","Type L":"Yes","Type N":"Yes","Type R":"Yes","Type S":"Yes","Type T":"Yes","Step: low":"Yes; 4x cycle time","Step: High":"Yes; 64x cycle time","Step: None":"Yes; 1x cycle time","Wire-break":"Yes; A break in the wire is only detected for thermocouples","Group error":"Yes","Step: Medium":"Yes; 32x cycle time","Shielded, Max.":"50 m","Parameterizable":"Yes; In four stages by means of digital filtering","Weight, approx.":"40 g","lifecycle_stage":"current","-80 mV to +80 mV":"Yes","Comparison point":"none / RTD","Isochronous mode":"No","Power loss, typ.":"0.6 W","Rated value (DC)":"24 V; From power module","Group diagnostics":"Disable / enable","Overflow/underflow":"Disable / enable","Between The Channels":"No","Group error SF (red)":"Yes","Integration time (ms)":"16,7 / 20 ms","Isolation tested with":"500 V DC","Measurement principle":"integrating","Diagnostics wire break":"Disable / enable (wire break is detected only in thermocouples)","Comparison point number":"None / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8","For Voltage Measurement":"Yes","Number of analog inputs":"2","Input resistance (Type B)":"1 MΩ","Input resistance (Type E)":"1 MΩ","Input resistance (Type K)":"1 MΩ","Input resistance (Type L)":"1 MΩ","Input resistance (Type N)":"1 MΩ","Input resistance (Type R)":"1 MΩ","Input resistance (Type S)":"1 MΩ","Input resistance (Type T)":"1 MΩ","Input resistance (type J)":"1 MΩ","Reverse polarity protection":"Yes","Conversion time (per channel)":"65 s; 55 / 65 ms (additional 20 ms on activated wire-break test)","Address space per module, max.":"4 byte","Cycle time (all channels) max.":"Number of active channels per module x basic conversion time","Diagnostic information readable":"Yes","Integration time, parameterizable":"Yes","Internal Temperature Compensation":"Not possible","from backplane bus 3.3 V DC, max.":"10 mA","Input resistance (-80 mV to +80 mV)":"1 MΩ","Between The Channels And Backplane Bus":"Yes","Voltage, relative to input range, (+/-)":"0.4 %","Between the channels and load voltage L+":"Yes","from load voltage L+ (without load), max.":"30 mA","Resolution with overrange (bit including sign), max.":"16 bit; 15 bit + sign","Technical unit for temperature measurement adjustable":"No; Celsius","External Temperature Compensation With Compensations Socket":"Yes; possible, one external compensating box per channel","Interference voltage suppression for interference frequency f1 in Hz":"50 / 60 Hz","Permissible Input Voltage For Voltage Input (Destruction Limit), Max.":"10 V; Permanent"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$261.62 – $367.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5444c2a6d45e12e1a825e1259ff12c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=115452&mlfb=6ES7134-4JB01-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7134-4JB01-0AB0/alternatives.json"},"ai":{"faq":[{"question":"Does it support wire-break diagnostics on voltage inputs?","answer":"No. Wire-break detection is only functional for thermocouples, as stated in the module's diagnostic features."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7134-4JB01-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7134-4JB01-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}