{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7134-4JB01-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7134-4JB01-0AB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7134-4JB01-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7134-4JB01-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200S 2AI TC/Voltage analog input module, 15 mm width, 0.6 W, type B/E/J/K/L/N/R/S/T, 52 mm depth, current lifecycle.","salesMarkdown":"## Part identity & placement Siemens 6ES7134-4JB01-0AB0 is a 2-channel analog input module for the ET 200S family. It supports thermocouple types B, E, J, K, L, N, R, S, and T. Runs on 24 V DC from the power module, draws 0.6 W typical. Integration time is parameterizable at 16,7 or 20 ms, and digital filtering can be set in four stages (none, low, medium, high) to knock down line noise. The 1 MΩ input resistance (Type B) means negligible loading on thermocouple signals. Wire-break diagnostics work on thermocouples only — if you tie it to a voltage source, wire-break detection won't trip, so don't rely on it for RTD or mV-only loops. Shielded cable max length is 50 m; longer runs invite noise into the integrating ADC. The module isolates inputs to 500 V DC tested, which covers the ground-loop gap typical in multi-drop field wiring. Group diagnostics and overflow/underflow flags are individually enable/disable. The group error SF LED (red) on the front stays lit for any enabled fault, so you can wire it to the CPU's digital input for a single alarm point. Between-the-channels isolation is absent — keep the common-mode voltage within the module's range on each channel pair. ## Lifecycle & sourcing posture If you're filling a BOM line, quote this exact 6ES7134-4JB01-0AB0 against your order. No known direct replacement needed; it's the variant that covers the broadest TC list for a 2-channel ET 200S slice. Sourcing is straightforward — standard lead times apply, and we can quote to your schedule.","metaTitle":"Siemens 6ES7134-4JB01-0AB0 Analog Input Module, 2AI TC/Volta","metaDescription":"Siemens ET 200S 2-channel analog input module. Supports thermocouple types K,J,E,N,R,S,B,T,L. 15mm width, 0.6W. Still in current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"52 mm","Width":"15 mm","Height":"81 mm","Product Status":"Active","Measurement Principle":"Integrating","Conversion Time Per Channel":"65 s; 55 / 65 ms (additional 20 ms on activated wire-break test)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$261.62 – $367.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5444c2a6d45e12e1a825e1259ff12c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=115452&mlfb=6ES7134-4JB01-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7134-4JB01-0AB0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7134-4JB01-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7134-4JB01-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}