{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7134-4LB02-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7134-4LB02-0AB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7134-4LB02-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7134-4LB02-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200S, analog input module, 2 AI, voltage, 0.85 W, 52 mm depth, 15 mm width, 81 mm height.","salesMarkdown":"## Integrator overview The 6ES7134-4LB02-0AB0: Input ranges cover 1–5 V, ±5 V, and ±10 V. Wire-break detection enabled only on the 1–5 V range. Group diagnostics and overflow/underflow reporting can be disabled per channel. Isochronous mode supported for deterministic read cycles. Conversion time is 0.04 ms per channel without noise suppression; with suppression expect 17–21 ms per channel. Reverse polarity protection on the 24 V DC supply. Power loss 0.85 W typical — keep rail power budget in mind for dense arrays. Channel-to-channel isolation is not provided, but permissible potential difference between inputs is increased. Isolation tested at 500 V DC between channels and backplane / load voltage L+. ## Diagnostics & configuration Address space 4 bytes per module. Input resistance 800 kΩ for all voltage ranges. Parameterizable integration time and active interference frequency suppression to reduce noise. Group error SF LED (red) and hardware interrupt output. Shielded cable maximum 200 m.","metaTitle":"Siemens 6ES7134-4LB02-0AB0 ET 200S Analog Input Module, 2 AI","metaDescription":"Siemens ET 200S analog input module 6ES7134-4LB02-0AB0 with 2 voltage inputs, 0.85 W, 500 V DC isolation. Current production. Source via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Analog Input Modules"],"specifications":{"Depth":"52 mm","Width":"15 mm","Height":"81 mm","Remark":"12 bytes, 4 bytes in compatibility mode","Step: low":"Yes; 4x","1 V to 5 V":"Yes","Step: High":"Yes; 32x","Step: None":"Yes; 1x","Wire-break":"Yes; Measuring range 1 to 5 V only","Group error":"Yes","-5 V to +5 V":"Yes","Step: Medium":"Yes; 16x","-10 V to +10 V":"Yes","Shielded, Max.":"200 m","Parameterizable":"Yes; In 4 stages: 1x, 4x, 16x, 32x cycle time","Weight, approx.":"45 g","lifecycle_stage":"current","Isochronous mode":"Yes","Power loss, typ.":"0.85 W","Rated value (DC)":"24 V","Group diagnostics":"Disable / enable","Hardware interrupt":"Yes","Overflow/underflow":"Disable / enable","Between The Channels":"No; however, increased permissible potential difference between the inputs.","Group error SF (red)":"Yes","Isolation tested with":"500 V DC","For Voltage Measurement":"Yes","Number of analog inputs":"2","Reverse polarity protection":"Yes","Conversion time (per channel)":"0.04 ms; Without noise suppression 17/20 ms per channel with error","Input resistance (1 V to 5 V)":"800 kΩ","Address space per module, max.":"4 byte","Cycle time (all channels) max.":"0.5 ms; 0.5 ms for 2 channels without noise suppression, 18 / 21 ms per channel with noise suppression","Input resistance (-5 V to +5 V)":"800 kΩ","Input resistance (-10 V to +10 V)":"800 kΩ","Integration time, parameterizable":"Yes","from backplane bus 3.3 V DC, max.":"10 mA","Between The Channels And Backplane Bus":"Yes","Voltage, relative to input range, (+/-)":"0.05 %; 0.1% without interference frequency suppression","Between the channels and load voltage L+":"Yes","from load voltage L+ (without load), max.":"55 mA","Product Function / Supply Voltage For Transmitters":"No","Resolution with overrange (bit including sign), max.":"16 bit; 0 to 5 V: 15 bit, ±10 V: 16 bit, ±5 V: 16 bit","Interference voltage suppression for interference frequency f1 in Hz":"60 / 50 Hz / no","Permissible Input Voltage For Voltage Input (Destruction Limit), Max.":"35 V; 35 V continuous; 75 V for max. 1 ms"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$75.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5444c2a6d45e12e1a825e1259ff12c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=264424&mlfb=6ES7134-4LB02-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7134-4LB02-0AB0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7134-4LB02-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7134-4LB02-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}