{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7134-6JD00-0CA1","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7134-6JD00-0CA1","canonicalUrl":"https://aoctrl.com/siemens/6ES7134-6JD00-0CA1","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7134-6JD00-0CA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200SP analog input module, 6ES7134-6JD00-0CA1, PTC 15-bit, RTD/thermocouple/mV, 15 mm width, 58 mm depth.","salesMarkdown":"## ET 200SP slice with PTC and RTD coverage The 6ES7134-6JD00-0CA1 is a 15 mm-wide analog input module for the Siemens ET 200SP distributed I/O system. It reads PTC thermistors at 15-bit resolution and handles the full range of RTDs (Pt100, Pt1000, Ni100, Ni1000) and thermocouples (types B, C, E, J, K, L, N, R, S, T, U) at 16-bit resolution including sign. The module also accepts low-level mV signals (-50 mV to +50 mV, -80 mV to +80 mV, -1 V to +1 V) and resistance ranges up to 6000 ohms, making it a single-slot solution for temperature, strain-gauge, and resistive-sensor inputs. ## Sensor types and wiring reach Maximum cable length is 200 m for shielded RTD/resistance inputs, derated to 50 m for thermocouple inputs — the mV-level signal is more susceptible to noise over longer runs. Channel-by-channel wire-break detection and a group error signal are built in, so a failed sensor flags the specific channel without pulling down the entire module. I&M data (I&M0 to I&M3) is supported for asset tracking in TIA Portal.","metaTitle":"Siemens 6ES7134-6JD00-0CA1 Analog Input Module, PTC 15-bit","metaDescription":"Siemens 6ES7134-6JD00-0CA1 analog input module for ET 200SP. Supports PTC (15-bit), RTDs, thermocouples, mV signals. Active production, sourced per RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Analog Input Modules"],"specifications":{"PTC":"Yes; 15 bit","Cu 10":"Yes; 16 bit incl. sign","Depth":"58 mm","Width":"15 mm","title":"6ES7134-6JD00-0CA1","Height":"73 mm","Ni 100":"Yes; 16 bit incl. sign","Ni 120":"Yes; 16 bit incl. sign","Ni 200":"Yes; 16 bit incl. sign","Ni 500":"Yes; 16 bit incl. sign","Pt 100":"Yes; 16 bit incl. sign","Pt 200":"Yes; 16 bit incl. sign","Pt 500":"Yes; 16 bit incl. sign","Type B":"Yes; 16 bit incl. sign","Type C":"Yes; 16 bit incl. sign","Type E":"Yes; 16 bit incl. sign","Type J":"Yes; 16 bit incl. sign","Type K":"Yes; 16 bit incl. sign","Type L":"Yes; 16 bit incl. sign","Type N":"Yes; 16 bit incl. sign","Type R":"Yes; 16 bit incl. sign","Type S":"Yes; 16 bit incl. sign","Type T":"Yes; 16 bit incl. sign","Type U":"Yes; 16 bit incl. sign","Ni 1000":"Yes; 16 bit incl. sign","Pt 1000":"Yes; 16 bit incl. sign","I&M data":"Yes; I&M0 to I&M3","LG-Ni 1000":"Yes; 16 bit incl. sign","Wire-break":"Yes; channel by channel","Group error":"Yes","description":"SIMATIC ET 200SP, Analog input module, AI 4xRTD/TC High Feature, suitable for BU type A0, A1, Color code CC00, channel diagnostics, 16 bit, +/-0.1%, 2-/3-/4-wire","-1 V to +1 V":"Yes; 16 bit incl. sign","0 To 150 Ohms":"Yes; 15 bit","0 To 300 Ohms":"Yes; 15 bit","0 To 600 Ohms":"Yes; 15 bit","0 To 3000 Ohms":"Yes; 15 bit","0 To 6000 Ohms":"Yes; 15 bit","Shielded, Max.":"200 m; 50 m with thermocouples","Parameterizable":"Yes","lifecycle_stage":"current","-50 mV to +50 mV":"Yes; 16 bit incl. sign","-80 mV to +80 mV":"Yes; 16 bit incl. sign","Firmware version":"V2.1","Isochronous mode":"No","Power loss, typ.":"0.75 W","Rated value (DC)":"24 V","usable BaseUnits":"BU type A0, A1","Limit value alarm":"Yes; two upper and two lower limit values in each case","-250 mV to +250 mV":"Yes; 16 bit incl. sign","FW update possible":"Yes","Overflow/underflow":"Yes; channel by channel","Measurement principle":"integrating (Sigma-Delta)","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red DIAG LED","Input resistance (PTC)":"1 MΩ","For Channel Diagnostics":"Yes; red LED","For Voltage Measurement":"Yes","Number of analog inputs":"4","Type TXK/TXK(L) to GOST":"Yes; 16 bit incl. sign","Input resistance (Cu 10)":"1 MΩ","Common mode voltage, max.":"10 V","Input resistance (Ni 100)":"1 MΩ","Input resistance (Ni 120)":"1 MΩ","Input resistance (Ni 200)":"1 MΩ","Input resistance (Ni 500)":"1 MΩ","Input resistance (Pt 100)":"1 MΩ","Input resistance (Pt 200)":"1 MΩ","Input resistance (Pt 500)":"1 MΩ","Input resistance (Type B)":"1 MΩ","Input resistance (Type C)":"1 MΩ","Input resistance (Type E)":"1 MΩ","Input resistance (Type K)":"1 MΩ","Input resistance (Type L)":"1 MΩ","Input resistance (Type N)":"1 MΩ","Input resistance (Type R)":"1 MΩ","Input resistance (Type S)":"1 MΩ","Input resistance (Type T)":"1 MΩ","Input resistance (Type U)":"1 MΩ","Input resistance (type J)":"1 MΩ","Internal Comparison Point":"Yes; with BaseUnit type A1","Input resistance (Ni 1000)":"1 MΩ","Input resistance (Pt 1000)":"1 MΩ","Number of smoothing levels":"4; None; 4/8/16 times","Calibration possible in RUN":"Yes","Reverse polarity protection":"Yes","Vertical Installation, Max.":"50 °C","Vertical Installation, Min.":"-30 °C; < 0 °C as of FS08","Adjustment of measuring range":"Yes","Conversion time (per channel)":"180 / 60 / 50 / (67.5 / 22.5 / 18.75) ms","Horizontal Installation, Max.":"60 °C","Horizontal Installation, Min.":"-30 °C; < 0 °C as of FS08","Input resistance (LG-Ni 1000)":"1 MΩ","Monitoring the supply voltage":"Yes","Address space per module, max.":"8 byte; + 1 byte for QI information","Common mode interference, min.":"90 dB","Cycle time (all channels), min.":"Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels); for line compensation in case of a three-wire connection, an additional cycle is necessary","Input resistance (-1 V to +1 V)":"1 MΩ","Reference channel of the module":"Yes","Input resistance (0 to 150 ohms)":"1 MΩ","Input resistance (0 to 300 ohms)":"1 MΩ","Input resistance (0 to 600 ohms)":"1 MΩ","Input resistance (0 to 3000 ohms)":"1 MΩ","Input resistance (0 to 6000 ohms)":"1 MΩ","Integration time, parameterizable":"Yes","Type of mechanical coding element":"Type A","Crosstalk between the inputs, min.":"-50 dB","Number of reference channel groups":"4; Group 0 to 3","Reparameterization possible in RUN":"Yes","Input resistance (-50 mV to +50 mV)":"1 MΩ","Input resistance (-80 mV to +80 mV)":"1 MΩ","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","Input resistance (-250 mV to +250 mV)":"1 MΩ","Additional Power Line Wire-Break Check":"2 ms; for 3/4 wire transducer (resistance thermometer and resistor)","PROFIBUS from GSD version/GSD revision":"GSD Revision 5","PROFINET from GSD version/GSD revision":"GSDML V2.3","Voltage, relative to input range, (+/-)":"0.05 %","Input resistance (Type TXK/TXK(L) to GOST)":"1 MΩ","Monitoring of the supply voltage (PWR-LED)":"Yes; green PWR LED","PCS 7 configurable/integrated from version":"V8.1 SP1","Resistance, relative to input range, (+/-)":"0.05 %","STEP 7 configurable/integrated from version":"V5.5 SP3 / V5.5 SP4","Additional Processing Time For Wire-Break Check":"2 ms; In the ranges resistance thermometers, resistors and thermocouples","Linearity error (relative to input range), (+/-)":"0.01 %; ±0.1 % for resistance thermometers and resistance","Temperature error (relative to input range), (+/-)":"0.0009 %/K; ±0.005 % / K at thermocouple","For Resistance Measurement With Two-Wire Connection":"Yes","For Resistance Measurement With Four-Wire Connection":"Yes","Resolution with overrange (bit including sign), max.":"16 bit","For Resistance Measurement With Three-Wire Connection":"Yes","Technical unit for temperature measurement adjustable":"Yes; °C/°F/K","STEP 7 TIA Portal configurable/integrated from version":"V12 SP1 / V13","Color code for module-specific color identification plate":"CC00","Constant measurement current for resistance-type transmitter, typ.":"2 mA","Interference voltage suppression for interference frequency f1 in Hz":"16.6 / 50 / 60 Hz","Permissible Input Voltage For Voltage Input (Destruction Limit), Max.":"30 V","Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)":"0.05 %","Series mode interference (peak value of interference < rated value of input range), min.":"70 dB; With conversion time 67.5 / 22.5 / 18.75 ms: 40 dB"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$171.45","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2871d28a5ff860422aa78fec2c1f91db.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=515082&mlfb=6ES7134-6JD00-0CA1"},"ai":{"faq":[{"question":"Is 6ES7134-6JD00-0CA1 compatible with my Siemens ET 200SP system?","answer":"Yes, the 6ES7134-6JD00-0CA1 is a standard ET 200SP I/O module (15 mm width, 58 mm depth, 73 mm height) that snaps onto the DIN rail and connects via the backplane bus. It fits any ET 200SP interface module or bus adapter."},{"question":"What sensors does 6ES7134-6JD00-0CA1 support?","answer":"It supports PTC thermistors (15-bit), RTDs (Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, LG-Ni1000) at 16-bit including sign, thermocouples (types B, C, E, J, K, L, N, R, S, T, U) at 16-bit including sign, and low-level mV and resistance ranges."},{"question":"Where can I buy 6ES7134-6JD00-0CA1?","answer":"Send your quantity and target delivery window for a current price and lead-time quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7134-6JD00-0CA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7134-6JD00-0CA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}