{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7134-7SD00-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7134-7SD00-0AB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7134-7SD00-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7134-7SD00-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC ET 200SP, 6ES7134-7SD00-0AB0, 4 analog inputs for thermocouples, depth 136.5 mm, width 30 mm, height 129 mm.","salesMarkdown":"The Siemens 6ES7134-7SD00-0AB0 is a 4-channel analog input module for thermocouples in the SIMATIC ET 200SP I/O system. It accepts types B, C, E, J, K, L, N, R, S, T, and U, each with a 1 MΩ input resistance. Measurement is integrating (Sigma-Delta), with parametric step filtering from 1x to 64x cycle time to tune noise rejection against process speed. Shielded cable runs up to 50 m. Diagnostic and limit value alarms are parameterizable. Power draw is 0.4 W typical, 17 mA from the backplane bus.","metaTitle":"Siemens 6ES7134-7SD00-0AB0 SIMATIC ET 200SP, 4 AI TC Module","metaDescription":"4-input thermocouple module for ET 200SP. Supports types B, C, E, J, K, L, N, R, S, T, U. Depth 136.5 mm, width 30 mm. Current production. Available to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLC I/O & Expansion Modules"],"specifications":{"Depth":"136.5 mm","Width":"30 mm","Height":"129 mm","Type B":"Yes","Type C":"Yes","Type E":"Yes","Type J":"Yes","Type K":"Yes","Type L":"Yes","Type N":"Yes","Type R":"Yes","Type S":"Yes","Type T":"Yes","Type U":"Yes","CE mark":"Yes","Step: low":"Yes; 4x cycle time","Step: High":"Yes; 64x cycle time","Step: None":"Yes; 1x cycle time","Step: Medium":"Yes; 32x cycle time","Shielded, Max.":"50 m","Parameterizable":"Yes; in 4 stages","Weight, approx.":"230 g","lifecycle_stage":"current","-80 mV to +80 mV":"Yes","Diagnostic alarm":"Yes; Parameterizable","Power loss, typ.":"0.4 W","For Thermocouples":"Yes","Limit value alarm":"Yes; Parameterizable","Between The Channels":"Yes; Functional","Group error SF (red)":"Yes","Measurement principle":"integrating (Sigma-Delta)","SIL acc. to IEC 61508":"No","Number of analog inputs":"4","Current consumption, typ.":"17 mA","Input resistance (Type B)":"1 000 kΩ","Input resistance (Type C)":"1 000 kΩ","Input resistance (Type E)":"1 000 kΩ","Input resistance (Type K)":"1 000 kΩ","Input resistance (Type L)":"1 000 kΩ","Input resistance (Type N)":"1 000 kΩ","Input resistance (Type R)":"1 000 kΩ","Input resistance (Type S)":"1 000 kΩ","Input resistance (Type T)":"1 000 kΩ","Input resistance (Type U)":"1 000 kΩ","Input resistance (type J)":"1 000 kΩ","from supply voltage L+, max.":"30 mA","Common mode interference, min.":"90 dB","Cycle time (all channels) max.":"320 ms; 66 ms basic conversion time x 4 channels with interference frequency suppression 60 Hz, 80 ms basic conversion time x 4 channels with interference frequency suppression 50 Hz","Diagnostic information readable":"Yes","Integration time, parameterizable":"Yes","Internal Temperature Compensation":"Yes; via supplied TC sensor module","Crosstalk between the inputs, min.":"-50 dB","Input resistance (-80 mV to +80 mV)":"1 000 kΩ","Between The Channels And Backplane Bus":"Yes","Voltage, relative to input range, (+/-)":"0.1 %","Linearity error (relative to input range), (+/-)":"0.015 %","Temperature error (relative to input range), (+/-)":"0.02 %/K","Additional Conversion Time For Wire-Break Monitoring":"5 ms","Resolution with overrange (bit including sign), max.":"16 bit","Technical unit for temperature measurement adjustable":"Yes","Basic conversion time, including integration time (ms)":"80 ms at 50 Hz; 66 ms at 60 Hz","External Temperature Compensation With Compensations Socket":"Yes; via temperature value, acquired by an analog module of the same ET 200iSP station","Interference voltage suppression for interference frequency f1 in Hz":"50 / 60 Hz","Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)":"0.01 %","Series mode interference (peak value of interference < rated value of input range), min.":"70 dB"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$464.82 – $947.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5444c2a6d45e12e1a825e1259ff12c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=128246&mlfb=6ES7134-7SD00-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7134-7SD00-0AB0/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions of this module?","answer":"Width 30 mm, depth 136.5 mm, height 129 mm. It fits standard ET 200SP base units."},{"question":"What compliance documentation is available for 6ES7134-7SD00-0AB0?","answer":"The module carries a CE mark. Other certifications (e.g., RoHS, UL) are not detailed in the standard listing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7134-7SD00-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7134-7SD00-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}