{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7134-7SD51-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7134-7SD51-0AB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7134-7SD51-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7134-7SD51-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC ET 200S analog input module, 4-channel RTD / resistance, order code 6ES7134-7SD51-0AB0, for Pt 100, Ni 100 and 0–600 Ω / 1000 Ω inputs with integrating Sigma-Delta conversion.","salesMarkdown":"## What the conversion stages actually buy you The 6ES7134-7SD51-0AB0: Cycle time across all four channels reaches 320 ms at the longest integration setting, built from a 66 ms basic conversion time per channel under 60 Hz interference-frequency suppression or 80 ms under 50 Hz suppression, multiplied across the four channels. Common-mode rejection sits at 90 dB minimum, crosstalk between inputs is held to −50 dB, and linearity error runs ±0.015 % of the input range — numbers that make the module a reasonable fit for four-wire RTD piping across a process skid rather than a high-speed lab role. ## Diagnostics and fault surfacing The module reports wire-break and short-circuit on the sensor side, raises a group error on the red SF LED, and pushes a diagnostic alarm plus a separate limit-value alarm to the host. Diagnostic information is readable by the CPU, so a field wire-break surfaces as an identifiable event rather than an open reading. ## Isolation map and field wiring Galvanic isolation is provided between the channels and the backplane bus, and between the channels and load voltage L+, but not between the channels themselves — so shield grounding strategy and any per-channel grounding have to be planned as a common return. Shielded cable runs are rated up to 500 m, which covers most distributed skid layouts without an intermediate repeater. ## Footprint, power, and backplane budget On the DIN rail the module occupies a 30 mm slice, stands 129 mm tall, and runs 136.5 mm deep at roughly 230 g — the standard ET 200S terminal-module pitch. From the backplane it draws 19 mA typical and up to 22 mA from L+, with a typical power loss of 0.4 W, leaving room in a standard ET 200S power budget for adjacent digital slices on the same station. ## Sourcing posture","metaTitle":"Siemens 6ES7134-7SD51-0AB0 AI 4×RTD, ET 200S","metaDescription":"Siemens 6ES7134-7SD51-0AB0 ET 200S analog input, 4 channels for Pt 100 / Ni 100 / resistance, integrating conversion, diagnostics. Specified into the BOM against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"136.5 mm","Width":"30 mm","Height":"129 mm","Product Status":"Active","Measurement Principle":"integrating (Sigma-Delta)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$426.91 – $853.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5444c2a6d45e12e1a825e1259ff12c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=432798&mlfb=6ES7134-7SD51-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7134-7SD51-0AB0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7134-7SD51-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7134-7SD51-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}