{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7134-7TD00-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7134-7TD00-0AB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7134-7TD00-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7134-7TD00-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200S analog input module, 4 channels, 4-20 mA, integrating Sigma-Delta, ATEX Ex ib[ia] IIC T4, ET 200S terminal-block form factor, order code 6ES7134-7TD00-0AB0.","salesMarkdown":"## Integration time and noise rejection The 6ES7134-7TD00-0AB0: Integration is selectable in four parameterizable stages tied to line-frequency rejection. The fastest, \"None\", runs at 1× cycle time; \"low\" doubles to 4×; \"medium\" stretches to 32×; and \"High\" reaches 64×. With all four channels active the worst-case cycle time is 120 ms, derived from 30 ms basic conversion per channel plus a four-channel scan at either 50 Hz or 60 Hz interference-frequency suppression. Crosstalk between inputs is specified at -50 dB minimum, and there is no electrical isolation between channels — only between the channel group and the backplane bus. Integration time is not freely adjustable — only the four preset stages are available, which is what ties the speed-versus-rejection decision to a fixed menu. Wire-break detection and short-circuit monitoring are both supported, and the diagnostic alarm plus limit-value alarm are parameterizable per channel. Diagnostic information is readable from the host, with the group error (SF, red LED) flagging module-level faults. ## Lifecycle and procurement posture No official replacement order code is published; any migration would be a redesign onto a newer ET 200S analog input family. For new BOM lines or spares, request a quote against an RFQ to confirm factory-channel availability and lead time. ## Quality and compliance documentation CE marking is declared and the ATEX marking covers gas group IIC, dust, and mining group I. Buyers should expect the EU Declaration of Conformity, the ATEX Type Examination Certificate, and the SIMATIC technical documentation pack. Panel builders specifying into hazardous-area installs should pin the ATEX certificate reference into the panel cert bundle.","metaTitle":"Siemens 6ES7134-7TD00-0AB0 ET 200S AI 4x 4-20 mA","metaDescription":"Siemens ET 200S analog input SM 6ES7134-7TD00-0AB0, 4 channels, 4-20 mA, integrating Sigma-Delta, ATEX II2 G (1) GD Ex ib[ia] IIC T4. Specs and sourcing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLC I/O & Expansion Modules"],"specifications":{"Depth":"136.5 mm","Width":"30 mm","title":"6ES7134-7TD00-0AB0","Height":"129 mm","CE mark":"Yes","Step: low":"Yes; 4x cycle time","Step: High":"Yes; 64x cycle time","Step: None":"Yes; 1x cycle time","Wire-break":"Yes","description":"SIMATIC DP, electronic module for ET200iSP, 4 AI HART, 2DMU, for connecting HART 2-wire transmitters, supported HART protocol Version 6.0, Ex ib (ia Ga) IIC T4 Gb, Ex ib [ia IIIC Da] IIC T4 Gb, Ex ib [ia] I Mb","ATEX marking":"II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I","Step: Medium":"Yes; 32x cycle time","4 mA to 20 mA":"Yes","Short-circuit":"Yes","Shielded, Max.":"500 m","Parameterizable":"Yes; in 4 stages","Weight, approx.":"230 g","lifecycle_stage":"current","Diagnostic alarm":"Yes; Parameterizable","Power loss, typ.":"2.7 W","Limit value alarm":"Yes; Parameterizable","Short-Circuit Proof":"Yes","Between The Channels":"No","Group error SF (red)":"Yes","Supply current, max.":"23 mA; per channel","Measurement principle":"integrating (Sigma-Delta)","SIL acc. to IEC 61508":"No","Number of analog inputs":"4","Current consumption, typ.":"280 mA","from supply voltage L+, max.":"320 mA","Cycle time (all channels) max.":"120 ms; 30 ms basic conversion time x4 channels with 60 Hz, 50 Hz interference frequency suppression","Diagnostic information readable":"Yes","Integration time, parameterizable":"No","Burden of 2-wire transmitter, max.":"750 Ω","Crosstalk between the inputs, min.":"-50 dB","Between The Channels And Backplane Bus":"Yes","Current, relative to input range, (+/-)":"0.1 %","For Current Measurement As 2-Wire Transducer":"Yes","Linearity error (relative to input range), (+/-)":"0.015 %","Temperature error (relative to input range), (+/-)":"0.005 %/K","Resolution with overrange (bit including sign), max.":"13 bit","Technical unit for temperature measurement adjustable":"Yes","Interference voltage suppression for interference frequency f1 in Hz":"50 / 60 Hz","Permissible Input Current For Current Input (Destruction Limit), Max.":"90 mA","Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)":"0.01 %","Series mode interference (peak value of interference < rated value of input range), min.":"70 dB"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$438.15 – $816.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5444c2a6d45e12e1a825e1259ff12c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=266139&mlfb=6ES7134-7TD00-0AB0"},"ai":{"faq":[{"question":"What is the cycle time at full channel load?","answer":"With all four channels active, worst-case cycle time is 120 ms — 30 ms basic conversion time per channel scanned across four inputs at 50 Hz or 60 Hz line-frequency suppression. Integration stages are 1×, 4×, 32×, and 64× via the parameterizable noise rejection."},{"question":"What footprint does this module occupy in the panel?","answer":"It mounts on a single ET 200S slot at 30 mm wide by 129 mm tall by 136.5 mm deep, weighing approximately 230 g. Shielded cable runs are supported up to 500 m maximum between transmitter and module."},{"question":"Does 6ES7134-7TD00-0AB0 provide channel-to-channel isolation?","answer":"No — there is no isolation between input channels. Isolation is provided only between the channel group and the backplane bus."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7134-7TD00-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7134-7TD00-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}