{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7135-6HB00-0DA1","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7135-6HB00-0DA1","canonicalUrl":"https://aoctrl.com/siemens/6ES7135-6HB00-0DA1","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7135-6HB00-0DA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200SP analog output module, 2 channels, 4-wire, 16-bit, ±10 V / ±20 mA, oversampling, isochronous mode, BU type A0/A1.","salesMarkdown":"## What this module is and why it matters for your BOM 6ES7135-6HB00-0DA1: isochronous mode, diagnostic alarms, channel-by-channel diagnostics (wire-break current, short-circuit voltage). Each output sources up to 30 V, max 90 mA from 24 V DC backplane; typ power loss 0.9 W. Important constraint: there is no channel-to-channel isolation. All outputs share a common reference. If your application requires galvanic separation between channels, this module won't provide it. The isolation tested value is 707 V DC only between the module and the backplane. The closest same-function sibling is the 6ES7136-6AB00-0CA1. That module has 4 analog output channels and includes HART protocol support. The 6ES7135-6HB00-0DA1 has only 2 channels and no HART. If your application needs HART or four outputs, the 6ES7136-6AB00-0CA1 is the correct choice. If you need oversampling and high-speed updates (< 50 µs per channel), the 6ES7135-6HB00-0DA1 wins — the 6ES7136 does not support oversampling. Physically, both mount on the same base units (BU type A0 or A1), so the mechanical fit is identical. The wiring scheme differs because the 6ES7135 is 2-channel 4-wire while the 6ES7136 is 4-channel 2-wire. A panel wired for the 6ES7136 would need re-termination to use the 6ES7135, and vice versa. ## Production status and sourcing For a BOM freeze, confirm the base unit number (BU type A0 or A1) and that the firmware version is at least FS06 to access all hardware functions. The module supports I&M data (I&M0 to I&M3) for asset management. For voltage outputs, maximum shielded cable length is 200 m; for current outputs, up to 1 000 m. For capacitive loads (max 47 nF over 20 m), output settling time is 0.05 ms. Channel status and diagnostics via green/red LEDs: green per channel, green/red DIAG, red per channel.","metaTitle":"Siemens 6ES7135-6HB00-0DA1 ET 200SP AO 2x4-wire, 16 bit","metaDescription":"Siemens 6ES7135-6HB00-0DA1 analog output module for ET 200SP, 2 channels 4-wire, ±10 V / ±20 mA 16-bit, oversampling, isochronous mode. Active production. Quote against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Analog Output Modules"],"specifications":{"MSO":"No","Depth":"58 mm","Width":"15 mm","title":"6ES7135-6HB00-0DA1","Height":"73 mm","I&M data":"Yes; I&M0 to I&M3","0 to 10 V":"Yes; 15 bit","0 to 20 mA":"Yes; 15 bit","1 V to 5 V":"Yes; 13 bit","Wire-break":"Yes; channel-by-channel, only for output type \"current\"","Group error":"Yes","description":"SIMATIC ET 200SP, Analog output module, AQ 2x U/I High Speed, suitable for BU type A0, A1, Color code CC00, channel diagnostics, 16 bit, +/-0.2%","-5 V to +5 V":"Yes; 15 bit incl. sign","Oversampling":"Yes; 2 channels per module","4 mA to 20 mA":"Yes; 14 bit","Short-circuit":"Yes; channel-by-channel, only for output type \"voltage\"","-10 V to +10 V":"Yes; 16 bit incl. sign","Shielded, Max.":"1 000 m; 200 m for voltage output","Weight, approx.":"31 g","lifecycle_stage":"current","-20 mA to +20 mA":"Yes; 16 bit incl. sign","Diagnostic alarm":"Yes","Isochronous mode":"Yes","Power loss, typ.":"0.9 W","Rated value (DC)":"24 V","Resolution, min.":"45 µs; (2 channels), 35 µs (1 channel)","usable BaseUnits":"BU type A0, A1","For Inductive Load":"0.05 ms","For Resistive Load":"0.05 ms","Overflow/underflow":"Yes","For Capacitive Load":"0.05 ms; Max. 47 nF and 20 m cable length","Between The Channels":"No","Diagnostics function":"Yes","HW functional status":"From FS06","Isolation tested with":"707 V DC (type test)","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red DIAG LED","Values per cycle, max.":"16","For Channel Diagnostics":"Yes; red LED","Voltages at the outputs":"30 V","Number of analog outputs":"2","Current consumption, max.":"90 mA; 2 channels current output 20 mA","Mechanical coding element":"Yes","Bus cycle time (TDP), min.":"125 µs","With Current Outputs, Max.":"500 Ω","With Voltage Outputs, Min.":"2 kΩ","Calibration possible in RUN":"No","Reverse polarity protection":"Yes","Vertical Installation, Max.":"50 °C","Vertical Installation, Min.":"-30 °C; < 0 °C as of FS06","Horizontal Installation, Max.":"60 °C","Horizontal Installation, Min.":"-30 °C; < 0 °C as of FS06","Monitoring the supply voltage":"Yes","Substitute values connectable":"Yes","Address space per module, max.":"4 byte; + 1 byte for QI information (32 bytes in the oversampling operating mode)","Analog output with oversampling":"Yes","Cycle time (all channels), min.":"125 µs","Current consumption (rated value)":"45 mA; without load","Type of mechanical coding element":"Type A","Reparameterization possible in RUN":"Yes","Crosstalk between the outputs, max.":"-50 dB","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","Between The Channels And Backplane Bus":"Yes","For Current Output Two-Wire Connection":"Yes","For Voltage Output Two-Wire Connection":"Yes","PROFIBUS from GSD version/GSD revision":"GSD Revision 5","PROFINET from GSD version/GSD revision":"GSDML V2.3","For Voltage Output Four-Wire Connection":"Yes","Current, relative to output range, (+/-)":"0.1 %","Voltage output, short-circuit protection":"Yes","Voltage, relative to output range, (+/-)":"0.1 %","Execution and activation time (TCO), min.":"70 µs","Monitoring of the supply voltage (PWR-LED)":"Yes; green PWR LED","With Current Outputs, Inductive Load, Max.":"1 mH","Installation altitude above sea level, max.":"5 000 m; Restrictions for installation altitudes > 2 000 m, see manual","STEP 7 configurable/integrated from version":"V5.5 SP3 / -","Voltage output, short-circuit current, max.":"45 mA","With Voltage Outputs, Capacitive Load, Max.":"1 µF","Linearity error (relative to output range), (+/-)":"0.03 %","Temperature error (relative to output range), (+/-)":"0.003 %/K","Resolution with overrange (bit including sign), max.":"16 bit","STEP 7 TIA Portal configurable/integrated from version":"V13 SP1","Color code for module-specific color identification plate":"CC00","Between The Channels And The Power Supply Of The Electronics":"Yes","Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)":"0.02 %","Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)":"0.03 %"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$418.00 – $567.72","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/81d43a2d2d7eb7121c7151985b909dbd.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=190222&mlfb=6ES7135-6HB00-0DA1"},"ai":{"faq":[{"question":"What is the physical depth of this module?","answer":"It is 58 mm deep, compatible with standard ET 200SP enclosures."},{"question":"Does this module support isochronous mode?","answer":"Yes, it supports isochronous mode and oversampling for synchronized high-speed output updates."},{"question":"Can this module be used with an existing ET 200SP station using BU type A0 base units?","answer":"Yes, it is compatible with BU type A0 and A1 base units."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7135-6HB00-0DA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7135-6HB00-0DA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}