{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7136-6AA00-0CA1","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7136-6AA00-0CA1","canonicalUrl":"https://aoctrl.com/siemens/6ES7136-6AA00-0CA1","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7136-6AA00-0CA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200SP, analog input module, 6ES7136-6AA00-0CA1, 4 analog inputs, 24 V DC, 0/4-20 mA, SIL 3, diagnostic alarm.","salesMarkdown":"Siemens 6ES7136-6AA00-0CA1 is a 4-channel analog input module for ET 200SP that accepts 0 to 20 mA and 4 to 20 mA signals with configurable integration times. It is rated SIL 3 and operates on 24 V DC with 2 W dissipation. ## Mechanical & Diagnostic Fit Mechanical fit matches the ET 200SP base units BU type A0 or A1. Width is 15 mm, height 73 mm, depth 58 mm. The module auto-encodes its address on the backplane, supports firmware updates, and provides I&M data (I&M0 through I&M3) for asset management. Diagnostic capabilities include wire-break and short-circuit detection, a red/green DIAG LED and per-channel red LED. The analog section is isolated with 707 V DC type test.","metaTitle":"Siemens 6ES7136-6AA00-0CA1 Analog Input Module, 4 AI, SIL 3","metaDescription":"Active ET 200SP analog input module with 4 channels, 0/4-20 mA, 24 V supply, diagnostic alarms, SIL 3. 15 mm wide, 2 W. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Analog Input Modules"],"specifications":{"24 V":"Yes; min. L+ (-1.5 V)","Depth":"58 mm","Width":"15 mm","Height":"73 mm","Inputs":"14 byte; S7-300/400F CPU, 13 byte","Outputs":"5 byte; S7-300/400F CPU, 4 byte","RUN LED":"Yes; green LED","I&M data":"Yes; I&M0 to I&M3","ERROR LED":"Yes; red LED","Step: low":"Yes; 2x / 4x conversion cycle time","0 to 20 mA":"Yes","Step: High":"Yes; 32x / 64x conversion cycle time","Step: None":"Yes; 1x conversion cycle time","Wire-break":"Yes","Step: Medium":"Yes; 8x / 16x conversion cycle time","4 mA to 20 mA":"Yes","Short-circuit":"Yes","Shielded, Max.":"1 000 m","Parameterizable":"Yes","Weight, approx.":"48 g","lifecycle_stage":"current","Diagnostic alarm":"Yes","Power loss, typ.":"2 W","Rated value (DC)":"24 V","usable BaseUnits":"BU type A0, A1","Limit value alarm":"No","Automatic encoding":"Yes","FW update possible":"Yes","Between The Channels":"No","Diagnostics function":"Yes","Output current, max.":"300 mA; total current of all encoders/channels","Integration time (ms)":"20 / 16,667","Isolation tested with":"707 V DC (type test)","Measurement principle":"Sigma Delta","SIL acc. to IEC 61508":"SIL 3","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red DIAG LED","For Channel Diagnostics":"Yes; red LED","For current measurement":"4","Number of analog inputs":"4","Short-circuit protection":"Yes","between the inputs (UCM)":"10 Vpp","Current consumption, max.":"0.4 A","Number of smoothing levels":"7","Calibration possible in RUN":"No","Reverse polarity protection":"Yes","Vertical Installation, Max.":"50 °C","Vertical Installation, Min.":"0 °C","Horizontal Installation, Max.":"60 °C","Horizontal Installation, Min.":"0 °C","Input resistance (0 to 20 mA)":"125 Ω","Monitoring the supply voltage":"Yes","Common mode interference, min.":"70 dB","Electronic coding element type F":"Yes","Input resistance (4 mA to 20 mA)":"125 Ω","Category according to ISO 13849-1":"Cat. 4","Current consumption (rated value)":"0.38 A","Integration time, parameterizable":"Yes","Burden of 2-wire transmitter, max.":"650 Ω","Reparameterization possible in RUN":"No","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","Between The Channels And Backplane Bus":"Yes","Power available from the backplane bus":"70 mW","Current, relative to input range, (+/-)":"0.1 %","Monitoring of the supply voltage (PWR-LED)":"Yes; green PWR LED","Performance level according to ISO 13849-1":"PLe","For Current Measurement As 2-Wire Transducer":"Yes","For Current Measurement As 4-Wire Transducer":"Yes","power supply according to NEC Class 2 required":"No","Low demand mode: PFDavg in accordance with SIL3":"< 5.00E-05","Linearity error (relative to input range), (+/-)":"0.1 %","Temperature error (relative to input range), (+/-)":"0.023 %/K","Resolution with overrange (bit including sign), max.":"16 bit","STEP 7 TIA Portal configurable/integrated from version":"V15 with HSP 203","High demand/continuous mode: PFH in accordance with SIL3":"< 1.00E-09 1/h","Color code for module-specific color identification plate":"CC00","Between The Channels And The Power Supply Of The Electronics":"Yes","Interference voltage suppression for interference frequency f1 in Hz":"50 / 60 Hz","Permissible Input Current For Current Input (Destruction Limit), Max.":"35 mA","Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)":"0.1 %","Series mode interference (peak value of interference < rated value of input range), min.":"40 dB"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$373.38","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3cf167ba1f4a213dc03eb98151fa537f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1128698&mlfb=6ES7136-6AA00-0CA1","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7136-6AA00-0CA1/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7136-6AA00-0CA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7136-6AA00-0CA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}