{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7136-6RA00-0BF0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7136-6RA00-0BF0","canonicalUrl":"https://aoctrl.com/siemens/6ES7136-6RA00-0BF0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7136-6RA00-0BF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC ET 200SP, 6ES7136-6RA00-0BF0, Digital Output Module, 1 relay output (2 NO), 24 V DC coil, 230 V AC / 24 V DC switching, SIL 3, diagnostics, 20 x 73 x 58 mm.","salesMarkdown":"## Integrator's note — this relay output slice The 6ES7136-6RA00-0BF0 is a single-channel relay output module with two normally-open contacts rated for AC 230 V or DC 24 V switching and a 24 V DC coil. It is rated SIL 3. The relay contact current is 5 A at moderate ambient temperatures, derating to 3 A at 50 °C and 3 A at 60 °C. The module fits a BU type F0 base unit (not included). Physical size is 20 mm wide, 73 mm high, 58 mm deep — standard slice width for the ET 200SP family, so it keeps the rail density predictable. A green RUN LED and a green/red DIAG LED sit on the front; channel status per output is indicated by a green LED. ## Application and compliance detail The relay is UL approved for Pilot Duty B300, R300, with overvoltage category III (per IEC/EN 61131-2:2007) or II. Dielectric isolation tested at 2 545 V DC for 2 s; channel isolation only for SELV/PELV circuits. The module supports I&M data records 0 to 3 for asset management and automatic encoding via the base unit. Diagnostics functions are built in, including short-circuit and wire-break detection on the load side (with appropriate external wiring). Minimum switching current is 1 mA, which matters when driving low-signal loads such as PLC inputs or pilot LEDs.","metaTitle":"Siemens 6ES7136-6RA00-0BF0 SIMATIC ET 200SP Relay Output, 1x","metaDescription":"Siemens 6ES7136-6RA00-0BF0 SIMATIC ET 200SP digital output module with 1 relay output (2 NO contacts), 24 V DC coil, rated 230 V AC/24 V DC, SIL 3, diagnostics, current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Digital Output Modules"],"specifications":{"Depth":"58 mm","Width":"20 mm","title":"6ES7136-6RA00-0BF0","Height":"73 mm","Inputs":"1 byte","RUN LED":"Yes; green/red DIAG LED","I&M data":"Yes; I&M0 to I&M3","description":"SIMATIC DP, Electronics module f. ET200SP, F-RQ 1x 24 V DC/24..230VAC/5A ST, 20 mm overall width, 1 relay output (2 NO) Summation output current 5 A, load voltage 24 V DC and 24.. 230 V AC, Can be used up to PL E (ISO 13849-1: 2008)/ SIL 3 (IEC 61508: 2010) if control takes place by (e.g. 6ES7136-6DB00-0CA0) F-DQ","Shielded, Max.":"500 m; for load contacts","Weight, approx.":"56 g","lifecycle_stage":"current","Power loss, typ.":"1 W","Rated value (DC)":"24 V; Coil voltage","Unshielded, Max.":"300 m; for load contacts","usable BaseUnits":"BU type F0","Automatic encoding":"Yes","On Lamp Load, Max.":"25 W","up to 40 °C, max.":"5 A; note derating data in the manual","up to 50 °C, max.":"3 A; note derating data in the manual","up to 60 °C, max.":"3 A; note derating data in the manual","Between The Channels":"Yes; for SELV / PELV only","Diagnostics function":"Yes","Overvoltage category":"III (according to IEC/EN 61131-2:2007 and EN 298:2012), II (according to IEC 61131-2:2017 and IEC 61010-2-201)","Isolation tested with":"2 545 V DC/2 s (routine test)","SIL acc. to IEC 61508":"SIL 3","Channel status display":"Yes; green LED","Type of digital output":"Relays","Number of relay outputs":"1; 2 NO contacts","Switching current, min.":"1 mA","Mechanical coding element":"Yes","Number of digital outputs":"1","With Inductive Load, Max.":"see additional description in the manual","With Resistive Load, Max.":"see additional description in the manual","Control cable (input), max.":"10 m","Controlling a digital input":"Yes","Vertical Installation, Max.":"50 °C","Vertical Installation, Min.":"0 °C","Rated switching voltage (AC)":"230 V","Rated switching voltage (DC)":"24 V","Horizontal Installation, Max.":"60 °C","Horizontal Installation, Min.":"0 °C","Relay approved acc. to UL 508":"Yes; Pilot Duty B300, R300","Suitable for safety functions":"Yes","Thermal continuous current, max.":"5 A","Category according to ISO 13849-1":"4","Type of mechanical coding element":"type C","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","External Protection For Relay Outputs":"yes; 6 A, see data in manual","Between The Channels And Backplane Bus":"Yes","PROFINET from GSD version/GSD revision":"V2.31","Power available from the backplane bus":"100 mW","Between Backplane Bus And Supply Voltage":"707 V DC (type test)","Performance level according to ISO 13849-1":"PLe","Rated supply voltage of relay coil L+ (DC)":"24 V","Limitation of inductive shutdown voltage to":"No","STEP 7 configurable/integrated from version":"V5.5 SP4 and higher","Switching current after exceeding 300 mA, max.":"5 A","Switching current after exceeding 300 mA, min.":"10 mA","power supply according to NEC Class 2 required":"No","Low demand mode: PFDavg in accordance with SIL2":"< 1.00E-04, function test 1x per year","Low demand mode: PFDavg in accordance with SIL3":"< 1.00E-05, function test 1x per month","Between Channels And Backplane Bus/Supply Voltage":"DC 2 545 V 2 s (routine test), impulse voltage test DC 7 200 V / 5 positive and 5 negative pulses (type test)","STEP 7 TIA Portal configurable/integrated from version":"V13","High demand/continuous mode: PFH in accordance with SIL2":"< 1.00E-08 1/h, function test 1x per year","High demand/continuous mode: PFH in accordance with SIL3":"< 6.00E-09 1/h, function test 1x per month","Color code for module-specific color identification plate":"CC42","Between The Channels And The Power Supply Of The Electronics":"Yes","Current consumption of relays (coil current of all relays), max.":"70 mA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$81.28 – $239.86","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7e23208d88e0fdd6bb697e4c25ffeace.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=97729&mlfb=6ES7136-6RA00-0BF0"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7136-6RA00-0BF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7136-6RA00-0BF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}