{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7142-5AF00-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7142-5AF00-0BA0","canonicalUrl":"https://aoctrl.com/siemens/6ES7142-5AF00-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7142-5AF00-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200SP digital output module, 8 outputs, 2 A, IP65/67, M8, SIL 2.","salesMarkdown":"Siemens 6ES7142-5AF00-0BA0 is an ET 200SP digital output slice with 8 outputs rated 2 A per channel, built for distributed I/O in washdown or harsh environments — IP65/67, M8 shielded connectors, and a -30 to 55 °C range. It's current production, so no last-time-buy scramble; we quote against your BOM line. Each output switches 2 A continuous (resistive load at 100 Hz max; inductive loads at 0.1 Hz typical, 0.25 Hz at 25 °C). The module groups outputs in two load groups of four, with 4 A total per group — so if you're driving solenoids or contactors, keep the per-group draw under 4 A and no more than two inductive channels per group. Short-circuit protection is electronic and per channel, with a typical response threshold of 2.8 A. IP65/67 means it can live on-machine without a separate enclosure as long as the M8 connectors are tightened. The 707 V DC type-test isolation between channels and backplane means it sits comfortably on a 24 VDC supply with reverse polarity protection built in. Safety-rated at SIL 2 and Cat. 3, with parameterizable diagnostic alarms and substitute values per channel. The cross-shop candidate 6ES7522-1BH01-0AB0 is a central rack module, not an IP65/67 remote slice. Connector type differs (M8 vs front connector) and mounting footprint is different. Use this part for IP65/67 on-machine placement.","metaTitle":"Siemens 6ES7142-5AF00-0BA0 8-DO 2A IP65/67 SIL2","metaDescription":"Siemens ET 200SP digital output module, 8 outputs, 2A per channel, IP65/67, M8, SIL 2 / Cat. 3. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLC Communication Modules"],"specifications":{"Max.":"55 °C","Min.":"-30 °C","Depth":"40 mm","Width":"45 mm","title":"6ES7142-5AF00-0BA0","Height":"159 mm","I&M data":"Yes; I&M0 to I&M3","Lower Limit":"12 Ω","Upper Limit":"4 kΩ","description":"SIMATIC ET 200AL, DQ 8x 24 V DC/2 A, 8x M12, Degree of protection IP67","In Groups Of":"4; 2 load groups for 4 outputs each","ET-Connection":"M8, 4-pin, shielded","Short-circuit":"Yes; Outputs to ground; module by module","Weight, approx.":"192 g","lifecycle_stage":"current","Diagnostic alarm":"Yes; Parameterizable","Firmware version":"V1.0.x","Power loss, typ.":"4 W","Rated value (DC)":"24 V","Unshielded, Max.":"30 m","On Lamp Load, Max.":"1 Hz","For Signal \"1\", Min.":"L+ (-0.8 V)","HW functional status":"FS03","Isolation tested with":"707 V DC (type test)","SIL acc. to IEC 62061":"SIL 2","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red LED","Current per group, max.":"4 A; For inductive load max. 2 channels per group","IP degree of protection":"IP65/67","Response threshold, typ.":"2.8 A","Short-circuit protection":"Yes; per channel, electronic","Between The Load Voltages":"Yes","Number of digital outputs":"8","With Inductive Load, Max.":"0.1 Hz; 0.25 Hz at 25 °C","With Resistive Load, Max.":"100 Hz","For Signal \"1\" Rated Value":"2 A","For load voltage monitoring":"Yes; green LED","Reverse polarity protection":"Yes; against destruction; load increasing","from load voltage 2L+, max.":"4 A; Maximum value","Substitute values connectable":"Yes; channel by channel, parameterizable","Category according to ISO 13849-1":"Cat. 3","Current consumption (rated value)":"40 mA; without load","Between The Channels, In Groups Of":"4","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","For Signal \"0\" Residual Current, Max.":"0.5 mA","Between The Channels And Backplane Bus":"Yes","For Signal \"1\" Permissible Range, Max.":"2 A; with inductive load to IEC 60947-5-1, DC-13 / AC-15","PROFIBUS from GSD version/GSD revision":"GSD as of Revision 5","PROFINET from GSD version/GSD revision":"GSDML V2.3.1","Performance level according to ISO 13849-1":"PL d","from load voltage 1L+ (unswitched voltage)":"4 A; Maximum value","Limitation of inductive shutdown voltage to":"2L+ (-47 V)","STEP 7 configurable/integrated from version":"V5.5 SP4 Hotfix 7 or higher","power supply according to NEC Class 2 required":"No","Design of electrical connection for supply voltage":"M8, 4-pole","STEP 7 TIA Portal configurable/integrated from version":"STEP 7 V13 SP1 or higher","Suitable for safety-related tripping of standard modules":"Yes; From FS01","Design of electrical connection for the inputs and outputs":"M12, 5-pole","Between The Channels And The Power Supply Of The Electronics":"No; 4 channels are non-isolated and 4 channels are isolated from supply voltage 1L+"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$93.98","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/be1699dde60089070a9c868ac1c9a61b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629466&mlfb=6ES7142-5AF00-0BA0"},"ai":{"faq":[{"question":"What are the operating temperature limits?","answer":"Rated for -30 °C to 55 °C ambient."},{"question":"What connector type does it use?","answer":"M8, 4-pin, shielded; IP65/67 rated when mated."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7142-5AF00-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7142-5AF00-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}