{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7142-6BG00-0BB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7142-6BG00-0BB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7142-6BG00-0BB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7142-6BG00-0BB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC ET 200SP, 6ES7142-6BG00-0BB0, PROFINET DQ module, 2x M12, IRT 250 µs, -40 to +60°C.","salesMarkdown":"The Siemens 6ES7142-6BG00-0BB0 is a digital output (DQ) module in the ET 200SP family, built for PROFINET with IRT down to 250 µs in 125 µs increments. That makes it a candidate for isochronous applications like motion or high-speed gating where jitter under 10 µs matters. It carries 1 byte of output data and reads 1 byte of QI information. Protocol support covers PROFINET, Modbus TCP, and EtherNet/IP. MRP and shared-device mode with up to two EtherNet/IP scanners allow it to sit in a redundant network without a separate media converter. ## Protection and diagnostics that keep the line running Each output channel is short-circuit protected to M with channel-by-channel detection. Wire-break detection is built in; it trips between 48 Ω and 4 kΩ. That gives the maintenance planner a reason to log the fault before the motor drops out. Temperature range covers -40 to +60 °C—no derating worry in an unheated enclosure or next to a hot machine base. Diagnostic LEDs (IO LED red-green-yellow, MS/NS green/red, RUN green, ERROR red, MAINT yellow) make first-line troubleshooting possible without a laptop. No PROFIsafe or CIP Safety onboard—if the application needs functional safety over PROFINET, this module handles only standard I/O. The safety CPU would need a separate F-module.","metaTitle":"Siemens 6ES7142-6BG00-0BB0 SIMATIC ET 200SP DQ, 2x M12, IRT","metaDescription":"PROFINET DQ module with IRT, MRP, and 2x M12 ports. Sourced to order. 1 byte output, short-circuit protection, -40 to +60°C.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLC Communication Modules"],"specifications":{"DQ":"Yes","ARP":"Yes","IRT":"Yes; 250 µs to 4 ms in 125 µs frame","MRP":"Yes","MSO":"Yes","LLDP":"Yes","Max.":"60 °C","Min.":"-40 °C","SNMP":"Yes","Depth":"48 mm","Width":"45 mm","title":"6ES7142-6BG00-0BB0","Height":"200 mm","IO LED":"Yes; red-green-yellow LED","Inputs":"1 byte for QI information","MS LED":"Yes; green/red LED","NS LED":"Yes; green/red LED","TCP/IP":"Yes; (only EtherNet/IP or Modbus TCP)","Outputs":"1 byte","RUN LED":"Yes; green LED","I&M data":"Yes; I&M0 to I&M3","M12 port":"Yes; 2x M12, 4-pin, D-coded","ERROR LED":"Yes; red LED","MAINT LED":"Yes; Yellow LED","PROFIsafe":"No","CIP Safety":"No","Max. Cycle":"4 ms","Modbus TCP":"Yes","Wire-break":"Yes","on S7-400H":"Yes","EtherNet/IP":"Yes","Lower Limit":"48 Ω","Upper Limit":"4 kΩ","description":"SIMATIC ET 200eco PN, DQ 8x 24 V DC/0.5 A, M12-L, 8x M12, single and double assignment, source output (PNP,switching to P potential), substitute value output, channel diagnostics for wire break and short-circuit at the output, shared device with 2 controllers, 0.25 ms isochronous mode, prioritized startup, MSO, MRP, S2 redundancy, I&M0...3, multi-fieldbus, PN IO, Ethernet IP, Modbus TCP, degree of protection IP67 / IP69K","Autocrossing":"Yes","Equidistance":"Yes","For Uprating":"No","Jitter, max.":"10 µs","Shared device":"Yes; 2x EtherNet/IP Scanner","Short-circuit":"Yes; Outputs to M; channel by channel","on S7-1500R/H":"Yes","Interface type":"PROFINET with 100 Mbit/s full duplex (100BASE-TX)","Autonegotiation":"Yes","Number of ports":"2","Parameterizable":"Yes","Weight, approx.":"780 g","lifecycle_stage":"current","\"0\" To \"1\", Max.":"50 µs; at rated load","\"1\" To \"0\", Max.":"100 µs; at rated load","24 V DC circuits":"707 V DC (type test)","Current-sourcing":"Yes","Diagnostic alarm":"Yes; Parameterizable","Firmware version":"V5.1.x","Isochronous mode":"Yes","Power loss, typ.":"7 W","Rated value (DC)":"24 V","Unshielded, Max.":"30 m","H-Sync forwarding":"Yes","Integrated Switch":"Yes","FW update possible":"Yes","On Lamp Load, Max.":"1 Hz","PROFINET IO Device":"Yes","Prioritized startup":"Yes","Read Coils (Code=1)":"Yes","Between The Channels":"No","For Signal \"1\", Min.":"2L+ (-0,8 V)","HW functional status":"FS02","I/O request interval":"2 ms","Shortest Clock Pulse":"250 µs","Maintenance interrupt":"Yes; Parameterizable","Open IE communication":"Yes","SIL acc. to IEC 62061":"SIL 2","CIP Explicit Messaging":"Yes","CIP Implicit Messaging":"Yes","Channel status display":"Yes; green LED","DLR (Device Level Ring)":"No","For Channel Diagnostics":"Yes; red LED","IP degree of protection":"IP65/67/69K","Transmission rate, max.":"100 Mbit/s","Current per module, max.":"4 A","Response threshold, typ.":"1 A","Short-circuit protection":"Yes; per channel, electronic","Between The Load Voltages":"Yes","LargeForwardOpen (Class3)":"No","Number of digital outputs":"8","With Inductive Load, Max.":"0.5 Hz","With Resistive Load, Max.":"100 Hz","For Signal \"1\" Rated Value":"0.5 A","Parameter change by master":"No","Write Single Coil (Code=5)":"Yes","Controlling a digital input":"Yes","For load voltage monitoring":"Yes; green LED","Reverse polarity protection":"Yes; against destruction; load increasing","from load voltage 2L+, max.":"12 A; Maximum value","Device identifier (DeviceID)":"0306H","Modbus TCP Security Protocol":"No","Connection display LINK TX/RX":"Yes; green LED, only link","Monitoring the supply voltage":"Yes","Number of PROFINET interfaces":"1","Read Discrete Inputs (Code=2)":"Yes","Substitute values connectable":"Yes","Address space per module, max.":"20 byte","Write Multiple Coils (Code=15)":"Yes","Access-consistent address space":"2 byte","Address space per station, max.":"20 byte","Design of electrical connection":"4/5-pin M12 circular connectors","Diagnostic information readable":"Yes","For Redundant Control Of A Load":"Yes","Number of connections per slave":"12","PROFINET system redundancy (R1)":"No","PROFINET system redundancy (S2)":"Yes","Read Holding Registers (Code=3)":"Yes","Requested Packet Interval (RPI)":"2 ms","between Ethernet and electronics":"Yes","Category according to ISO 13849-1":"Cat. 3","Current consumption (rated value)":"65 mA; without load","Supports protocol for PROFINET IO":"Yes","Remark On Safety-Oriented Shutdown":"https://support.industry.siemens.com/cs/de/en/view/39198632","Write Multiple Registers (Code=16)":"Yes","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","For Signal \"0\" Residual Current, Max.":"0.1 mA","For Signal \"1\" Permissible Range, Max.":"0.5 A","PROFINET from GSD version/GSD revision":"GSDML V2.3.x","Number of configurable submodules, max.":"2","Multi Fieldbus Configuration Tool (MFCT)":"from V1.3 SP1","Device ID according to ODVA (Product code)":"0FA6H","Performance level according to ISO 13849-1":"PL d","from load voltage 1L+ (unswitched voltage)":"12 A; Maximum value","Limitation of inductive shutdown voltage to":"Typ. 2L+ (-52 V)","Number of scanners with shared device, max.":"2","Manufacturer ID according to ODVA (VendorID)":"04E3H","Test voltage for interface, rms value [Vrms]":"1 500 V; According to IEEE 802.3","power supply according to NEC Class 2 required":"No","Number of IO Controllers with shared device, max.":"2","Design of electrical connection for supply voltage":"M12, 4-pin, L-coded","Ambient air temperature-barometric pressure-altitude":"Up to max. 5 000 m, at installation height > 2 000 m additional restrictions","STEP 7 TIA Portal configurable/integrated from version":"STEP 7 V17 or higher with HSP 0363","Suitable for safety-related tripping of standard modules":"Yes; From FS02","Design of electrical connection for the inputs and outputs":"M12, 5-pin, A-coded","Between The Channels And The Power Supply Of The Electronics":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$583.20","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/850096a27dc7bea9014d29ed470e2cbc.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1343057&mlfb=6ES7142-6BG00-0BB0"},"ai":{"faq":[{"question":"Does the 6ES7142-6BG00-0BB0 support isochronous real-time (IRT)?","answer":"Yes. IRT update times range from 250 µs to 4 ms in 125 µs steps, with jitter limited to 10 µs. That suits motion axes or high-speed crosscut applications."},{"question":"Can it be used with Siemens S7-1500R/H or S7-400H redundant systems?","answer":"Yes. The module is explicitly approved for both S7-1500R/H and S7-400H redundant CPU architectures."},{"question":"What diagnostics are available per channel?","answer":"Short-circuit protection per channel to M and wire-break detection with limits of 48 Ω to 4 kΩ. Status LEDs include IO, MS, NS, RUN, ERROR, and MAINT."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7142-6BG00-0BB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7142-6BG00-0BB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}