{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7153-2BA02-0XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7153-2BA02-0XB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7153-2BA02-0XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7153-2BA02-0XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC S7-300 / ET 200M IM 153-2 PROFIBUS DP interface module, 12 Mbit/s, RS-485, 9-pin Sub-D, IP20, 0–60 °C, 5.5 W.","salesMarkdown":"## Part identity and role The 6ES7153-2BA02-0XB0: The PROFIBUS DP interface runs at up to 12 Mbit/s (automatic baud rate detection enabled), uses RS-485 transmission, and terminates in a 9-pin Sub-D socket. It supports 1 to 125 node addresses and provides potential separation across the bus. ## Time stamping and event capture The module records timestamps with a resolution of 0.466 ns, applying RFC 1119 time format. It captures up to 15 message buffers, each holding 20 event messages, triggered on rising or falling edges. SYNC and FREEZE bus commands are supported. Powered via the backplane bus (20.4 to 28.8 V DC input range). The bus holds up stored energy for 5 ms after a mains failure – enough for the CPU to complete a safe shutdown cycle. Configuration is done in STEP 7, COM PROFIBUS, or third-party tools using GSD file SI04801.GSG.","metaTitle":"Siemens 6ES7153-2BA02-0XB0 IM 153-2 PROFIBUS DP, 12 Mbit/s","metaDescription":"PROFIBUS DP interface module for ET 200M. 12 Mbit/s, RS-485, 9-pin Sub-D, 0–60 °C, 5.5 W. Current production. Order to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLC Communication Modules"],"specifications":{"I2t":"0.1 A²·s","Max.":"60 °C","Min.":"0 °C","Depth":"117 mm","Width":"40 mm","title":"6ES7153-2BA02-0XB0","Height":"125 mm","Inputs":"244 byte","STEP 7":"Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file","TCP/IP":"No","Outputs":"244 byte","Accuracy":"1 ms; 1 ms at up to 8 modules; 10 ms at up to 12 modules","GSD file":"SI04801.GSG","Time format":"RFC 1119","description":"***Spare part*** SIMATIC DP, Connection ET 200M IM 153-2 High Feature for max. 12 S7-300 modules with redundancy capability, Timestamping suitable for isochronous mode New features: up to 12 modules can be used Slave INITIATIVE for Drive ES and Switch ES Expanded quantity structure for HART auxiliary variables Operation of the 64-channel modules 32 signals/slot","SYNC capability":"Yes","Time resolution":"0.466 ns","Weight, approx.":"360 g","lifecycle_stage":"current","Power loss, typ.":"5.5 W","Rated value (DC)":"5 V","FREEZE capability":"Yes","Inrush current, typ.":"3 A","Isolation tested with":"Isolation voltage 500 V","Transmission procedure":"RS 485","IP degree of protection":"IP20","Transmission rate, max.":"12 Mbit/s","Design of the connection":"9-pin sub D socket","Current consumption, max.":"600 mA","Number of message buffers":"15","Automatic Baud Rate Search":"Yes","Messages per message buffer":"20","Potential separation exists":"Yes","Time stamp on signal change":"rising / falling edge as signal entering or exiting","Number of node addresses, max.":"1 to 125 permitted","for backplane bus (5 V DC), max.":"1.5 A","Bus protocol/transmission protocol":"PROFIBUS DP to EN 50170","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","Output current of the interface, max.":"70 mA","Automatic Detection Of Transmission Rate":"Yes","Mains/voltage failure stored energy time":"5 ms","Number of stampable digital inputs, max.":"128; Max. 128 signals/station; max. 32 signals/slot","Installation altitude above sea level, max.":"3 000 m","Number of modules per DP slave interface, max.":"12","Direct data exchange (slave-to-slave communication)":"Yes; Sender","External Protection For Power Supply Lines (Recommendation)":"2,5 A","Time interval for transmitting the message buffer if a message is present":"1 000 ms"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$247.65 – $455.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/599fb3d3d8592ec955b0ddbf0a810439.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=230229&mlfb=6ES7153-2BA02-0XB0"},"ai":{"faq":[{"question":"What is the I²t rating?","answer":"The module carries a listed I²t of 0.1 A²·s, used for short-circuit energy coordination on the backplane bus."},{"question":"What is the maximum ambient temperature?","answer":"Operating temperature range is 0 °C to 60 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7153-2BA02-0XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7153-2BA02-0XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}