{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7153-2BA82-0XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7153-2BA82-0XB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7153-2BA82-0XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7153-2BA82-0XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens, ET 200M, PROFIBUS DP interface module, 6ES7153-2BA82-0XB0, 12 Mbit/s, 5 V DC backplane, 5.5 W, IP20.","salesMarkdown":"The Siemens 6ES7153-2BA82-0XB0 is a PROFIBUS DP slave interface module for the ET 200M distributed I/O family. It communicates at up to 12 Mbit/s over an RS-485 bus per EN 50170, exchanging up to 244 bytes each for input and output. The module draws a maximum of 650 mA from the backplane at 5 V DC, with a typical power loss of 5.5 W. The backplane current on the 5 V rail is limited to 1.5 A total — keep that in mind when populating the rack, because exceeding it drops the interface without warning. ## Time stamping and sequence-of-events capture Time stamps at signal change with a resolution of 0.466 ns and an accuracy of 1 ms when the station holds up to eight modules; accuracy relaxes to 10 ms with up to twelve modules. This module holds the station for event-triggered capture on a burner management or turbine governor system — that 1 ms window is fine for most plant-level sequence-of-events records, but if you need to resolve sub-millisecond faults you'll need a faster dedicated recorder. ## Integration notes Mounts on a DIN rail (IP20). Dimensions: 40×125×117 mm. PROFIBUS RS-485 via 9-pin sub-D; GSD file SI0480E.GSG. Operating temperature -25 to 60 °C; max altitude 3 000 m.","metaTitle":"Siemens 6ES7153-2BA82-0XB0 PROFIBUS DP IM, 12 Mbit/s","metaDescription":"Siemens 6ES7153-2BA82-0XB0 PROFIBUS DP interface module for ET 200M, 12 Mbit/s, 244 byte I/O, 5.5 W. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLC Communication Modules"],"specifications":{"I2t":"0.1 A²·s","Max.":"60 °C","Min.":"-25 °C","Depth":"117 mm","Width":"40 mm","title":"6ES7153-2BA82-0XB0","Height":"125 mm","Inputs":"244 byte","STEP 7":"Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file","Outputs":"244 byte","Accuracy":"1 ms; 1 ms at up to 8 modules; 10 ms at up to 12 modules","GSD file":"SI0480E.GSG","Time format":"RFC 1119","description":"********** Replacement part ********* SIMATIC DP, Connection DP/PA-LINK and ET200M IM153-2 HF for extended temperature range for max. 12 S7-300 modules with redundancy capability, timestamping suitable for isochronous mode new features: up to 12 modules can be used Slave initiative for Drive ES and Switch ES expanded quantity structure for HART auxiliary variables Operation of the 64-channel modules 32 signals / slot","SYNC capability":"Yes","Time resolution":"0.466 ns","Weight, approx.":"360 g","lifecycle_stage":"current","Power loss, typ.":"5.5 W","Rated value (DC)":"5 V","FREEZE capability":"Yes","Inrush current, typ.":"3 A","Isolation tested with":"Isolation voltage 500 V","Transmission procedure":"RS 485","IP degree of protection":"IP20","Transmission rate, max.":"12 Mbit/s","Design of the connection":"9-pin sub D socket","Current consumption, max.":"650 mA","Number of message buffers":"15","Automatic Baud Rate Search":"Yes","Messages per message buffer":"20","Time stamp on signal change":"rising / falling edge as signal entering or exiting","Number of node addresses, max.":"1 to 125 permitted","for backplane bus (5 V DC), max.":"1.5 A","Bus protocol/transmission protocol":"PROFIBUS DP to EN 50170","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","Output current of the interface, max.":"70 mA","Automatic Detection Of Transmission Rate":"Yes","Mains/voltage failure stored energy time":"5 ms","Number of stampable digital inputs, max.":"128; Max. 128 signals/station; max. 32 signals/slot","Installation altitude above sea level, max.":"3 000 m","Number of modules per DP slave interface, max.":"12","Direct data exchange (slave-to-slave communication)":"Yes; Sender","External Protection For Power Supply Lines (Recommendation)":"2,5 A","Time interval for transmitting the message buffer if a message is present":"1 000 ms"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$520.70 – $568.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/599fb3d3d8592ec955b0ddbf0a810439.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=454906&mlfb=6ES7153-2BA82-0XB0"},"ai":{"faq":[{"question":"What is the I²t rating of this module?","answer":"The listed I²t value is 0.1 A²·s, used for fuse coordination of the backplane supply circuit."},{"question":"What is the maximum ambient temperature for operation?","answer":"The operating temperature range is from -25 °C to 60 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7153-2BA82-0XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7153-2BA82-0XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}