{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7157-0AC82-0XA0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7157-0AC82-0XA0","canonicalUrl":"https://aoctrl.com/siemens/6ES7157-0AC82-0XA0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7157-0AC82-0XA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200SP digital output module, 6ES7157-0AC82-0XA0, DQ Yes, current-sourcing, 24V DC, 8A total (derated), diagnostics.","salesMarkdown":"## ET 200SP Digital Output Slice The Siemens 6ES7157-0AC82-0XA0 is a digital output module for the ET 200SP distributed I/O system. DQ is enabled—this is a straight on/off slice, no PWM or MSO. Current-sourcing outputs, 24V DC nominal. Firmware V1.0, field-upgradeable. Diagnostics are built-in per module: wire-break detection, short-circuit to M and to L+, group error, and diagnostic alarm. The module reports I&M data up to I&M3. No oversampling or uprating. ## Interchangeability with 6ES7522-1BH01-0AB0 The 6ES7157-0AC82-0XA0 and the 6ES7522-1BH01-0AB0 both provide 24V DC digital outputs but are not mechanically interchangeable. The 6ES7157 mounts on a 15 mm BU type A0 base unit; the other module uses a different connector. No adapter exists — a panel wired for the 6ES7522 requires a redesign.","metaTitle":"Siemens 6ES7157-0AC82-0XA0 DO Module, 24V, 8A","metaDescription":"Active production ET 200SP digital output module with diagnostics. Rated 24V DC, 8A total at 30°C, current-sourcing. Quoted to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Digital Output Modules"],"specifications":{"DQ":"Yes","MSO":"No","PWM":"No","Depth":"58 mm","Width":"15 mm","title":"6ES7157-0AC82-0XA0","Height":"73 mm","I&M data":"Yes; I&M0 to I&M3","Wire-break":"Yes; Module-wise","Group error":"Yes","Lower Limit":"48 Ω","Upper Limit":"12 kΩ","description":"SIMATIC DP, distributed I/O field device interface DP/PA coupler not Ex-Version 1000mA/31V Field coupler between PROFIBUS DP and PROFIBUS PA for extended temperature range Degree of protection IP20","For Uprating":"No","Oversampling":"No","Shielded, Max.":"1 000 m","Current-sinking":"No","Weight, approx.":"28 g","lifecycle_stage":"current","\"0\" To \"1\", Typ.":"50 µs","\"1\" To \"0\", Typ.":"100 µs","Current-sourcing":"Yes","Diagnostic alarm":"Yes","Firmware version":"V1.0","Power loss, typ.":"1 W","Rated value (DC)":"24 V","Unshielded, Max.":"600 m","usable BaseUnits":"BU type A0","1-Wire Connection":"BU type A0","2-Wire Connection":"BU type A0 + Potential isolation module","3-Wire Connection":"BU type A0 + Potential isolation module","4-Wire Connection":"BU type A0 + Potential isolation module","FW update possible":"Yes","On Lamp Load, Max.":"10 Hz","Short-circuit to M":"Yes; Module-wise","up to 30 °C, max.":"8 A","up to 40 °C, max.":"6 A","up to 50 °C, max.":"4 A","up to 60 °C, max.":"4 A","Short-circuit to L+":"Yes; Module-wise","Between The Channels":"No","Diagnostics function":"Yes","Isolation tested with":"707 V DC (type test)","Redundancy capability":"Yes","SIL acc. to IEC 61508":"SIL 2","Channel status display":"Yes; Green LED","For Module Diagnostics":"Yes; green/red DIAG LED","Type of digital output":"Source output (PNP, current-sourcing)","For Channel Diagnostics":"No","Current per module, max.":"8 A","Response threshold, typ.":"0.7 to 1.3 A","Short-circuit protection":"Yes","Current consumption, max.":"60 mA; without load","Current per channel, max.":"0.5 A","Mechanical coding element":"Yes","Number of digital outputs":"16","With Inductive Load, Max.":"2 Hz","With Resistive Load, Max.":"100 Hz","For Signal \"1\" Rated Value":"0.5 A","Controlling a digital input":"Yes","Reverse polarity protection":"Yes","Vertical Installation, Max.":"50 °C; in all other mounting positions","Vertical Installation, Min.":"0 °C; in all other mounting positions","Horizontal Installation, Max.":"60 °C","Horizontal Installation, Min.":"0 °C","Monitoring the supply voltage":"Yes","Substitute values connectable":"Yes","Suitable for safety functions":"No","Address space per module, max.":"2 byte","DQ with energy-saving function":"No","For Redundant Control Of A Load":"Yes","Digital outputs, parameterizable":"Yes","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","For Signal \"0\" Residual Current, Max.":"0.1 mA","Between The Channels And Backplane Bus":"Yes","PROFIBUS as of GSD version/GSD revision":"GSD Revision 5","PROFINET as of GSD version/GSD revision":"GSDML V2.3","Monitoring of the supply voltage (PWR-LED)":"Yes; Green PWR LED","Performance level according to ISO 13849-1":"PL d","Limitation of inductive shutdown voltage to":"Typ. L+ (-50 V)","PCS 7 configurable/integrated as of version":"V8.1 SP1","STEP 7 configurable/integrated as of version":"V5.5 SP3 / -","Ambient air temperature-barometric pressure-altitude":"On request: Negative ambient temperature down to -30 °C (without condensation), installation altitudes between 2 000 m and 5 000 m","STEP 7 TIA Portal configurable/integrated as of version":"V11 SP2 / V13","Suitable for safety-related tripping of standard modules":"Yes; From FS03","Color code for module-specific color identification plate":"CC00","Between The Channels And The Power Supply Of The Electronics":"No","Isochronous operation (application synchronized up to terminal)":"No"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$800.10","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/599fb3d3d8592ec955b0ddbf0a810439.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=448539&mlfb=6ES7157-0AC82-0XA0"},"ai":{"faq":[{"question":"What is the DQ status of this module?","answer":"DQ is Yes; it functions as a digital output module."},{"question":"Does it support MSO?","answer":"No, MSO is not supported."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7157-0AC82-0XA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7157-0AC82-0XA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}