{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7223-1PH32-0XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7223-1PH32-0XB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7223-1PH32-0XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7223-1PH32-0XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens S7-1200 SM1223 combination module, 6ES7223-1PH32-0XB0, 8 relay outputs, -40 to 70 °C, 45 mm width, cULus/CE/FM/marine/UL/CSA approvals.","salesMarkdown":"The Siemens 6ES7223-1PH32-0XB0 is a DC-input/relay-output combination module for the S7-1200 system, providing 8 relay outputs and digital inputs in a 45 mm-wide housing. Rated for -40 to 70 °C, it carries cULus, CE, FM, KC, UL, CSA, marine, and RCM approvals—covering most global panel requirements. ## Input/output characteristics Inputs switch at a 15 V DC threshold (signal '1', 2.5 mA), compatible with standard 24 V DC sensors. Outputs handle 5–250 V AC or 5–30 V DC relay loads, up to 30 W DC / 200 W AC on lamp loads. Cabling distances: 500 m shielded, 150 m unshielded. Power draw is 5.5 W typical. Marked as current production. Available through standard Siemens distribution channels. For BOM-frozen projects, confirm lead time against your schedule.","metaTitle":"Siemens 6ES7223-1PH32-0XB0 S7-1200 SM1223, -40..70°C","metaDescription":"Siemens 6ES7223-1PH32-0XB0 S7-1200 combination module with 8 relay outputs, digital inputs, -40 to 70 °C, cULus/CE/FM/UL/CSA/Marine approvals. Active production. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLC I/O & Expansion Modules"],"specifications":{"Max.":"70 °C","Min.":"-40 °C","Depth":"75 mm","Width":"45 mm","cULus":"Yes","Height":"100 mm","CE mark":"Yes","Plastic":"Yes","FM approval":"Yes","KC approval":"Yes","UL approval":"Yes","CSA approval":"Yes","In Groups Of":"2","For Signal \"0\"":"5 V DC at 1 mA","For Signal \"1\"":"15 V DC at 2.5 mA","Shielded, Max.":"500 m","Marine approval":"Yes","Parameterizable":"Yes","Weight, approx.":"230 g","lifecycle_stage":"current","\"0\" To \"1\", Max.":"10 ms","\"1\" To \"0\", Max.":"10 ms","Diagnostic alarm":"Yes","Power loss, typ.":"5.5 W","Rated value (AC)":"5 V AC to 250 V AC","Rated value (DC)":"5 V DC to 30 V DC","Unshielded, Max.":"150 m","Fall height, max.":"0.3 m; five times, in product package","On Lamp Load, Max.":"30 W with DC, 200 W with AC","up to 40 °C, max.":"8","up to 50 °C, max.":"10 A; Current per mass","Between The Channels":"Relays","For Signal \"1\", Min.":"2.5 mA","For Signal \"1\", Typ.":"4 mA","RCM (formerly C-TICK)":"Yes","Type of input voltage":"DC","IP degree of protection":"IP20","Number of relay outputs":"8","Storage/transport, max.":"1 080 hPa","Storage/transport, min.":"660 hPa","For Status Of The Inputs":"Yes","Number of digital inputs":"8","Required Front Connector":"Yes","Short-circuit protection":"No; to be provided externally","For Status Of The Outputs":"Yes","Number of digital outputs":"8","With Inductive Load, Max.":"2 A","With Resistive Load, Max.":"2 A","Between Different Circuits":"750 V AC for 1 minute","For Signal \"1\" Rated Value":"2 A","Vertical Installation, Max.":"50 °C","Vertical Installation, Min.":"-20 °C","Horizontal Installation, Max.":"60 °C","Horizontal Installation, Min.":"-20 °C","Permissible Temperature Change":"5°C to 55°C, 3°C / minute","from backplane bus 5 V DC, max.":"145 mA","Number of operating cycles, max.":"mechanically 10 million, at rated load voltage 100 000","Between The Channels, In Groups Of":"2","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","Between The Channels And Backplane Bus":"1 500 V AC for 1 minute","For Signal \"1\" Permissible Range, Max.":"2 A","from load voltage L+ (without load), max.":"4 mA/input 11 mA/relay","Rated supply voltage of relay coil L+ (DC)":"24 V","Operation at 25 °C without condensation, max.":"95 %","Product Function / Supply Voltage For Transmitters":"Yes","For Signal \"0\", Max. (Permissible Quiescent Current)":"1 mA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$132.08 – $345.06","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a4442c09a7ee11fd820a4bb5289cf494.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=81219&mlfb=6ES7223-1PH32-0XB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7223-1PH32-0XB0/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this module carry?","answer":"It carries cULus, CE, FM, KC, UL, CSA, marine (e.g., DNV), and RCM approvals."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7223-1PH32-0XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7223-1PH32-0XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}