{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7231-5PF32-0XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7231-5PF32-0XB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7231-5PF32-0XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7231-5PF32-0XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC S7-1200, analog input module SM 1231 RTD, 8-channel, -40 to 70 °C, width 70 mm, Pt100/Ni1000/Cu10/resistance, diagnostic alarm, wire-break detection, cULus/CE/UL/CSA/FM/KC/Marine approvals.","salesMarkdown":"## Field integration notes The 6ES7231-5PF32-0XB0: RTD and resistance module for the S7-1200 backplane, supporting Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, LG-Ni1000, Cu10, and three resistance ranges (150, 300, 600 Ω). The diagnostic alarm and wire-break detection feed back to the CPU early, so you see a sensor fault before the loop goes dead. Operates from -40 °C to 70 °C ambient with atmospheric pressure from 795 to 1 080 hPa. Approved under cULus, UL, CSA, FM, KC, CE, and Marine, covering the common global panel certifications in one module. Mounts on the standard S7-1200 DIN rail; 70 mm width leaves room for a CPU and two more signal modules in a typical rack.","metaTitle":"Siemens 6ES7231-5PF32-0XB0 RTD Module, 70°C, -40°C","metaDescription":"Active Siemens S7-1200 analog input module for RTD/resistance. Supports Pt100, Ni1000, Cu10, resistance ranges, cULus, CE. Diagnostic alarm & wire-break detection. RFQ sourcing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Analog Input Modules"],"specifications":{"Max.":"70 °C","Min.":"-40 °C","Cu 10":"Yes","Depth":"75 mm","Width":"70 mm","cULus":"Yes","Alarms":"Yes","Height":"100 mm","Ni 100":"Yes","Ni 120":"Yes","Ni 200":"Yes","Ni 500":"Yes","Pt 100":"Yes","Pt 200":"Yes","Pt 500":"Yes","CE mark":"Yes","Current":"No","Ni 1000":"Yes","Plastic":"Yes","Pt 1000":"Yes","Voltage":"No","LG-Ni 1000":"Yes","Resistance":"Yes; 150 Ω, 300 Ω, 600 Ω","Wire-break":"Yes","FM approval":"Yes","KC approval":"Yes","UL approval":"Yes","CSA approval":"Yes","Thermocouple":"No","0 To 150 Ohms":"Yes","0 To 300 Ohms":"Yes","0 To 600 Ohms":"Yes","For Maintenance":"Yes","Marine approval":"Yes","Operation, max.":"1 080 hPa","Operation, min.":"795 hPa","Parameterizable":"No","Weight, approx.":"220 g","lifecycle_stage":"current","Diagnostic alarm":"Yes","Power loss, typ.":"1.5 W","Rated value (DC)":"24 V","Fall height, max.":"0.3 m; five times, in product package","Diagnostics function":"Yes; Can be read out","Measurement principle":"integrating","RCM (formerly C-TICK)":"Yes","Resistance thermometer":"Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG-Ni1000","IP degree of protection":"IP20","Number of analog inputs":"8; Resistance thermometer","Storage/transport, max.":"1 080 hPa","Storage/transport, min.":"660 hPa","For Status Of The Inputs":"Yes","Input resistance (Cu 10)":"10 Ω","Required Front Connector":"Yes","Current consumption, typ.":"40 mA","Input resistance (Ni 100)":"100 Ω","Input resistance (Ni 120)":"120 Ω","Input resistance (Ni 200)":"200 Ω","Input resistance (Ni 500)":"500 Ω","Input resistance (Pt 100)":"100 Ω","Input resistance (Pt 200)":"200 Ω","Input resistance (Pt 500)":"500 Ω","Input resistance (Ni 1000)":"1 000 Ω","Input resistance (Pt 1000)":"1 000 Ω","Vertical Installation, Max.":"50 °C","Vertical Installation, Min.":"-20 °C","Horizontal Installation, Max.":"60 °C","Horizontal Installation, Min.":"-20 °C","Input resistance (LG-Ni 1000)":"1 000 Ω","Monitoring the supply voltage":"Yes","Common mode interference, min.":"120 dB","from backplane bus 5 V DC, typ.":"80 mA","Integration time, parameterizable":"No","SO2 at RH < 60% without condensation":"S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free","Operation at 25 °C without condensation, max.":"95 %","Temperature error (relative to input range), (+/-)":"25 °C ±0.1%, to 55 °C ±0.2% total measurement range","Resolution with overrange (bit including sign), max.":"15 bit; + sign","Technical unit for temperature measurement adjustable":"Degrees Celsius/degrees Fahrenheit","Interference voltage suppression for interference frequency f1 in Hz":"85 dB at 50 / 60 / 400 Hz","Permissible Input Voltage For Voltage Input (Destruction Limit), Max.":"±35 V","Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)":"0.05 %"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$375.92 – $1,008.63","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/af61be94e65810b2cc9e0fb826fe666e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=98209&mlfb=6ES7231-5PF32-0XB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7231-5PF32-0XB0/alternatives.json"},"ai":{"faq":[{"question":"What approvals does it carry?","answer":"Holds cULus, CE, FM, KC, UL, CSA, and Marine approvals."},{"question":"Does it include diagnostic alarm and wire-break detection?","answer":"Yes, both are integrated. The diagnostic alarm and wire-break detection give early warning of sensor degradation or open circuits."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7231-5PF32-0XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7231-5PF32-0XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}