{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7232-4HB30-0XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7232-4HB30-0XB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7232-4HB30-0XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7232-4HB30-0XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC S7-1200 SM1232 analog output module, 2 AO configurable current/voltage, 24 V DC, 45 mm wide, IP20.","salesMarkdown":"## What this analog output module brings to the S7-1200 rack The 6ES7232-4HB30-0XB0: Operating temperature spans -40 to 70 °C, so it'll start up in an unheated warehouse or a refrigerated line without a cold-start complaint. Vertical installation derates the top end to 45 °C, horizontal to 55 °C — the figure you want for panel layout is the orientation you'll use. Each output can drive a 600 Ω load on current loops, or a minimum 1 000 Ω impedance on voltage outputs. ## Sourcing and compliance — what a buyer needs The module carries CE, FM (Factory Mutual), and RCM (formerly C-TICK) approvals. That covers most industrial machinery, process control, and Australian/New Zealand installations. IP20 protection means it's for a clean, dry enclosure — no hose-down zones. Power draw is 1.5 W typical from the backplane, plus 45 mA from the 24 V DC sensor supply. That's modest — two or three of these won't strain the CPU's bus capacity. Diagnostics are included: wire-break detection, short-circuit monitoring, and a diagnostic alarm that fires on the backplane. If a field device goes open or a cable gets pinched, the CPU sees it — you're not chasing ghosts. Common-mode voltage on the outputs is limited to 12 V max. That matters if you're driving isolated actuators with separate supplies — stay within that window or add isolation amplifiers. The module requires a front connector not included; order separately.","metaTitle":"Siemens 6ES7232-4HB30-0XB0 SM1232 Analog Output, 2 AO, -40..","metaDescription":"Siemens SM1232 analog output module 6ES7232-4HB30-0XB0 for S7-1200. 2 AO with current/voltage output, 24 V DC, -40 to 70 °C, IP20. Current production. CE, FM, RCM. Sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Analog Output Modules"],"specifications":{"Max.":"70 °C","Min.":"-40 °C","Depth":"75 mm","Width":"45 mm","title":"6ES7232-4HB30-0XB0","Alarms":"Yes","Height":"100 mm","CE mark":"Yes","Plastic":"Yes","0 to 20 mA":"Yes","Wire-break":"Yes","FM approval":"Yes","description":"***Spare part*** SIMATIC S7-1200, Analog output, SM 1232, 2 AO, +/-10 V, 14-bit resolution, or 0-20 mA, 13-bit resolution","Short-circuit":"Yes","-10 V to +10 V":"Yes","For Maintenance":"Yes","Operation, max.":"1 080 hPa","Operation, min.":"795 hPa","Weight, approx.":"180 g","lifecycle_stage":"current","Diagnostic alarm":"Yes","Power loss, typ.":"1.5 W","Rated value (DC)":"24 V","Fall height, max.":"0.3 m; five times, in product package","Diagnostics function":"Yes","RCM (formerly C-TICK)":"Yes","IP degree of protection":"IP20","Storage/transport, max.":"1 080 hPa","Storage/transport, min.":"660 hPa","Number of analog outputs":"2; Current or voltage","Required Front Connector":"Yes","Common mode voltage, max.":"12 V","Current consumption, typ.":"45 mA","For Status Of The Outputs":"Yes","With Current Outputs, Max.":"600 Ω","With Voltage Outputs, Min.":"1 000 Ω","Vertical Installation, Max.":"45 °C","Vertical Installation, Min.":"0 °C","Horizontal Installation, Max.":"55 °C","Horizontal Installation, Min.":"0 °C","Monitoring the supply voltage":"Yes","from backplane bus 5 V DC, typ.":"80 mA","SO2 at RH < 60% without condensation":"S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free","Current, relative to output range, (+/-)":"0.3 %","Voltage, relative to output range, (+/-)":"0.3 %","Operation at 25 °C without condensation, max.":"95 %","Temperature error (relative to output range), (+/-)":"25 °C ±0.3%, to 55 °C ±0.6% total measurement range","Resolution with overrange (bit including sign), max.":"14 bit; Voltage: 14 bit; Current : 13 bit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$296.04 – $315.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4e1b047c88d7a611c8aaabc85bee0854.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=214741&mlfb=6ES7232-4HB30-0XB0"},"ai":{"faq":[{"question":"What are the operating temperature limits?","answer":"The module is rated -40 to 70 °C for horizontal installation. Vertical installation derates the maximum to 45 °C. This range suits cold storage, unheated shops, and warm enclosures."},{"question":"What certifications does this module carry?","answer":"It has CE, FM (Factory Mutual), and RCM (formerly C-TICK) approvals. These cover European, North American hazardous-location, and Australasian installations. IP20 protection means it's for a dry enclosure."},{"question":"Does this module provide diagnostics?","answer":"Yes, it has wire-break detection, short-circuit monitoring, diagnostic alarm, and status indication for the outputs. Faults are reported via the backplane."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7232-4HB30-0XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7232-4HB30-0XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}