{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7322-5SD00-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7322-5SD00-0AB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7322-5SD00-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7322-5SD00-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC S7 SM 322, isolated digital output module, 4 DO, 24 V DC, 10 mA, Ex(i) protection, 1 x 20-pole front connector, diagnostics-capable, PTB tested, end-of-life.","salesMarkdown":"## Ex(i) isolated output for hazardous areas The 6ES7322-5SD00-0AB0: This SM 322 module provides four intrinsically safe (Ex(i)) digital outputs at 24 V DC, 10 mA per channel, designed to connect field devices in hazardous area Zones 0/1 and Div 1/2 locations. It carries FM marking for AIS CL.1, DIV 1, GP A, B, C, D and CL.I, DIV 2, GP A, B, C, D T4, plus ATEX marking [EEx ib] IIC with PTB test number Ex-96.D.2093X — so it is accepted in both North American and European hazardous-location installations. ## Channel isolation and diagnostics Each of the four outputs is galvanically isolated from the others in groups of one. Isolation voltage between channels is 60 V DC/30 V AC when used in the hazardous area, and 400 V DC/250 V AC when used in a non-hazardous area — a key distinction for wiring planning. Diagnostics are built in: a group error SF (red) LED, per-channel fault indicator (red), and per-channel status indicator (green). Diagnostic information is readable over the backplane bus, which saves commissioning time when a field device drops out. Maximum unshielded cable length to the field device is 200 m. The module draws 85 mA from the 5 V DC backplane bus and up to 160 mA from the load voltage L+ (without load). Typical power loss is 3 W. Short-circuit protection is electronic and per-channel, with a response threshold at minimum 10 mA + 10 %. The module also has reverse polarity protection on the load voltage supply.","metaTitle":"Siemens 6ES7322-5SD00-0AB0 SM 322, 4 DO, Ex(i), EOL","metaDescription":"Siemens 6ES7322-5SD00-0AB0 SM 322 digital output module, 4 channels, 24 V DC, 10 mA, Ex(i) isolated, FM/ATEX rated. End-of-life; sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"120 mm","Width":"40 mm","Height":"125 mm","Product Status":"End of Life"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$438.15 – $662.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cfaff874a9ec5c19a802dcad29772cca.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=406895&mlfb=6ES7322-5SD00-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7322-5SD00-0AB0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7322-5SD00-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7322-5SD00-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}