{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7331-7TB00-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7331-7TB00-0AB0","canonicalUrl":"https://aoctrl.com/siemens/6ES7331-7TB00-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7331-7TB00-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC S7-300 SM 331 analog input module, 2 AI, HART, Ex(i), 24 V DC, 2-wire, 4 to 20 mA, FM/ATEX, 6ES7331-7TB00-0AB0.","salesMarkdown":"## What this module does in a hazardous-area loop The Siemens 6ES7331-7TB00-0AB0 is a 2-channel analog input module designed for intrinsically safe (Ex(i)) 2-wire transmitters in hazardous locations. It accepts 0 to 20 mA or 4 to 20 mA signals, with HART communication active on both channels — indicated by a green LED per channel. The module carries FM approval for Class I, Division 2, Groups A–D T4 and ATEX marking II3 (2) G Eex nA [ib] IIC T4, so it slots into Zone 2 installations with Ex(i) loop-powered field devices without an external barrier. ## End-of-life — sourcing reality No pin-compatible drop-in replacement from Siemens has been published for this exact Ex(i) variant. ## Integration into an S7-300 rack The module occupies one slot in an S7-300 rack — 40 mm wide, 125 mm high, 120 mm deep — and draws 100 mA from the 5 V DC backplane bus plus 4.5 W from the 24 V DC load voltage L+. It is compatible with ET200M distributed I/O via an IM 153-2 interface module, which is the typical deployment for hazardous-area remote I/O. Channel-to-channel isolation is 1 500 V AC, and isolation between channels and the backplane bus is 500 V DC. The 50 Ω input resistance on the 4 to 20 mA range means the loop burden is low enough for most 2-wire transmitters to drive without exceeding compliance voltage. ## Sigma-delta conversion with configurable integration The module uses a sigma-delta measurement principle with parameterizable integration times: 2.5 ms, 16.67 ms, 20 ms, or 100 ms. The 16.67 ms and 20 ms settings reject 60 Hz and 50 Hz line noise respectively — a practical choice when the module shares a panel with VFDs or switching power supplies. Diagnostics are fully parameterizable: a red SF group-error LED, a red F channel-fault LED per channel, and configurable limit-value alarms on channels 0 and 1. Overrange is indicated by a red LED and a signal flag.","metaTitle":"Siemens 6ES7331-7TB00-0AB0 Analog Input Module, 2 AI, HART","metaDescription":"Siemens 6ES7331-7TB00-0AB0 analog input module, 2 channels, HART active, Ex(i) protection, FM/ATEX rated. End-of-life — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"120 mm","Width":"40 mm","Height":"125 mm","Product Status":"End of Life","Measurement Principle":"integrating (Sigma-Delta)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$192.02","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aa98043430345f30f576ec74f153f551.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=110116&mlfb=6ES7331-7TB00-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7331-7TB00-0AB0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7331-7TB00-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7331-7TB00-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}