{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7352-5AH10-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7352-5AH10-0AE0","canonicalUrl":"https://aoctrl.com/siemens/6ES7352-5AH10-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7352-5AH10-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC S7-300 digital output module, order code 6ES7352-5AH10-0AE0, 24 V rated, 2-wire sensor output typ. 1 A, SSI encoder interface, lifecycle stage EOL hot.","salesMarkdown":"## SSI encoder interface and diagnostic depth The 6ES7352-5AH10-0AE0: This module integrates an SSI encoder interface with a 25-bit message frame, accepting DATA/notDATA and CK/notCK differential signals. The monoflop time is settable in four steps — 16, 32, 48, or 64 µs — letting you match the encoder read cycle to the PLC update window. Unshielded cable runs up to 100 m; shielded cable extends to 600 m. That 100 m unshielded limit is the one that bites on a factory floor with variable-frequency drive noise — budget shielded cable for any run past a welding cell. Diagnostic alarm coverage is broad: missing supply on 1L, 2L, 3L, MMC error, output overload (8), encoder supply overload, differential wire break, parameterization error, and SSI message frame overflow. Eight hardware interrupts are available for generation by the user program. For a line-side maintenance planner, the wire-break diagnostic alone saves hours of tracing a dropped encoder signal. ## Output timing and switching limits The 2-wire sensor output is rated typ. 1 A. Switching times: 0 to 1 at 50 mA is 0.6 µs, at 0.5 A is 1.0 µs; 1 to 0 at 50 mA is 1.7 µs, at 0.5 A is 1.5 µs. The maximum on lamp load is 10 Hz. These edges are fast enough for direct drive of a fast-acting solenoid valve on a pick-and-place gripper — the 1 µs rise at 0.5 A keeps the valve spool transition deterministic, holding takt time.","metaTitle":"Siemens 6ES7352-5AH10-0AE0 Digital Output Module, EOL Hot","metaDescription":"Siemens 6ES7352-5AH10-0AE0 digital output module, EOL hot. 24 V, 2-wire sensor output typ. 1 A, SSI encoder interface, monoflop time settable 16-64 µs.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Digital Output Modules"],"specifications":{"5 V":"Yes","24 V":"Yes","Max.":"70 °C","Min.":"-40 °C","Depth":"120 mm","Width":"80 mm","Height":"125 mm","Multiturn":"Yes; 25 bit message frame","Data signal":"DATA, notDATA","Memory size":"128 kbyte; required for operation, MMC","Clock signal":"CK, notCK","For Uprating":"Yes; 2","RUN/STOP LED":"Yes","2-Wire Sensor":"Yes; typ. 1 A","Input voltage":"24 V","Monoflop time":"settable: 16/32/48/64 µs","For Signal \"0\"":"-30 to +5 V","For Signal \"1\"":"+11 to +30V","Listening mode":"Yes; one or two stations","Shielded, Max.":"600 m","Type of memory":"RAM","Updating times":"PLC interface: 5 ms (2.6 ms type)","Weight, approx.":"434 g; Module weight: approx. 434 g (with 1L connection and without I/O connection or MMC); shipping weight: approx. 500 g (with bus and 1L connection and without I/O connection or MMC)","lifecycle_stage":"eol_hot","\"0\" To \"1\", Max.":"1 µs; 0.6 µs 50 mA / 1.0 µs 0.5 A","\"1\" To \"0\", Max.":"1.5 µs; 1.7 µs 50 mA / 1.5 µs 0.5 A","Current-sourcing":"Yes","Diagnostic alarm":"Yes; 1L, 2L, 3L missing; MMC error; output overload (8); encoder supply overload; differential wire break; parameterization errror; SSI message frame overflow","Power loss, typ.":"6.5 W","Rated value (DC)":"24 V","Unshielded, Max.":"100 m","Zero mark signal":"N","Hardware interrupt":"Yes; 8 available; for generation by user program","On Lamp Load, Max.":"10 Hz","Overflow/underflow":"Yes","Trace mark signals":"A, B","At \"0\" To \"1\", Max.":"3 µs; typ. 1.5 µs","For Signal \"0\", Max.":"28.8 V","For Signal \"1\", Max.":"0.5 V","For Signal \"1\", Typ.":"3.8 mA","Group error SF (red)":"Yes","I/O status IOF (red)":"Yes","Missing Load Voltage":"Yes","Output current, max.":"400 mA","Clock frequency, max.":"1 MHz; 125 kHz, 250 kHz, 500 kHz or 1 MHz","Input frequency, max.":"200 kHz","Absolute encoder (SSI)":"Yes","Counting mode, periodic":"Yes","Number of digital inputs":"8; Standard and up to 12 with 24 V DC encoder inputs as digital inputs","Required Front Connector":"1x 40-pin","Response threshold, typ.":"1.7 to 3.5 A","Short-circuit protection":"Yes; Overvoltage protection, thermal protection","between 1L and 2L and 3L":"Yes; 75 V DC/60 V AC","Counting mode, continuous":"Yes","Counting mode, individual":"Yes","Number of digital outputs":"8","Program cycle time (scan)":"1 µs","With Inductive Load, Max.":"2 Hz; 2 Hz at 0.5 A with external commutator diodes; 0.5 Hz at 0.5 A without external commutator diodes","With Resistive Load, Max.":"100 kHz; 20 kHz at 0.5 A; 100 kHz at 0.25 A","For Signal \"1\" Rated Value":"0.5 A; At 60 °C","from load voltage1L+, max.":"150 mA; typ. 60 mA","Controlling a digital input":"No","Counting direction, forward":"Yes","Counting range, description":"Counting range (16-bit counters): -32 768 to 32 767 (user-specific within this range); counting range (32-bit counters): -2 147 483 648 to 2 147 483 647 (user-specific within this range)","Counting range, lower limit":"-2 147 483 648","Counting range, upper limit":"2 147 483 647","Reverse polarity protection":"Yes","Cable length, shielded, max.":"320 m; Cable length, RS-422 SSI absolute encoders, Siemens type 6FX201-5, 24 V supply: 125 kHz, 320 meters shielded, max.; 250 kHz, 160 meters shielded, max.; 500 kHz, 60 meters shielded, max.; 1 MHz, 20 meters shielded, max.","Counting direction, backward":"Yes","Module supply 5 V DC (green)":"Yes","Input- to output response time":"5 V input to 24 V output, 0 filter: 1 to 4 µs (typ.); 24 V input to 24 V output, 0 filter: 2 to 6 µs (typ.)","from backplane bus 5 V DC, typ.":"100 mA","Telegram length, parameterizable":"13 or 25 bit","Incremental encoder (symmetrical)":"Yes","Micro Memory Card error MCF (red)":"Yes","Programmable Digital Filter Delay":"None, 5 µs, 10 µs, 15 µs, 20 µs, 50 µs, 1.5 ms","Incremental encoder (asymmetrical)":"Yes","Potential separation digital inputs":"Yes; Yes CPU, I/O and sensor units are isolated","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","For Signal \"0\" Residual Current, Max.":"1 mA","Status indicator digital input (green)":"Yes; I 0 to I 11","Wire-break in signal transmitter cable":"Yes","Status indicator digital output (green)":"Yes; Q 0 to Q 7","Minimum pulse width for program reactions":"1 µs, 5 µs, 10 µs, 15 µs, 20 µs, 50 µs, 1,6 ms","from load voltage 2L+ (without load), max.":"200 mA; typ. 60 mA, DI/DO supply","from load voltage 3L+ (with encoder), max.":"600 mA; typ. 80 mA plus encoder supply","from load voltage 3L+ (without load), max.":"200 mA; typ. 80 mA","Limitation of inductive shutdown voltage to":"2M +45 V typ, (40 to 55 V); comment: no protection against inductive kickback >55 mJ","Overload encoder supply voltage 5 V F (red)":"Yes","Overload encoder supply voltage 24 V F (red)":"Yes","Input frequency (with a time delay of 0.1 ms), max.":"200 kHz","Permissible Quiescent Current (2-Wire Sensor), Max.":"1.5 mA","For Signal \"0\", Max. (Permissible Quiescent Current)":"1.5 mA","for signal \"1\" permissible range for 0 to 60 °C, max.":"600 mA","for signal \"1\" permissible range for 0 to 60 °C, min.":"5 mA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$688.09","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=231798&mlfb=6ES7352-5AH10-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7352-5AH10-0AE0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 6ES7352-5AH10-0AE0?","answer":"Submit an RFQ for your BOM quantity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7352-5AH10-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7352-5AH10-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}