{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6ES7522-1BP00-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"6ES7522-1BP00-0AA0","canonicalUrl":"https://aoctrl.com/siemens/6ES7522-1BP00-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/6ES7522-1BP00-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens S7-1500 digital output module, 6ES7522-1BP00-0AA0, 16 channels, 24 V DC, 8 A total, 35 mm wide.","salesMarkdown":"The 6ES7522-1BP00-0AA0: The 8 A total current limit at 60 °C is the module-wide budget, not per-channel. With 16 channels, each output is good for about 0.5 A continuous if evenly loaded; for heavier single loads, you'll need to parallel channels while staying under the module total. Signal \"1\" is guaranteed at L+ minus 0.8 V, keeping thresholds tight even on longer runs. Response times are 100 µs turn-on and 500 µs turn-off. ## No-frills output module No diagnostic alarm, no wire-break or short-circuit detection, no PWM or isochronous mode. The red ERROR and green RUN LEDs give basic status. Firmware is V1.0.0 and field-updatable. This module is for simple on/off loads (valves, contactors, indicators) where fault feedback is handled elsewhere.","metaTitle":"Siemens 6ES7522-1BP00-0AA0 Digital Output Module, 24 V DC, 8","metaDescription":"Siemens S7-1500 digital output module, 16 channels, 24 V DC, 8 A total, 35 mm wide. Current production – order via RFQ for your BOM line.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Digital Output Modules"],"specifications":{"DQ":"Yes","MSO":"Yes","PWM":"No","Depth":"129 mm","Note:":"Please order cable and connection modules separately","Width":"35 mm","Height":"147 mm","RUN LED":"Yes; green LED","I&M data":"Yes; I&M0 to I&M3","ERROR LED":"Yes; red LED","MAINT LED":"No","Wire-break":"No","Group error":"No","Lower Limit":"80 Ω","Upper Limit":"10 kΩ","For Uprating":"No","Oversampling":"No","Short-circuit":"No","Shielded, Max.":"1 000 m","Current-sinking":"No","For Logic Links":"Yes","Weight, approx.":"270 g","lifecycle_stage":"current","\"0\" To \"1\", Max.":"100 µs","\"1\" To \"0\", Max.":"500 µs","Current-sourcing":"Yes","Diagnostic alarm":"No","Firmware version":"V1.0.0","Isochronous mode":"No","Power loss, typ.":"3.5 W","Rated value (DC)":"24 V","Unshielded, Max.":"600 m","FW update possible":"Yes","On Lamp Load, Max.":"10 Hz","up to 40 °C, max.":"8 A","up to 60 °C, max.":"8 A","Prioritized startup":"No","Between The Channels":"No","Diagnostics function":"No","For Signal \"1\", Min.":"L+ (-0.8 V)","HW functional status":"From FS01","Isolation tested with":"707 V DC (type test)","Maintenance interrupt":"No","SIL acc. to IEC 62061":"SIL 2","Channel status display":"Yes; via SIMATIC TOP connect connection module","For Module Diagnostics":"No","Type of digital output":"Transistor","Current per group, max.":"2 A","For Channel Diagnostics":"No","Current per module, max.":"8 A","Short-circuit protection":"Yes","Current consumption, max.":"90 mA; without load","Current per channel, max.":"0.3 A","Number of digital outputs":"64","With Inductive Load, Max.":"0.5 Hz; According to IEC 60947-5-1, DC-13","With Resistive Load, Max.":"100 Hz","For Signal \"1\" Rated Value":"0.3 A","Controlling a digital input":"Yes","Reverse polarity protection":"Yes; through internal protection with 7 A per group","Vertical Installation, Max.":"40 °C","Vertical Installation, Min.":"-30 °C","Horizontal Installation, Max.":"60 °C","Horizontal Installation, Min.":"-30 °C","Monitoring the supply voltage":"No","Substitute values connectable":"No","Suitable for safety functions":"No","DQ with energy-saving function":"No","For Redundant Control Of A Load":"Yes","Digital outputs, parameterizable":"No","Category according to ISO 13849-1":"Cat. 3","Between The Channels, In Groups Of":"16; 32 when using SIMATIC TOP connect connection module","Integrated operating cycle counter":"No","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","For Signal \"0\" Residual Current, Max.":"0.5 mA","Between The Channels And Backplane Bus":"Yes","For Signal \"1\" Permissible Range, Max.":"0.3 A","PROFIBUS from GSD version/GSD revision":"V1.0 / V5.1","PROFINET from GSD version/GSD revision":"V2.35 / -","Power available from the backplane bus":"0.6 W","Monitoring of the supply voltage (PWR-LED)":"Yes; via SIMATIC TOP connect connection module","Performance level according to ISO 13849-1":"PL d","Installation altitude above sea level, max.":"5 000 m","Limitation of inductive shutdown voltage to":"L+ (-53 V)","STEP 7 configurable/integrated from version":"V5.5 SP3 / -","Cam control (switching at comparison values)":"No","STEP 7 TIA Portal configurable/integrated from version":"V16 with HSP 0319 / V17","Suitable for safety-related tripping of standard modules":"Yes; From FS01","External Protection For Power Supply Lines (Recommendation)":"24 V DC/6 A miniature circuit breaker with type B tripping characteristic"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$571.00 – $962.18","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8eb6c4216dc4208d80e67a8b78e590f0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1448136&mlfb=6ES7522-1BP00-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6ES7522-1BP00-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What does MSO = Yes mean?","answer":"MSO = Yes indicates the module supports Modular Slice Object, enabling unified data access in TIA Portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6ES7522-1BP00-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6ES7522-1BP00-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}