{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6SL3200-6AM13-1BH0","brand":"Siemens","brandSlug":"siemens","productSlug":"6SL3200-6AM13-1BH0","canonicalUrl":"https://aoctrl.com/siemens/6SL3200-6AM13-1BH0","factsUrl":"https://aoctrl.com/api/mcp/products/6SL3200-6AM13-1BH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120P, FSA, IP55, Filter B, 1.1 kW variable speed drive, order code 6SL3200-6AM13-1BH0.","salesMarkdown":"The Siemens 6SL3200-6AM13-1BH0 is a SINAMICS G120P variable speed drive in frame size FSA, rated for 1.1 kW power output at 400 V operating voltage and delivering 3.1 A output current. It carries an integrated Filter B, making it suitable for environments where conducted emissions need to be suppressed per EN 61800-3 — that standard covers power drive systems and their EMC limits, so this unit is pre-configured for installations where line-side filtering is required without an external box. The 1.1 kW power output at 3.1 A is sized for a 400 V three-phase supply. Output frequency ceiling is 550 Hz. Overload capacity is 110% for 57 seconds and 150% for 3 seconds, repeating every 300 seconds. That 150% burst handles short-duration torque spikes — a jammed conveyor or a fan restart against a closed damper — without tripping. The 57-second window at 110% covers moderate overloads like a pump cycling against a partially closed valve. IP55 degree of protection means the drive is dust-protected and can withstand water jets from any direction. This unit is built for standalone mounting in washdown areas or outdoor cabinets — no need for a separate enclosure in most indoor industrial environments, though direct hose-down still requires the cable glands to be properly sealed. The drive supports Modbus/RTU, RS485/USS, and BACnet MS/TP natively, with optional PROFIBUS, PROFINET, and CANopen via add-on modules. For a building-automation or HVAC application, the onboard BACnet MS/TP is the direct fit — it talks to a BMS without a gateway. For a factory-floor line, the optional PROFINET card is the usual choice. It carries 4 analog inputs, 2 analog outputs, and 6 digital inputs. That is enough for a basic PID loop (one analog input for feedback, one analog output for speed reference) plus a handful of start/stop and fault-reset signals. No analog expansion is needed for simple pressure or flow control. It is a mature product in the SINAMICS G120P line. The drive carries CE, EAC, and RCM conformity marks. The EN 61800-3 standard covers EMC performance for power drive systems.","metaTitle":"Siemens 6SL3200-6AM13-1BH0 G120P VFD, 1.1 kW, IP55, Filter B","metaDescription":"Siemens 6SL3200-6AM13-1BH0 variable speed drive, G120P FSA, 1.1 kW output, IP55, integrated Filter B, 400 V, 3.1 A. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Standard":"EN 61800-3","Frequency":"50/60 Hz","Data sheet":"N5111","Filter type":"B","Power output":"1.1 kW","Weight (net)":"5.01 kg","Communication":"Modbus/RTU; RS485/USS; BACnet MS/TP; PROFIBUS (optional); PROFINET (optional); CANopen (optional)","Output current":"3.1 A","lifecycle_stage":"mature","Output frequency":"550 Hz","Operating voltage":"400 V","Overload capacity":"110% for 57 sec. and 150% for 3 sec. every 300 sec.","Product conformity":"CE; EAC; RCM","Degree of protection":"IP55","Analog inputs, number":"4","Analog outputs, number":"2","Digital inputs, number":"6","Dimensions (W x H x D)":"154 x 460 x 249 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=342614&mlfb=6SL3200-6AM13-1BH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6SL3200-6AM13-1BH0/alternatives.json"},"ai":{"faq":[{"question":"What is the EN 61800-3 standard listed on this drive?","answer":"EN 61800-3 is the EMC standard for power drive systems. It defines emission and immunity limits for adjustable-speed drives. The integrated Filter B on this unit addresses the conducted emission requirements of that standard."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6SL3200-6AM13-1BH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6SL3200-6AM13-1BH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}