{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6SL3210-1PE27-5UL0","brand":"Siemens","brandSlug":"siemens","productSlug":"6SL3210-1PE27-5UL0","canonicalUrl":"https://aoctrl.com/siemens/6SL3210-1PE27-5UL0","factsUrl":"https://aoctrl.com/api/mcp/products/6SL3210-1PE27-5UL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120 Power Module PM240-2, blocksize format FSD, 30 kW high overload / 37 kW low overload, 3AC 380-480 V, IP20, without filter, with built-in braking chopper.","salesMarkdown":"## Duty ratings that drive the selection The 6SL3210-1PE27-5UL0: Rated for 30 kW high overload (HO) with a duty cycle of 200 % for 3 s, 150 % for 57 s, and 100 % for 240 s at an ambient temperature of -20 to +50 °C — this is the spec that governs the real-world starting and acceleration torque for a pump or conveyor. Low overload (LO) rating is 37 kW with 150 % for 3 s, 110 % for 57 s, and 100 % for 240 s at -20 to +40 °C ambient — use this for constant-torque loads that don't need the peak headroom. Input supply is 3-phase 380-480 V AC +10/-20 %, 47-63 Hz, covering the standard global industrial mains range without needing a transformer tap change. ## Cabinet integration and control-unit dependency IP20 protection means this module is intended for enclosure mounting — no washdown or outdoor exposure without a separate cabinet. The PM240-2 ships without a Control Unit (CU) or operator panel; you must order the matching CU separately and pair it with firmware version V4.7 HF8 or later for full compatibility. Built-in braking chopper handles regenerative energy from fast deceleration — no external braking module needed for most duty cycles. ## Compliance and substance disclosure RoHS compliant since 01-01-17; the REACH Article 33 candidate list includes lead (CAS 7439-92-1) above 0.1 % w/w, which must be declared in the supply chain documentation.","metaTitle":"Siemens 6SL3210-1PE27-5UL0 SINAMICS G120 PM240-2, 30 kW HO","metaDescription":"Siemens 6SL3210-1PE27-5UL0 SINAMICS G120 Power Module PM240-2, 30 kW high overload / 37 kW low overload, 380-480 V, IP20, active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drives (VFD)"],"specifications":{"title":"6SL3210-1PE27-5UL0","Group Code":"R220","description":"SINAMICS G120 POWER MODULE PM240-2 WITHOUT FILTER WITH BUILT IN BRAKING CHOPPER 3AC380-480V +10/-20% 47-63HZ OUTPUT HIGH OVERLOAD: 30KW FOR 200% 3S,150% 57S,100% 240S AMBIENT TEMP -20 TO +50 DEG C (HO) OUTPUT LOW OVERLOAD: 37kW FOR 150% 3S,110% 57S,100% 240S AMBIENT TEMP -20 TO +40 DEG C (LO) 472 X 200 X 237 (HXWXD), FSD PROTECTION IP20 WITHOUT CONTROL UNIT AND PANEL APPROVED FOR CU FIRMWARE- VERSION V4.7 HF8","Product Group":"9775","Product class":"A: Standard product which is a stock item could be returned within the returns guidelines/period.","Quantity Unit":"1 Piece","Product Family":"Air-cooled Power Modules in blocksize format","lifecycle_stage":"mature","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : 9N9999","Packaging dimensions (L x W x H)":"495.00 x 356.00 x 300.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 01-01-17","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,471.42 – $2,624.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://mall.industry.siemens.com/mall/Document/GetDocumentBasedOnCode?code=aHR0cHM6Ly9tYWxsLmluZHVzdHJ5LnNpZW1lbnMuY29tL3NwaWNlL2RvY3VzZXJ2aWNlL2RvY3VzZXJ2aWNlP2NvbmZpZ2lkPTE0JmRvY3UubWxmYj02U0wzMjEwLTFQRTI3LTVVTDAmZG9jdS5pbml0dHlwZT1NTEZCJmRvY3UuZ2VuZXJhdGlvbnR5cGU9VklFVyZkb2N1LnZpZXdpZD1QREYmcmVnaW9uPUFFJmxhbmd1YWdlPWVuJmRvY3UubGFuZ3VhZ2UubG9jYWxlMT1lbiZkb2N1Lmxhbmd1YWdlLmxvY2FsZTI9ZW4=', 'path_name': 'e3a8a7d6d766c437a06afba31137f8cc.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/sieportal_siemens/e3a8a7d6d766c437a06afba31137f8cc.pdf', 'status': 1}","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=472519&mlfb=6SL3210-1PE27-5UL0"},"ai":{"faq":[{"question":"What is the difference between high overload and low overload ratings on this drive?","answer":"High overload (HO) delivers 30 kW with 200 % torque for 3 s, suitable for starting high-inertia loads; low overload (LO) delivers 37 kW continuous with 150 % for 3 s, for constant-torque applications where peak current is lower."},{"question":"Does the 6SL3210-1PE27-5UL0 include a Control Unit or operator panel?","answer":"No, it is a Power Module only — you must order a separate Control Unit (CU) and optional operator panel. The module is approved for CU firmware version V4.7 HF8."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6SL3210-1PE27-5UL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6SL3210-1PE27-5UL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}