{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6SL3211-1NE17-7UG1","brand":"Siemens","brandSlug":"siemens","productSlug":"6SL3211-1NE17-7UG1","canonicalUrl":"https://aoctrl.com/siemens/6SL3211-1NE17-7UG1","factsUrl":"https://aoctrl.com/api/mcp/products/6SL3211-1NE17-7UG1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120 PM230 power module, 6SL3211-1NE17-7UG1, unfiltered, IP20/PT, 380-480 V 3 AC, 3 kW low overload, FSA frame.","salesMarkdown":"## Power module for the G120 family The Siemens 6SL3211-1NE17-7UG1 is a SINAMICS G120 PM230 Power Module in the FSA frame size, designed as a spare part for the G120 drive platform. It runs on 380-480 V 3 AC, 47-63 Hz, and delivers 3 kW under low overload (LO) conditions — meaning it can handle 150% overload for 3 seconds, 110% for 57 seconds, and 100% continuously over 240 seconds, all at an ambient temperature of 0 to +40 °C. The 3 kW low-overload rating is the key selection parameter here: this module is sized for a 3 kW motor running a constant-torque load like a conveyor or pump, where short bursts of extra torque (150% for 3 seconds) are needed for starting or brief overloads. The 110% for 57 seconds covers longer, moderate overload events — think a crusher jam or a sticky roller. The 100% continuous rating means it can run at full rated current indefinitely within the 40 °C ambient limit. The FSA frame size (238 x 126 x 171 mm, HxWxD) is the smallest in the PM230 family, so it fits in compact panel layouts. This module mounts in a standard enclosure on a backplate — no DIN rail. It ships without a Control Unit or operating unit, so you pair it with a CU240B/E-2 or CU230P-2 at firmware V4.4 or higher. The unfiltered variant means it does not include an internal EMC filter, so plan for an external line filter if the installation must meet conducted-emission limits (EN 61800-3 Category C2 or C3, depending on cable length and environment).","metaTitle":"Siemens 6SL3211-1NE17-7UG1 SINAMICS G120 PM230 Power Module,","metaDescription":"Siemens 6SL3211-1NE17-7UG1 SINAMICS G120 PM230 power module, 3 kW low overload at 380-480 VAC. Mature lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["AC Drives (VFD)"],"specifications":{"lifecycle_stage":"mature"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cfc679bb6584a136b7edfb2519b7b1ce.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=697054&mlfb=6SL3211-1NE17-7UG1","alternativesUrl":"https://aoctrl.com/api/mcp/products/6SL3211-1NE17-7UG1/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 6SL3211-1NE17-7UG1?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What control units are compatible with 6SL3211-1NE17-7UG1?","answer":"It is released for CU240B/E-2 and CU230P-2 control units running firmware version V4.4 or higher. The module ships without a control unit, so you must order one separately."},{"question":"What is the overload profile of this power module?","answer":"Under low overload, it delivers 150% rated current for 3 seconds, 110% for 57 seconds, and 100% continuous for 240 seconds, all at 0 to +40 °C ambient. This suits constant-torque loads with short-duration overload events."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6SL3211-1NE17-7UG1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6SL3211-1NE17-7UG1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}