{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6SL3220-1YH62-0CB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6SL3220-1YH62-0CB0","canonicalUrl":"https://aoctrl.com/siemens/6SL3220-1YH62-0CB0","factsUrl":"https://aoctrl.com/api/mcp/products/6SL3220-1YH62-0CB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120X infrastructure converter, 6SL3220-1YH62-0CB0, 450 kW, 3AC 500-690 V, IP20, Size FSH, with integrated MODBUS RTU, BACnet MS/TP, USS.","salesMarkdown":"## 450 kW overload profile for pump and fan duty The 6SL3220-1YH62-0CB0 is a SINAMICS G120X infrastructure converter rated 450 kW with a 135% overload for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — a profile matched to centrifugal pump and fan starting torque where the peak demand is brief and the continuous load stays near the nameplate. It accepts 3-phase 500-690 V AC +10/-20% at 47-63 Hz, covering the common 575 V and 690 V industrial grids in North America and Europe without an external transformer. ## Fieldbus integration for building automation The drive ships with integrated MODBUS RTU, BACnet MS/TP, and USS protocols on the standard communication port — no option module needed for connection to a BAS controller or a water/wastewater SCADA system. No IO expansion or operator panel is included in the base unit; the control terminals and fieldbus interface handle start/stop, speed reference, and status feedback for remote operation. ## Panel mounting and cooling in Size FSH The FSH frame size with IP20 / UL open type protection requires mounting inside a ventilated enclosure — the drive relies on forced-air cooling from its internal fans, so the cabinet must allow free airflow through the heatsink fins and maintain ambient temperature between 0 and 45 °C. ## Compliance and export documentation RoHS compliant since March 2020, with a REACH Article 33 declaration for lead content above 0.1% w/w — the lead CAS-No. 7439-92-1 is present in certain component alloys and must be declared in the supply chain documentation. Export Control Classification is AL:N / ECCN:EAR99H, meaning no special export license is required for most destinations under US and EU regulations.","metaTitle":"Siemens 6SL3220-1YH62-0CB0 SINAMICS G120X VFD, 450 kW","metaDescription":"Siemens 6SL3220-1YH62-0CB0 SINAMICS G120X AC drive, 450 kW at 135% overload, 3AC 500-690 V, IP20, MODBUS/BACnet. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drives (VFD)"],"specifications":{"Group Code":"R220","Product Group":"4R53","Product class":"C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.","Quantity Unit":"1 Piece","Product Family":"SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater","lifecycle_stage":"mature","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : EAR99H","Packaging dimensions (L x W x H)":"800.00 x 1,870.00 x 600.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 11-03-20","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://sieportal.siemens.com/en-ae/products-services/detail/6SL3220-1YH62-0CB0?tree=CatalogTree","alternativesUrl":"https://aoctrl.com/api/mcp/products/6SL3220-1YH62-0CB0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6SL3220-1YH62-0CB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6SL3220-1YH62-0CB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}